background image

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

11

To Select ORP Feed Mode:

The CAT 4000 is programmed at the factory to operate in automatic feed mode as the default set-

ting. Other ORP feed mode selections include off (disabled), and manual on for a fixed interval up to 

25 minutes after which automatic feed will resume.  While in normal operating mode:

Press MENU.

Press DOWN to find the ORP Feed Mode menu item. 

Press ENTER to select ORP Feed Mode.

The current ORP Feed Mode will be displayed:

 

Press UP or DOWN to find the desired selection.

Press ENTER to save your selection.

The controller will automatically return to normal operating mode in 10 seconds.

The “Off” (disabled) mode is useful when servicing ORP feed equipment, or if sanitizer chemical 

supply has been depleted. 

The “Manual On” mode allows constant chemical feed for a fixed interval of up to 25 minutes, use-

ful when the addition of extra chemicals is desired, as well as initial balancing of the water.

Advanced Configuration Options

To Enter The Configuration Setup Menu:

The configuration setup menu contains features which enable the CAT 4000 to be customized to 

the unique characteristics of the application. Optional accessories such as the digital flow meter 

are also activated through this menu.  While in normal operating mode: 

Press MENU.

Press DOWN to find the Configuration Setup menu item. 

Press ENTER to select Configuration Setup.

The Configuration Setup Menu will be displayed:

 

Press DOWN to scroll through menu items. 

Press ENTER to make a selection.

Press MENU to return to the Operating Menu.

The controller will automatically return to normal operating mode in 10 seconds.

     Configuration Setup

     pH Control Mode

     ORP Feed Mode

     Automatic Feed

Содержание CAT 4000

Страница 1: ...ivision Street Elizabeth NJ 07207 www hayward com CAT 4000 Water Quality Controller Owner s Manual 092431A RevE CAT 4000 Contents Introduction 2 Installation 4 Pool Chemistry 7 Configuration 7 SystemM...

Страница 2: ...flow protection WARNING Installation requires a properly located GFI protected receptacle Never use an extension cord for electrical connections to the controller WARNING Always mount controller in a...

Страница 3: ...lity print charts graphs and logs change controller settings and designate contacts for outbound notification via email cell phone or PDA Optional digital flow and level sensors are available to monit...

Страница 4: ...hemical feeding during periods when the filtration system is off or low recirculation flow is detected The Flow Cell provides a convenient location for mounting the pH ORP and Flow sensors while ensur...

Страница 5: ...sing the enclosed tubing and fittings to create a pressure suction loop line Follow the directions below for installation and refer to the Installation Diagram on page 6 1 Turn off heater chemical fee...

Страница 6: ...rs are to be used with the controller install according to manufacturer s instructions at this time 11 Connect chemical feeders to the controller as labeled See diagram on following page 12 Check all...

Страница 7: ...AT CO2 pH Control Erosion Feeder or or Chemical Pump Chemical Pump pH Feed Output Power Cord ORP Feed Output Influent to Return Line Effluent to Suction CAT 4000 SYSTEM CAT Controllers SUCTION LINE PU...

Страница 8: ...as pH cyanuric acid concentration and total dissolved solids can affect sanitizer residual readings relative to ORP CAT Controllers recommends establishing desired pH sanitizer residual calcium hardn...

Страница 9: ...ing Mode During normal operating mode the display will indicate sensed pH ORP Flow Rate with optional digital flow sensor and a status line which alternates between a System OK or a list of any alarm...

Страница 10: ...played Press UP or DOWN to select the desired pH Press ENTER to save your selection The controller will automatically return to normal operating mode in 10 seconds To Calibrate pH The CAT 4000 is far...

Страница 11: ...adding extra chemicals is desired and during initial balancing of the water NOTE Always disconnect chemical feeder power cords prior to performing any electrical service To Change The ORP Setpoint The...

Страница 12: ...s been depleted The Manual On mode allows constant chemical feed for a fixed interval of up to 25 minutes use ful when the addition of extra chemicals is desired as well as initial balancing of the wa...

Страница 13: ...ating mode in 10 seconds NOTE In certain unusual applications pH correction may be required in both acid feed and base feed modes The third relay can be programmed as described later in this manual to...

Страница 14: ...on a fixed basis From the Configuration Setup Menu Press DOWN to find the pH Feed menu item Press ENTER to select pH Feed The current pH Feed setting will be displayed Press UP or DOWN to select Prop...

Страница 15: ...the pH setpoint is not reached after feeding continuously for a selectable period of time From the Configuration Setup Menu Press DOWN to find the pH Overfeed Timeout menu item Press ENTER to select...

Страница 16: ...election ORP Mixing Time On This feature prevents the controller from receiving inaccurate readings due to chemicals passing directly through the flow cell and over the sensors before being injected i...

Страница 17: ...setting Press ENTER to save your selection ORP Low Alarm The ORP Low Alarm inhibits ORP feed sounds audible and visual alarms and sends a message to the POOLCOMM website during a low ORP condition Fr...

Страница 18: ...recommends always having the Overfeed Timeout functions enabled as a precaution ary measure By disabling the Overfeed Timeout the overfeeding of chemicals could occur and create unsafe water chemistry...

Страница 19: ...e Configuration Setup Menu Press DOWN to find the Alarm Setup menu item Press ENTER to select Alarm Setup The current Alarm Setup option will be displayed Press UP or DOWN to scroll to the desired set...

Страница 20: ...Output selection will be displayed Press UP or DOWN to scroll to the desired setting Press ENTER to save your selection Level Flow Sensor Input 3 Setup The third Level Flow Sensor input is provided t...

Страница 21: ...will inhibit chemical feed From the Configuration Set Up Menu Press DOWN to find the Digital Flow Alarm item Press ENTER to select Digital Flow Alarm The current Digital Flow Alarm setting will be dis...

Страница 22: ...ve firmware issues with your controller From the Configuration Setup Menu Press DOWN to find the Update FW via BL Menu item Restore Factory Defaults The Restore Factory Defaults function erases all us...

Страница 23: ...ENTER to select Demo The current status of Demo Mode will be displayed Press UP or DOWN to make a selection Press ENTER to save your selection The controller will revert to the Configuration Setup Men...

Страница 24: ...arm pH Overfeed Timer ORP Feed ORP Low Alarm ORP High Alarm Acid Feed Base Feed Off On Proportional Fixed 0 0 to 14 0 Default 7 0 pH 0 0 to 14 0 Default 8 0 pH Off 5 to 240 Minutes Default 240 Min Pro...

Страница 25: ...ow Sensor Level Flow Sensor 3 On for Specified Time Level Flow Input 3 Setup Digital Flow Pipe Size Digital Flow Alarm Digital Flow Sensor Type Display System Information Update FW via BL Restore Fact...

Страница 26: ...and free from oil chemical deposits and contamination to function properly After saturation in pool or spa water the sensors may need to be cleaned on a weekly or monthly basis depending on bather lo...

Страница 27: ...d Satellite All CAT controllers set up on Cell and Satellite networks come already activated for wireless com munication Once the unit has been installed and registered on www poolcomm com the devices...

Страница 28: ...lick on Register Account and complete all requested account information Click on Register Account again to register with the system The next screen will then inform you that your account has been crea...

Страница 29: ...during the past 24 hours Red A warning condition currently exists Facility Name This field provides a list of facilities automated with CAT 4000 wireless controllers Click on a facil ity name to enter...

Страница 30: ...from the Unit Profile screen Site Location This field is used to identify the specific asset being monitored main pool lap pool spa etc within the facility Last Warning This field provides a timestam...

Страница 31: ...CAT 4000 has been feeding chemicals for a time greater than the selected maximum feed time and has not reached its setpoint A properly selected Overfeed timeout prevents the unit from continuing to fe...

Страница 32: ...arm setting can be entered in gallons per minute to send a No Flow alarm when the filters require cleaning or backwashing Service Request The Transmit button on the CAT 4000 sends logged data to the P...

Страница 33: ...l Flow Sensor 3 Time based Activation Communications Bi directional Wireless Internet URL http www poolcomm com Latency 2 Minutes per Path Alarm Format Email Text Message Internet Safety Systems pH Lo...

Страница 34: ...USE ONLY HAYWARD GENUINE REPLACEMENT PARTS 33...

Страница 35: ...ibutor Liability under this warranty is limited to the repair or replacement of any device or component which is returned to the factory within one year of delivery to original pur chaser shipping pre...

Страница 36: ...hnical support visit our website at www hayward com CONTENTS COPYRIGHT 2016 HAYWARD INDUSTRIES INC ALL RIGHTS RESERVED All other trademarks not owned by Hayward are the property of their respective ow...