Installation
MiniWave
User Manual
5
Mounting
•
Sensor should be mounted 1/3 the diameter of the
vessel from the vessel wall
•
Unit should never be closer than 250mm (10") to the
liquid surface
•
Do not mount over or near objects which can interfere
with the unit measurement
•
Do not mount in the centre of a curved roof to avoid
the potential of parabolic echoes
• Ensure appropriate UV protection
.
2” NPT (MWN1A)
or
2“ BSPT (MWB1A)
min. 250mm (10”)
min. 250mm (10”)
These are examples of common
INCORRECT
mountings which can prevent the unit from
operating correctly.
Do
NOT
mount near infeed
Do
NOT
mount cone or transducer
face above roofline
Do
NOT
mount over or adjacent to
any
obstacles
Do
NOT
mount on angle
in liquid applications
2” NPT (MWN1A)
or
2“ BSPT (MWB1A)
min. 250mm (10”)
min. 250mm (10”)
Protect from UV