VPT10-H
HART
®
PRESSURE TRANSMITTER
INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
______________________________________________________________________________________________________________________________
34
6.2.
TECHNICAL SPECIFICATION
Table 6.1 – Technical specification for VPT10-H.
Accuracy
Standard Model: ± 0.075% High Performance Model: ± 0.05%
Communication Protocol
HART
®
7 / 4-20 mA according to NAMUR NE-43
Sensor Type
Capacitive sensor with microprocessor, digital reading and compensation algorithm.
Models / Measurement Range
D1 / -7.5 to 7.5 kPa (-30 to 30 inH
2
O) D2 / -37.4 to 37.4 kPa (-150 to 150 inH
2
O)
D3 / -147.1 to 147.1 kPa (-21 to 21 psi) D4 / -690 to 690 kPa (-100 to 100 psi)
D5 / -2068 to 2068 kPa (-300 to 300 psi) D6 / -6890 to 6890 kPa (-1000 to 1000 psi)
M1 / -7.5 to 7.5 kPa (-30 to 30 inH
2
O) M2 / -37.4 to 37.4 kPa (-150 to 150 inH
2
O)
M3 / -100 to 147.1 kPa (-14.7 to 21 psi) M4 / -100 to 690 kPa (-14.7 to 100 psi)
M5 / -100 to 2068 kPa (-14.7 to 300 psi) M6 / -100 to 6890 kPa (-14.7 to 1000 psi)
M7 / -0.1 to 20.68 MPa (-14.7 to 3000 psi) A2 / 0 to 37.4 (0 to 150 inH
2
O)
A3 / 0 to 147.1 kPa (0 to 21 psi) A4 / 0 to 690 kPa (0 to 100 psi)
A5 / 0 to 2068 kPa (0 to 300 psi) A6 / 0 to 6890 kPa (0 to 1000 psi)
H2 / -37.4 to 37.4 kPa (-150 to 150 inH
2
O) H3 / -147.1 to 147.1 kPa (-21 to 21 psi)
H4 / -690 to 690 kPa (-100 to 100 psi) H5 / -2068 to 2068 kPa (-300 to 300 psi)
Static Pressure and Overpressure
Limits
Range 1: 8 MPa (81.6 kgf/cm
2
) Ranges 2 to 6: 16 MPa (163.1 kgf/cm
2
)
Range 7: 40 MPa (407.9 kgf/cm
2
) For model H: 31,2 MPa (318,15 kgf/cm
2
)
Stability
Standard Model: ±0.2% URL (5 years) High Performance Model: ±0.2% URL (15 years)
Turndown
150:1 or 200:1 (depending on model)
Response Time
50 ms
Output Current
4-20 mA according to NAMUR-NE43
Output Type
Linear, Square Root and Table
Power Supply
12 to 45 Vdc, no polarity, with transient suppressor
Temperature Limits
Ambient: -40 to 85°C Process: -40 to 100°C Storage: -40 to 100°C
Humidity Limits
0 to 100% RH (relative humidity)
Configuration
Remote configuration using EDDL or FDT/DTM-based tools, as well as PALM and Android
platforms. Local configuration via magnetic tool.
Write Proteçtion
Via hardware and software with indicative icon on display
Totalization
Non-volatile volumetric and mass flow
Hazardous Area Classification
Explosion Proof and Intrinsically Safe
Protection Degree
IP67
Mounting
Field, through a bracket on a 2” pipe
Housing Material
Aluminum
Approximated Weight with Bracket
3,5 Kg