APPENDIX A - TECHNICAL SPECIFICATION

A.1

GENERAL

DISPLAY

Type

High intensity numeric and alphanumeric LCD, UV-resistant, with bright backlight (intensity
adjusted via the keypad)

Digits

Seven 12 mm (0.47”) and eleven 7 mm (0.28”). Various symbols and measuring units.

Dimensions

Ø 65 x 45 mm (2.56” x 1.77”)

Refresh rate

User definable: 8 times/sec – 30 secs.

Speedometer

Indicates the actual flowrate (bargraph runs from 0 to 100% in steps of 5%)

OPERATING TEMPERATURE

Ambient

-40°C to +70°C (-40°F to +158°F)

ENCLOSURE

Dimensions

112 x 133 x 148 mm (4.41” x 5.24” x 5.83”) (WxHxD)

Protection method

ATEX/IECEx: Ex d, Ex t. US: XP, DIP.

Control keys

Three optical keys with operation through the glass front window

Sealant

Silicone and EPDM

Anti-seize compound

EPDM compliant silicone oil based grease (Ambergrease FG2 or equivalent)

Material (metal parts)

Type HA_: Die-cast aluminum AlSi8Cu3/AlSi9Cu3(Fe) (weight 1300 gram)
Type HS_: Stainless steel 316L (weight 3600 gram)

Rating

IP66 / 67 / TYPE 4X / TYPE 7 / TYPE 9

Thread type H_A

2 x ¾”NPT / 1 x 1”NPT

Thread type H_B

3 x ¾”NPT

Thread type H_C

2 x ½”NPT / 1 x 1”NPT

Thread type H_D

2 x ½”NPT / 1 x ¾”NPT

Thread type H_G

2 x M20 / 1 x M25

Thread type H_H

3 x M25

TERMINAL CONNECTIONS

Type

Removable plug-in terminal strip (wire max. 1.5 mm

2

 and 2.5 mm

2

).

DATA PROTECTION

Backup

EEPROM backup of all settings (running totals every minute; data retention at least 10 years)

Password

Configuration settings can be password protected

POWER REQUIREMENTS

Type PB

Long life lithium battery - lifetime depends upon settings and configuration (up to approx. 3
years).
The battery can power the backlight briefly after a keypad touch but cannot power the relay
output (OR) or the real sensor supply (Terminal P3).

Type PD

9 – 27 VDC. Consumption max. 4.5 W (sensor excitation and backlight included) in combination
with relay output (type OR); 24-27 VDC

Type PX

9 – 27 VDC. Consumption max. 3 W (including backlight)

Type AH

Loop powered, analog output. 11 – 27 VDC, min. 2 mA; consumption max. 675 mW (25 mA @
27 VDC). The loop powered analog output cannot power the backlight, mechanical relay output
(type OR) or the real sensor supply (Terminal P3).

Содержание E018-P

Страница 1: ...ART communication Signal input Flowmeter type P Pulse NAMUR and coil Signal outputs Analog referenced flowrate Scaled or unscaled pulse referenced total Remote control External reset with clear lock O...

Страница 2: ...w battery 14 4 5 3 Internal error 14 5 CONFIGURATION 15 5 1 Introduction 15 5 2 Operating the Main Electronics Module MEM 15 5 2 1 Configuring using PC Configuration tool 16 5 2 2 Mechanical keys 16 5...

Страница 3: ...4 10 Terminals S1 S3 Flowmeter input 45 6 4 11 Terminals E1 E2 External reset with clear lock Type IB 48 6 4 12 Terminals A1 A2 Isolated analog output Type AH 48 7 MAINTENANCE 50 7 1 Check for wear or...

Страница 4: ...zardous situation that could cause injury or death A caution indicates a condition that could cause moderate minor personal injury or equipment damage incorrect functioning of the unit or connected in...

Страница 5: ...apter of this manual Never remove the earth lead between the housing and the removable terminal block The local labor and safety laws and regulations must be adhered to Modifying the unit without prio...

Страница 6: ...instrument designed to linearize the flowmeter s flow curve and to show the current flowrate the totalized flow and the accumulated totalized flow Fig 1 The E018 P This manual describes the daily use...

Страница 7: ...or Status input to reset total remotely or to lock the clear total key Standard outputs Configurable pulse output to transmit pulses representing a certain linearized total quantity The pulse length c...

Страница 8: ...EXAMPLE Following parts can be recognized in below installation example 1 2 6 4 5 9 7 3 8 9 Fig 3 Installation example E018 P 1 Cover 4 Display 7 Grounding 2 Armed cable connection 5 Optical touch ke...

Страница 9: ...a setting is being changed this is indicated by the mode indicator PROG on the display The following paragraphs describe the modes of operation in more detail SETUP mode and PROGRAM mode are described...

Страница 10: ...used to control the unit through the glass without the need to open the enclosure To activate an optical key position a finger clean and without gloves in front of the glass above the indicated area...

Страница 11: ...n Electronics Module MEM 15 for more information 4 2 3 BACKLIGHT The E018 is equipped with a backlight to illuminate the display for improved readability Depending on the type of supply the backlight...

Страница 12: ...ate Total 1 Acc Total SCREEN 1 Total 1 Acc Total Total 1 Acc Total Total 1 Flowrate SCREEN 2 2 Alarm Lo Lo SCREEN 3 2 Alarm Lo SCREEN 4 2 Alarm Hi SCREEN 5 2 Alarm Hi Hi INTERNAL ERROR 3 Internal alar...

Страница 13: ...sed 8 times per second To obtain a readable value the flowrate shown on the display is updated once every second Speedometer A speedometer view of the actual flowrate can be shown along the top edge o...

Страница 14: ...ion of the flowrate alarm RATE GAL TOTAL ALARM 0 00 1 10 30 20 80 90 70 Fig 8 Example of LO LO flowrate alarm 4 5 2 LOW BATTERY When a battery is used to supply the unit Type PB and the battery voltag...

Страница 15: ...is present Opening and servicing of the unit may only be carried out by authorized and trained personnel who have read and understood this manual particularly Section 2 Safety 5 Before opening the en...

Страница 16: ...convenient way to configure the E018 P is by means of SETUP mode and three mechanical keys push buttons at the side of the MEM available with the cover removed PROG CLEAR SELECT Fig 13 Control panel p...

Страница 17: ...SING SETUP MODE For an overview of Operating modes see Section 4 1 1 Operating modes 9 Changing settings may influence current operation In SETUP mode the unit remains fully operational Make sure the...

Страница 18: ...em either contains a value a number with optionally a decimal point and sign e g 123 45 or a selection list e g L m3 USGAL After a menu item is selected in the SETUP menu a new value can be programmed...

Страница 19: ...is cancelled and the former value is reinstated 5 3 4 RETURNING TO OPERATOR MODE When all configuration settings are set correctly return to OPERATOR mode by pressing the PROG key for three seconds or...

Страница 20: ...ESPAN 0000000 9999999 9999 5 FLOWMETER DEFAULT 5 1 SIGNAL NPN NPN_LP REED REED_LP PNP PNP_LP NAMUR Coil_Hi Coil_Lo Act_8 2 8 2V DC Act_24 24V DC Coil_Lo 6 LINEARIZATION DEFAULT 6 1 F FREQ M FACTOR 1 1...

Страница 21: ...is based on the number of pulses generated by the flowmeter per selected measurement unit as defined in 1 1 TOTAL UNIT The more accurate the K Factor the more accurate the system After pressing PROG t...

Страница 22: ...important for battery powered applications For low frequency applications below 10 Hz do not program more than 10 pulses otherwise the update time will be very slow For high frequency applications ab...

Страница 23: ...s delay time an alarm is generated 3 7 DELAY LOW An alarm generated by 3 3 ALARM ALARM LOW can be ignored during X time period If the actual flowrate is still incorrect after this delay time an alarm...

Страница 24: ...owrate alarm the color is red FLASH during a flowrate alarm the color flashes red 4 6 BARGRAPH The unit has a speedometer bar graph around the edge of the display that gives a quick impression of the...

Страница 25: ...xternal sensor power required COIL HI Coil input high sensitivity min 20 mVpp Sensitive for interference Type ZF min 10 mVpp Type ZG min 5 mVpp COIL LO Coil input low sensitivity min 90 mVpp Normal se...

Страница 26: ...he linearization points are usually located at frequencies where the linear behavior of the flowmeter changes Linearization points that are not used can be disabled by entering a frequency of 0 Hz The...

Страница 27: ...V LRV at 0 l sec What will be the value of the analog output when the actual flowrate is 1000 l sec Analog output current 1000 1600 20 mA 4 mA 4 mA 14 mA 7 ANALOG OUTPUT 7 1 RATE MIN 4MA Primary Varia...

Страница 28: ...ollowing functions are available off lo lo lo hi hi hi all pulse retransmit The Retransmit mode is often used when sinus non square wave input signals are present for example coil signals that need to...

Страница 29: ...before The following selections are available Off Output current set to normal Set 4 mA Output current set to 4 mA Set 20 mA Output current set to 20 mA The loop test function only works if SETUP 9 2...

Страница 30: ...trained personnel Take careful notice of the Section 2 Safety 5 at the front of this manual 6 1 INSTALLATION ENVIRONMENTAL CONDITIONS Take the relevant IP classification of the enclosure into account...

Страница 31: ...Main Electronics Module MEM 6 Grounding terminal 3 Battery 7 Label 4 Supply Module RSM or BSM BSM RSM MEM 1 1 2 2 2 2 3 5 5 4 6 Fig 18 Main Electronic Module and two types of Supply Module BSM RSM 1 F...

Страница 32: ...el placed on the outside of the unit Information on this label includes the configuration options chosen for your product E Y YY YY YYY YY YY YY YY YY Th e r ad Sizes P uct Configuration rod and Seria...

Страница 33: ...ate serial number of the electronics product configuration and connectors and more The MEM is supplied with two labels Fig 21 Example MEM labeling The Supply Module is also labeled Depending on produc...

Страница 34: ...ing Make sure the MEM inside doesn t fall out or gets damaged Remove the cover carefully 3 Store the cover in a safe location Make sure the mounting thread and glass screen are protected and the fixin...

Страница 35: ...nto the housing in one of the four positions 0 90 180 270 so the display is best readable Closing the cover 1 Apply a very thin layer of the specified anti seize compound see Section A Technical speci...

Страница 36: ...ENTRIES WITHIN 18 INCHES For CSA Group B C D SEAL ALL CONDUIT ENTRIES WITHIN 18 INCHES For CSA Group A SEAL AT ENCLOSURE WALL Use certified cable glands and conduit sealing devices All flameproof join...

Страница 37: ...osure 6 3 3 MOUNTING THE UNIT The Main Electronics Module MEM can be placed into the body in 4 directions 0 90 180 270 This allows the unit to be mounted in any direction while still allowing the MEM...

Страница 38: ...unit on a flowmeter 1 Remove the cover and the MEM see Section 6 2 3 Opening assembling and closing the unit 34 2 If present remove the cap from the bottom connector of the housing 3 Position the uni...

Страница 39: ...tection level Gb and Db the unit must be installed such that even in the event of rare incidents an ignition source due to impact or friction sparks between the enclosure and aluminum steel is exclude...

Страница 40: ...ion the housing temperature exceeds 70 C 158 F use suitable cable and gland to withstand high temperatures 6 4 2 GROUNDING OF THE ENCLOSURE For Class 1 applications make sure to apply proper in and ex...

Страница 41: ...can use some low power NPN or PNP output signals but battery life will be significantly reduced consult your distributor Type PD Sensor supply 8 2 VDC 12 VDC or 24 VDC Vin P2 minus 1 V This option pro...

Страница 42: ...omatically R4 PULSE OUTPUT ALARM S D2 R5 R6 D3 R7 OT passive transistor output PULSE OUTPUT ALARM S D4 Fig 27 Terminal connectors MEM upper row E1 E2 E3 IB Reset total Clear lock P3 S2 S3 SENSOR INPUT...

Страница 43: ...ge selection sensor supply 41 6 4 8 TERMINALS P3 SENSOR SUPPLY TYPE PD This terminal may be used for sensor supply See Section 6 4 4 Voltage selection sensor supply 41 for relevant information Power r...

Страница 44: ...R1 R7 Transistor outputs D1 D4 With Type OT Terminals R1 R3 and R5 are common ground GND terminals The output functionality of digital outputs D5 and D6 corresponds to the functionality of digital ou...

Страница 45: ...ER 25 Sine wave signal Coil The unit can be used with flowmeters which have a coil output signal Two sensitivity levels can be selected see SETUP 5 1 FLOWMETER SIGNAL 25 COIL LO sensitivity 90 mVpp CO...

Страница 46: ...gnal noise filter which limits the maximum input frequency to avoid pulse bounce see SETUP 5 1 FLOWMETER SIGNAL 25 Power supply type PD provides a sensor supply voltage of 8 2 12 or 24 VDC S1 S2 S3 P3...

Страница 47: ...2V Common system ground R MEM Fig 36 Terminals S1 S2 and P3 NAMUR input signal Active signals 8 2 V and 24 V The unit is suitable for flowmeters with an Active signal The detection levels are about 50...

Страница 48: ...rd available This output is an isolated 4 20 mA output with the possibility to power the device via the 4 20 mA loop It is non polarity sensitive When the output is disabled the current is by default...

Страница 49: ...E018 P User Manual FW_E018 P_M_v0301 01_EN Page 49 A1 A2 10 27V DC MEM MASTER Fig 40 Terminals A1 A2 Isolated 4 20 mA analog output with HART devices...

Страница 50: ...damage or aging symptoms 2 Check the process accuracy If necessary re calibrate the flowmeter Do not forget to re enter any updated K factor values 3 Check the battery indicator for low level replace...

Страница 51: ...is with the next clip 2 Carefully lift the back cover and remove the battery from the battery holder 3 Dispose of the battery according to local regulations Insert new battery in MEM 1 Unpack the new...

Страница 52: ...t 3600 gram Rating IP66 67 TYPE 4X TYPE 7 TYPE 9 Thread type H_A 2 x NPT 1 x 1 NPT Thread type H_B 3 x NPT Thread type H_C 2 x NPT 1 x 1 NPT Thread type H_D 2 x NPT 1 x NPT Thread type H_G 2 x M20 1 x...

Страница 53: ...nternally pulled up switch contact NPN Pulse duration 100 msec minimum A 3 OUTPUT DIGITAL OUTPUT Function Transmitting flowrate alarm status linearized accumulated total scaled pulse or input pulse re...

Страница 54: ...AL Digits 7 digits Unit L m3 US gal igal cf Oil bbl kg ton US ton lb or none Decimals 0 1 2 or 3 Note Total can be reset to zero ACCUMULATED TOTAL Digits 11 digits Unit decimals According to selection...

Страница 55: ...Db IECEx Gas Ex d IIC T6 Gb Dust Ex tb IIIC T85 C Db CSA c us Class I Division 1 Grps A B C D Class II III Division 1 Grps E F G Class I Zone 1 Aex d IIC T6 T5 Gb Zone 21 Aex tb IIIC T85 C T100 C Db...

Страница 56: ...LOWMETER 25 Grounding Reconnect ground cables and avoid ground loops Connect screen to the ground input terminal of the flowmeter input Wiring type Use screened wire for flowmeter signals Analog outpu...

Страница 57: ...shown is the sum of the error codes as given below For example 0048 is a combination of error code 0016 and 0032 Alarm Explanation 0001 Display error 0002 Data storage error 0004 Initialization error...

Страница 58: ...evision 0x03 Software Revision 0x01 Hardware Revision 0x00 Physical layer FSK 4 wire high impedance transmitter Device type physical category DC isolated Bus Device Transmitter Device ID 0x177864 Devi...

Страница 59: ...er 2 Fld Dev stat 15 1 0x01 Initialization error Fld Dev stat 15 2 0x02 Warning Total was cleared either via HART or by hand FLD DEV STAT 14 1 and FLD DEV STAT 14 2 are critical errors The device malf...

Страница 60: ...136 gal day 235 Igal Igal sec 137 Igal min 18 Igal hr 30 Igal day 31 cf Cuft sec 26 Cuft min 15 Cuft hr 130 Cuft day 27 bbl bbl sec 132 bbl min 133 bbl hr 134 bbl day 135 nl Normal l sec 176 Normal l...

Страница 61: ...ns as desired up or download the settings to the MEM and print a hardcopy for each product With the software programming of multiple products can be done very easy D 2 CABLE CONNECTION Before opening...