Mounting and Dismounting
Only authorised experts, who are familiar with the safety instructions for handling electrical
components, are allowed to perform mounting or dismounting work on or using this control. For
handling ATEX-certified controls within potentially explosive atmospheres the expert also has to be
familiar with the safety instructions relevant there.
Requirements
?
Mounting surface clean and flat,
i.e. free from paint, rust, etc.
?
Threaded hole on the mounting
surface:
Depth: 15 mm
Thread: M8
Unscrew housing cover from housing
base.
?
Allen key, SW8
Use Allen screw and spring
washer to
friction-lock
the control
on the mounting surface.
?
Allen key, SW6
Slightly fasten housing cover to housing
base by hand.
(Avoid jamming the thread!)
Tighten housing cover using a tightening
torque = 5 Nm.
?
Torque wrench SW8
Workflow
1.
2.
3.
?
Allen key, SW6, SW8
?
Torque wrench SW8
?
Allen screw M8x20
?
Spring washer for M8
Tools and materials
Note:
To prevent any cold-welding between housing cover and housing base, the control is
delivered
with a fitting lubricant for stainless steel connections applied to its thread.
Before mounting or dismounting, disconnect the control from the mains! Ensure that
disconnected plug connections are always de-energised! Otherwise, there is an explosion
hazard from sparking when operating ATEX-certified Type 663-Window in potentially
explosive atmospheres!
Ground the control housing via the fastening, i.e. the machine earth or a seperate earth
conductor (PE)!
16.1
Fastening on the Mounting Surface
Fastening on the mounting surface
Mounting Surface
zu
5 Nm
Tightening housing cover using a torque wrench