9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Troubleshooting
1.
No response to buttons
: Check that the Pro Logic/Aqua Logic has input power and the
AQL-SS-6B/D cable is correctly wired to the terminal block according to page 4. If OK,
cycle the Pro Logic/Aqua Logic’s power off and on. If using the AQL-SS-6B and Aqua Logic
software version 2.40 or greater, make sure that the buttons are properly configured in the
configuration menu (page 5 - 6).
2.
“Er1” on display (AQL-SS-D only)
: An AQL-SS-D is connected to a Pro Logic or Aqua
Logic P-4. The AQL-SS-D is not compatible with any model P-4. Disconnect the AQL-SS-D
and use an AQL-SS-6B if a spa side remote control is desired.
This error also occurs if a spaside remote control is connected to a Pro Logic or Aqua Logic
PS without first turning off power. If this is the case, cycle power on the Pro Logic/Aqua
Logic and the remote control should be recognized.
3.
“Er2” on display (AQL-SS-D only)
: The most likely cause of this problem is a broken black
and/or white wire or “open circuit” between the display/keypad and the Pro Logic/Aqua Logic
main control unit. If you are unable to find the problem, contact the Goldline Technical Sup-
port department Monday through Friday, from 8AM to 8PM eastern time.
4.
“Er3” on display (AQL-SS-D only)
: The black and white wires are reversed. Reverse these
two wires to fix the problem. If this doesn’t take care of the problem, contact the Goldline
Technical Support department.
5.
Two blinking backlights (AQL-SS-6B only)
: The most likely cause of this problem is a bro-
ken black and/or white wire or “open circuit” between the display/keypad and the Pro Logic/
Aqua Logic main control unit. If you are unable to find the problem, contact the Goldline
Technical Support department.
6.
Three blinking backlights (AQL-SS-6B only)
: The black and white wires are reversed.
Reverse these two wires to fix the problem. If this doesn’t take care of the problem, contact
the Goldline Technical Support department.
7.
Wrong response to buttons
: Check that the Pro Logic/Aqua Logic is in the proper mode,
either “Pool and Spa -Std” or “Pool and Spa - Dual”.
8.
Erratic Operation
: If the operation appears erratic, turn off input power to the unit, wait one
minute, then power back up. This should reset the microprocessor and return operation to
normal.