-9-
Checking the valve
•
Remove the position indicator from valve cover.
•
Check that the valve spindle moves easily by raising and lowering it with the threaded rod.
•
Install the optical position indicator.
Putting the valve back into service
•
see chapter
Commissioning
Checking the operation of the valve
The pressure-sustaining valve has to be set eventually in such a way for the check that the inlet pressure
permits the opening of the valve (see also the Chapter:
Commissioning
).
•
Close the ball valve
(2C)
slowly
; Valve must close.
•
Open the ball valve
(2C)
slowly
; Valve must open.
2.3 Four or five yearly maintenance
Cleaning the strainer in the main supply
•
Unscrew the lid
•
Clean the filter with a brush or cloth, or replace it
•
Refit the filter and screw the lid back on
Cleaning the filter in the control line
•
Unscrew the lid of the filter
•
Clean the filter with a brush or cloth, or replace it
•
Refit the filter mesh and screw the filter lid back on
Main valve (see chapter: Repair kits and spare parts)
•
Undo the fittings of the control line and lay the complete control line aside.
•
Disassemble the Optical Position Indicator and replace the gaskets
•
Undo the screws of the valve cover and remove this valve cover.
•
Visually inspect all inner components for wear, dirt and scaling
•
Clean inner components, seat and inner surfaces including the valve cover
•
Disassembly the spindle guide at the housing, rinse the housing interior.
For valves from DN 40 to DN 100 built in 2012 and DN 125 to DN 200 built in 2014, the spindle
guide has to be removed from inside of the housing. The guiding thread of the spindle and the base
valve must be
extremely clean
. Grease the thread well (eg Food Grease Aqua, Item No. 5292, see
chapter control line parts and accessories).
•
Replace the diaphragm, the O-ring and if necessary also the seat seal
•
Thinly grease the area around the spindle guide with an agent, which is suitable for contact with
foodstuffs. Check for easy movement of the spindle in the housing guide and in the cover guide.
•
Assemble the main valve (See torque table in Annex). During assembly the easy movement of the
spindle must be checked
several times
by actuating the threaded rod.
Disassembling the control valve (see chapter: Repair kits and spare parts)
•
Tip over the adjusting lever
•
Turn the lever counter-clockwise until no resistance from the spring can be felt
•
Remove housing screw
•
Replace the diaphragm, the O-ring and if necessary also the seat seal
•
Visually inspect the inner surfaces of the housing and clean if necessary, including the cover
•
Assemble the control valve (See torque table in Annex).
Содержание HAWIDO 1405
Страница 1: ...manual Pressure retention valve DAV for monitoring third party pressure...
Страница 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Страница 17: ...14 3 3 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Страница 24: ...21 3 6 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Страница 28: ...25...