CONFIGURATION RESTORE
Should the user require a full factory reset of the transmitter (including current and sensor calibrations),
insert two magnetic switches (one in each hole - Z and S) at the local adjust and restart the equipment,
waiting for the numeric count to be completed until display shows the word "donE". After that, simply
reconfigure transmitter with the desired values for the application.
3.2.
JUMPER CONFIGURATION FOR LOCAL ADJUST AND WRITE PROTECTION
VPT10-H has two jumpers on its main board to protect data writing (WP1) and also enabling/disabling local adjust
(ADJL1). Figure 3.2 presents those jumpers.
Figure 3.2 – Jumpers of main board.
NOTE
Default selection for these jumpers is Write Protection
DISABLED
and Local Adjust
ENABLED.
WP1
Write Protection
Enabled
Disabled
ADJL1
Local Adjust
Enabled
Disabled