User Manual
E018-P
Page 54
FW_E018-P_M_v0301-01_EN
COMMUNICATION
Function
Reading display information, reading/writing all configuration settings
Type CR
HART Communication protocol, Revision 7.0
Type CX
No communication, remote configuration possible with accessory cable (ACE02)
Addressing
Maximum 32 addresses
Loop resistance
Between 250 and 1100Ω
A.4
OPERATIONAL
OPERATOR FUNCTIONS
Displayed information
●
Linearized flowrate and / or total.
●
Linearized total and accumulated total.
●
Indicating speedometer for flowrate
●
Total can be reset to zero by pressing the CLEAR-key twice
TOTAL
Digits
7 digits
Unit
L, m3, US gal, igal, cf, Oil bbl, kg, ton, US ton, lb or none
Decimals
0 – 1 – 2 or 3
Note
Total can be reset to zero
ACCUMULATED TOTAL
Digits
11 digits
Unit decimals
According to selection for total
Note
Accumulated total cannot be reset to zero
FLOW RATE
Digits
7 digits
Units
mL, L, m3, g, kg, ton, US ton, US gal, igal, Oil bbl, lb, cf, rev, none, scf, nm3, nL
Bar graph
speedometer
20 blocks, each block is 5% of total span
Decimals
0 – 1 - 2 or 3
Time units
/sec - /min - /hr - /day
A.5
DIRECTIVES/STANDARDS AND HAZARDOUS AREA CLASSIFICATION
APPLICABLE DIRECTIVES AND STANDARDS
EU Directives
See
Section E: Legal information [»63]
EMC
FCC 47 CFR part 15
CSA
CSA 22.2 No. 25, CSA 22.2 No. 30, CAN/CSA 22.2 No. 94-M91, CSA C22.2 No. 61010-1-12
FM
FM3600; FM3615; FM3616; FM3810
IP & TYPE
EN 60529; NEMA 250