-5-
3. Venting
Proceed as follows:
Slowly open the inlet gate valve until water flows into the valve. The valve fills with water and the air escapes
via the vent holes. When the valve venting procedure has caused all the air to be expelled from the control
lines, retighten the headless screws. Check that all fittings are sealing properly and tighten if necessary.
Open the inlet valve slowly and completely.
Check:
When the outlet gate valve is opened slightly the valve should close and remain shut. Then close the gate
valve again.
If the valve does not close, the commissioning procedure must be repeated from the preceding chapter
onwards. Special care must be taken here to ensure that the upper valve chamber and control lines are
properly vented.
4. Adjustments Sustainable Pressure
The valve is prepared according to the preceding chapter. The valve is open on the inlet side and closed on
the outlet side.
Proceed as follows:
•
Slowly
open ball valve (2C).The valve then opens and fills the pipe work on the outlet side until a
pressure of 0.4 bar is reached. The valve then closes again.
•
Gradually and slowly
open the gate valve on the outlet side.
•
Slowly turn the adjusting lever of the control valve (6) counter-clockwise until the valve opens
(audible sound of water flow).
•
Check the inlet pressure on the pressure gauge.
•
Step by step tighten the hand wheel of the control valve (6) (½ turn) according the table below.
Note:
Pause between each half turn of the adjusting lever until the hydraulic system has stabilised. Check the
pressure on the pressure gauge on the inlet side.
If the required relief or sustaining pressure has been set, tip over the adjusting lever for fixing.
Spring
Mark
Regulating
pressure
Pressure
change at 1
turn [bar]
Number of
spindel turns
for
p = 1bar
Standard
None
1.5 - 12bar
0.4
2.5
Strong
Yellow
10 - 22bar
0.9
1.1
Light
Blue
0.08
– 5bar
0.08
12.6
Содержание HAWIDO 1405
Страница 1: ...manual Pressure retention valve DAV for monitoring third party pressure...
Страница 14: ...11 3 1 Main valve with stainless steel connection ND 40 to ND 200 drawing 08 12 2011 pl...
Страница 17: ...14 3 3 Control valve pressure sustaining INOX drawing 05 09 2017 pl...
Страница 24: ...21 3 6 Position indicator drawing DN 40 DN 100 DN 125 DN 300 12 03 2014 pl...
Страница 28: ...25...