w w w . h a w k e y e e l e c t r o n i c s . c o m
continue to blink until the depth increases, or the alarm is reset. To reset the
alarm repeat steps 1 thru 5.
N
OTICE
:
Each time the Deep Water Alarm setting is changed you must wait 5
seconds for the depth finder to return to the Normal Operation Mode in
order for the setting to be saved?
KEEL OFFSET
The Keel Offset feature is used to
adjust the depth readings
displayed by the device to
compensate for the depth of the
water required for your vessel to
operate safe (
typically referred to
as your vessel’s “Draft”)
For Example:
If your boat’s draft is 3 feet, the Keel Offset feature should be set
to 3 feet. The device will then subtract 3 feet from the actual depth reading and
display this figure as the depth. If the water depth is 5 feet and the Keel Offset is
set to 3 feet, the depth will be displayed as 2 feet, indicating to the operator that
there is 2 feet of safe operating water.
The maximum Keel Offset setting is 20 FT (6.1 M), and can be set in .1
(1/10th)
Feet or Meter increments. The unit will read “---” when a negative value occurs
due to the Keel Offset subtraction.
W
ARNING
:
If you are unsure of the Draft of your vessel, please consult with the
vessel’s manufacturer before setting the Keel Offset. An improper
Keel Offset setting can cause accidentally grounding of the vessel
and may cause severe damage to the vessel and its passengers.
To set the Keel Offset:
1. Press and hold the "UP" and “DOWN” keys
until the
K/O
indicator begins to blink
(approximately 6 seconds)
.
•
On depth finders with Temperature
press and hold BOTH the “UP” &
“DOWN” keys until
K/O
blinks on the
display.
2. Release the Keys.
DRAFT