P-K THERMIFIC
®
Gas-Fired Boiler
11
Type of Surface
Dimensions (inches)
A B C† D
Combustible Surfaces
30
24*
30
24
Recommended Service Clearance
30
24
30
24**
† "C" dimension includes clearance to remove the burner. Do not put pipes, ducts, etc. in this area above the boiler.
* CSA minimum. Actual clearance depends upon venting requirements.
** Service access need be only on one side of a boiler or row of boilers.
Boilers may be installed immediately adjacent to each other. However, Harsco Industrial, Patterson-
Kelley recommends this clearance between
each boiler
when there is insufficient access at the rear to
allow for service and adjustment.
Bumping hazard from overhead ducts! Install all components with adequate
vertical clearances.
In Canada:
The boilers are approved for installation with zero clearance to combustible surfaces, but 24
inch service clearances are recommended.
3.4 E
LECTRICAL
C
ONNECTIONS
The boiler is wired for 120 volts, single phase, 60 hertz. The electrical connections should be made in
the junction box on the rear of the boiler. The total operating amperage is indicated on the rating
nameplate. The 700 and 1000 series require less than 8 amps; while the 1500, 1700, 2000 series
requires less than 12 amps. Before starting the boiler, check to ensure that the proper voltage and
amperage is connected to the boiler.
An external electrical disconnect (not supplied with the boiler) with adequate overload protection is
required. The boiler must be grounded in accordance with local codes or in the absence of such
requirements, in the U.S. with National Electrical Codes, ANSI/NFPA No. 70, latest edition and in
Canada, wire according to the current Canadian Electrical Code, Part I, CSA C22.1.
NOTICE! A dedicated earth ground (green wire) is required to avoid nuisance shutdowns. Do not
ground through the conduit. It is also important that proper polarity be maintained.
3.5 I
NLET
A
IR AND
E
XHAUST
V
ENTING
3.5.1 Applicable Codes & Standards
CODES
United States:
NFPA 54/ANSI Z223.1
National Fuel Gas Code
NFPA/ANSI 211
Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances
Canada
CAN/CSA B149.1
Installation Codes for Gas Burning Equipment
STANDARDS
Содержание P-K THERMIFIC N700
Страница 2: ...P K THERMIFIC Gas Fired Boiler 2...
Страница 52: ...P K THERMIFIC Gas Fired Boiler 52 6 1 1 On Off 6 1 1 1 On Off Wiring Diagram 700 1000 1500 1700 2000...
Страница 53: ...P K THERMIFIC Gas Fired Boiler 53 6 1 1 2 On Off Sealed Combustion Diagram 700 1000...
Страница 54: ...P K THERMIFIC Gas Fired Boiler 54 6 1 1 3 On Off Sealed Combustion Diagram 1500 1700 2000...
Страница 55: ...P K THERMIFIC Gas Fired Boiler 55 6 1 2 Lo Hi Lo 6 1 2 1 Lo Hi Lo Wiring Diagram 1500 1700 2000...
Страница 56: ...P K THERMIFIC Gas Fired Boiler 56 6 1 2 2 Lo Hi Lo Sealed Combustion Diagram 1500 1700 2000...
Страница 57: ...P K THERMIFIC Gas Fired Boiler 57 6 1 3 Low Water Cutoff 6 1 3 1 Field Installed Low Water Cut Off Diagram...
Страница 58: ...P K THERMIFIC Gas Fired Boiler 58 6 1 3 2 Factory Installed Low Water Cut Off Diagram...
Страница 64: ...P K THERMIFIC Gas Fired Boiler 64...