Hearth & Home IntelliFire IFT-RC150 Скачать руководство пользователя страница 8

Hearth & Home Technologies  •  RC150 IntelliFire

 Touch Installation Instructions  •  2326-980  •  9/16

8

Symptom

Possible Cause

Corrective Action

Pilot sparks for 60 sec, but will not 

light, 3 Red/1 Green Lockout.

No gas supply.

Verify incoming as line ball valve is ‘Open’.  Verify inlet pressure 

is within requirement for gas type used.  Contact gas supplier.

ECM has poor ground.

Verify wiring, check valve harness black wire is securely 

grounded to metal chassis.

Gas valve defective.

Check pilot valve solenoid kick and hold voltages during igni-

tion cycle.  Kick V should be >1 V, hold V minimum 0.26 V.  If 

voltages are OK, replace gas valve.

Pliot lights but main burner does 

not light.   Pilot continues to spark 

for 60 sec then goes into 3 Red/1 

Green Lockout.

No flame detected. Flame 

rectification issue.

Check if white sense lead is securely connected to ‘S’ terminal 
of 

IFT-

ECM.  Check resistance of sense lead between sense 

rod tip and connector to 

IFT-

ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

No flame detected or sense 

rod contamination. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.

Pilot lights and rectifies, but main 

burner does not light.

Main valve solenoid.

Check if green wire in valve harness is connected to green 

main valve solenoid.  Check main valve solenoid resistance, 

nominal is 60 ohms.  If open or shorted, replace valve.  Verify 

valve inlet pressure is correct for gas type.

Pilot and main do not light, ECM 

goes into 5 Red/1 Green Lockout.

Power Vent (PV) Failure.

Power Vent blower defective - check wiring to 

IFT-

ACM, check 

if blower is working.  Check if PV pressure switch is connected 

to brown and black wire in 6-pin valve wire harness.  Check if 

pressure switch is closed (shorted) when PV blower is running.  

Refer to PV troubleshooting instructions. 

Appliance lights and runs for a few 

minutes then shuts down and/or 

appliance cycle ON and OFF with 

less than 60 sec of ON time. 

Shorted or loose connection in 

flame detection circuit.

Check if white sense lead is securely connected to ‘S’ terminal 
of 

IFT-

ECM.  Check resistance of sense lead between sense 

rod tip and connector to 

IFT-

ECM, should be less than 1 ohm 

- if not, replace pilot assembly.  Check system ground, ensure 

black valve harness wire is securely attached to metal chassis.  

Check wiring for damage.  With system OFF, check resistance 

between tip of sense rod and pilot hood, should be resistance 

(>1 M-ohm). 

Poor flame rectification or 

contaminated sense rod. 

With  glass  assembly  installed,  verify  pilot  flame  is  engulfing 

flame sense rod on pilot assembly.  Verify inlet gas pressure 

is correct for gas type.  Polish flame sense rod with fine steel 

wool to remove any contaminants that may have accumulated.  

Verify no soot deposits are in sense rod to pilot hood gap.

Logs are set up wrong. 

Remove and re-install logs per the log placement instructions.

Damaged pilot assembly.

Verify the pilot assembly ceramic insulators around the flame 

sensing rod is not cracked, damaged or loose.  Check re-
sistance between tip of sense rod and 

IFT-

ECM connector, 

should be less than 1 ohm.  Replace pilot assembly if damage 

is detected.

Troubleshooting 

(continued)

Содержание IntelliFire IFT-RC150

Страница 1: ...nd or use of any component part not approved by Hearth Home Technologies Any such action may cause a fire hazard Read understand and follow these instructions for safe installation and operation B Determine Location Determine the location for the IFT RC150 The selected location should be in the same space as the gas appli ance with visual sight of the appliance The device must be placed within 30 ...

Страница 2: ...3 2 On the IFT ECM move the ON OFF REMOTE switch to the REMOTE position The green LED will blink three times A few seconds later an audible beep will occur to indicate that the system is ready Note If the green LED continues to blink slowly system is searching for a clear channel wait until it stops before proceeding to step 3 3 Locate the pairing hole on the IFT ECM See Figure 4 Using a paper cli...

Страница 3: ...GNITER ADAPTER I S 6 PIN 6V DC BATTERY PACK RED BLK BRN ORANGE PILOT GREEN MAIN BLK RED IFT RC150 WIRELESS WALL SWITCH RF MODULE ELECTRONIC CONTROL MODULE VALVE OPTIONAL WIRE ASSEMBLY MODULE RESET SWITCH APPLIANCE ON OFF CONTROL BRN BLK OPTIONAL ON SOME MODELS ONLY SPLITTER BLK RED F Wiring Diagram IntelliFire Touch System Wiring Diagram ...

Страница 4: ...wer source in the event of a power outage Batteries should not be used as a primary long term power source A Turn Flame ON OFF To turn the flame ON press the top of the rocker switch To turn the flame OFF press the bottom of the rocker switch The IFT ECM on the appliance has a safety feature that automatically shuts down the appliance after 9 hours of continuous operation without receiving a comma...

Страница 5: ...ve IFT ECM or RF module Manually turn OFF the appliance following steps listed under 3E and contact your dealer The IFT RC150 LED blinks randomly even though no command is given Communicating with IFT ECM This is normal operation The IFT RC150 com municates periodically with the IFT ECM to send or receive information The IFT RC150 LED blinks in a pattern of every 3 seconds continuously for longer ...

Страница 6: ...wired wall switch IFT RC400 or IFT RC150 The wired wall switch is NOT available if a Power Vent is used 3 The Pilot button on the IFT ECM activates the Cold Climate function of the fireplace This function lights the pilot flame ONLY to provide enough heat in the firebox to reduce condensation in cool high humidity ambient conditions To activate the Cold Climate function press and hold the Pilot bu...

Страница 7: ...or or no system ground Verify black gound wire in valve harness is connected to metal chassis of fireplace Pilot won t light there is no noise or spark 2 Red 1 Green Lockout Pilot solenoid not detected Check if valve harness orange wire is connected to pilot so lenoid valve Check pilot solenoid resistance nominal is 40 ohms If open or shorted replace valve Check valve harness wire continuity if op...

Страница 8: ... Check main valve solenoid resistance nominal is 60 ohms If open or shorted replace valve Verify valve inlet pressure is correct for gas type Pilot and main do not light ECM goes into 5 Red 1 Green Lockout Power Vent PV Failure Power Vent blower defective check wiring to IFT ACM check if blower is working Check if PV pressure switch is connected to brown and black wire in 6 pin valve wire harness ...

Страница 9: ...ever there is no guarantee that in terference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation b...

Отзывы: