Troubleshooting

MiniWave

 

User Manual

10

Unit is displaying incorrect distance

• Confirm display mode is suitable.  
 

Space

 is measured from Sensor face to measured level.   

 

Material

 is measured from Low Level to measured level.

• If unit is measuring too deep increase 

Sensitivity

.  

  If the unit continues to measure too deep, increase   
 

WaveBoost

 

• If unit is measuring too high, reduce 

Sensitivity

 and  

 ensure 

WaveBoost

 is set to 0.

• Check if material is present to be measured. Unit    
  will output and display FailSafe reading if it cannot    
  detect a level within range.

PLC indication does not match measurement

• Connect a Multimeter in series with the powered    
  loop. Compare the 'mA' diagnostic on the display  
  with the mA reading on the loop. If these values do  
  not match, disconnect the loop wires and measure  
  the resistance across the loop. This should not  
  exceed specification.

• Confirm 

High Level

 and 

Low Level

 are set to the    

  same values in MiniWave and control system.

Analogue trend is erratic/unstable

• Increase '

Damping

' value for smoother trends.

• Choose a slower '

Tracking

' speed.

• Check there are no objects interfering with the  

 

  transit pulse in the application (such as ladders and  
  cross beams).

Unit is locked up or flat line measurement

• Confirm there is material within measurement  

 

  range, the unit may go to Failsafe if there is no flat    
  level available.
• If the unit is locked to a high level perform 

Mapping

  

  for distance beyond false echoes.
• If the unit is locked higher than the real level check  
  for objects interfering with the transit pulse in the  
  application (such as ladders and cross beams). 

 

  Lower the 

Sensitivity/WaveBoost

. Re-locate the    

  installation to avoid the interfering object.
• If the unit is locked lower than the real level confirm  
  the application is not within 

Blanking

 distance.  

 Increase 

Sensitivity/WaveBoost

 until unit  

 

  measures correct level.
• 

Tracking

 speed may be too slow for the application.  

 Increase 

Tracking

 speed.

AutoSet fails

• Increase '

Sensitivity

' to a higher value.

• Allow the unit to run for a longer time (one minute).   
  Re-attempt the AutoSet.

• Increase 

WaveBoost and re-

attempt the AutoSet.

• Set High and Low level manually in 'Setup' menu.

If problems persist, install replacement 
MiniWave in the application. 
'Bench test' the problem unit in a controlled 
environment.
Difficult applications may be required a low 
frequency Acoustic Wave device. Contact 
HAWK for information about the Sultan series. 

Содержание MiniWave Ultrasonic Level Series

Страница 1: ...MiniWave Ultrasonic Level Series Liquid Level Measurement User Manual Sultan Sonar Manual Rev 1 0 A Higher Level of Performance www hawkmeasure com For more information please visit...

Страница 2: ...Commissioning Software 7 Startup 7 Main Menu 7 Setup 7 AutoSet 7 Advanced Settings 8 HART 9 HART Universal Common Practice command list 9 Troubleshooting 10 Unit is displaying incorrect distance 10 An...

Страница 3: ...ndustries Principle of Operation The MiniWave emits an ultrasonic pulse which is reflected from the surface of the liquid being measured The reflected signal is processed using specially developed sof...

Страница 4: ...ring 15mm 0 60 2 NPT or BSPT INTERNAL THREAD 152mm 6 0 4 x 19mm 0 75 HOLES THROUGH 120mm 4 7 P C D FA2NB 4 2 ANSI Polypropylene Flange for NPT threaded units FA2BB 4 2 ANSI Polypropylene Flange for BS...

Страница 5: ...re of a curved roof to avoid the potential of parabolic echoes Ensure appropriate UV protection 2 NPT MWN1A or 2 BSPT MWB1A min 250mm 10 min 250mm 10 These are examples of common INCORRECT mountings w...

Страница 6: ...e Space 1 402m 17 2mA SCANNING Set Lo Level No Yes 2 597m Set Lo Level Diagnostic Display Mode Interface Button Action Navigation Function Press and release Press and hold for 3 seconds Access Main M...

Страница 7: ...toset See B Autoset Main Menu Setup Advanced Autoset Setup Display Mode Display Unit Low Level Hi Level Damping FailSafe Advanced Comms Echo Size Lock Code Analogue Language Autoset See B Aut AutoSet...

Страница 8: ...EchoSize The unit will target this echo size measured in signal voltage during operation High values can increase stability but make the unit more susceptible to false echoes Lower values can make th...

Страница 9: ...ident associated with tag 12 Read message 13 Read Tag Description Date 14 Read PV sensor information 15 Read output information 16 Read final assembly number 17 Write message 18 Write Tag Description...

Страница 10: ...ng with the transit pulse in the application such as ladders and cross beams Unit is locked up or flat line measurement Confirm there is material within measurement range the unit may go to Failsafe i...

Страница 11: ...cessories FA2NB 4 2 ANSI Polypropylene Flange for NPT threaded units FA2BB 4 2 ANSI Polypropylene Flange for BSPT threaded units Hawklink MiniUSB PC connecter for GoshawkII Model Type MWN1A MiniWave w...

Страница 12: ...t Resolution 1 mm 0 04 Electronic Accuracy 0 25 of maximum range Operating Temperature 40 C to 60 C 40 F to 140 F Maximum Operating Pressure 0 5 to 3 bar 0 44 PSI Automatic Temperature Compensation Ye...

Страница 13: ...Contact MiniWave User Manual 13 13 13...

Страница 14: ...Overview MiniWave User Manual 14 14...

Страница 15: ...Overview MiniWave User Manual 15 15...

Страница 16: ...he need for immediate technical assistance The HawkLink 3G communication device allows any computer with internet access and our free GosHawk diagnostic calibration software to dial in calibrate test...

Отзывы: