Assembly Instructions M8095-EN
M8095-EN 2020-09
7/13
13.
Calibrate the pressure sensor
with pressure sensor system (BP 1)
Fig. 10: Calibrate the pressure sensor 1
Read off the current
System pressure actual value
under
Display \ Actual value
.
Set the parameter
Pressure sensor 1 offset
under
Service \
Calibrating \ Pressure
according to the following calculation:
Pressure sensor 1 offset
new =
Pressure sensor 1 offset
current
–
System pressure actual value
current
with pressure sensor main line (BP 2)
Fig. 11: Calibrate the pressure sensor 2
Read off the current
Main line pressure
under
Display \
Actual value
Set the parameter
Pressure sensor 2 offset
under
Service \
Calibrating \ Pressure
according to the following calculation:
Pressure Sensor 2 offset
new =
Pressure Sensor 2 offset
current
–
Main line pressure
current
14.
Check calibration pressure sensor
Parameter
System pressure actual value
resp.
Main line
pressure
under
Display \ Actual value
must be 0 bar ± 0,1.
If this is not the case, item calibration pressure sensor must be
repeated.
ATTENTION!
Risk of incorrect calibration!
False calibrations can lead to faults witch the unit.
Therefore:
– Check the calibrations.