6.1.2 Terminal Block Assignments — High Voltage (TB2) Terminal Block
SC-1500
SC-2000
Terminal
Number
SC-3000
SC-4000
Terminal
Number
Label
Description
25
22
MASTER ALARM RELAY
Normally-Open Dry Contact, Close on Alarm
(240VAC Max Voltage & 1/2Amp Max Current)
24
21
MASTER ALARM RELAY
23
20
RELAY A
User-Configurable Normally-Open Dry Contact A
(240VAC Max Voltage & 1/2Amp Max Current)
22
19
RELAY A
21
18
RELAY B
User-Configurable Normally-Open Dry Contact B
(240VAC Max Voltage & 1/2Amp Max Current)
20
17
RELAY B
19
16
RELAY C
User-Configurable Normally-Open Dry Contact C
(240VAC Max Voltage & 1/2Amp Max Current)
18
15
RELAY C
17
14
RELAY D
User-Configurable Normally-Open Dry Contact D
(240VAC Max Voltage & 1/2Amp Max Current)
16
13
RELAY D
N/A
12
GROUND
Ground Terminals for I/O Devices
15
11
GROUND
14
10
[120V+] AIR DAMPER
120VAC Pilot-Duty for Air Damper End Limit Switch
Contact Closure When Air Damper Proven Open
13
9
AIR DAMPER INTERLOCK
12
8
[120V+] AUXILIARY #1
Reserved for Future Use
11
7
AUXILIARY INPUT #1
10
6
[120V+] AUXILIARY #2
Reserved for Future Use
9
5
AUXILIARY INPUT #2
8
4
START INTERLOCK #1
External Interlock Circuit #1
7
3
START INTERLOCK #1
6
2
START INTERLOCK #2
External Interlock Circuit #2 (In Series w/ #1)
5
1
START INTERLOCK #2
4
N/A
GROUND
G1 for 208-240VAC, Single phase, 60Hz
3
N/A
NEUTRAL
N1 for 208-240VAC, Single phase, 60Hz
2
N/A
HOT L2
L2 for 208-240VAC, Single phase, 60Hz
1
N/A
HOT L1
L1 for 208-240VAC, Single phase, 60Hz