HS-3030 Programming Manual
55
The Addressable Module supports the following key board commands:
21
Detail
For a single device, shows all the programming, analog values,
status and commands sent.
22
Type On-Line
For a single circuit, shows a grid displaying all the devices that
are actually on the circuit.
23
Type Assigned
For a single circuit, shows a grid displaying all the devices that
are programmed to be on the circuit.
24*
Errors
For a single circuit, shows a grid displaying all the incorrect,
missing and mismatched devices. This shows the differences
between what is expected to be on the circuit and what actually is
on the circuit.
25
Alarms
For a single circuit, shows a grid displaying the current Alarm,
Early Warning, Supervisory and Trouble conditions for all devices
on the circuit.
26
Function
For a single circuit, shows a grid displaying the Alarm and
Supervisory initiating devices. Control modules are neither type
and are displayed as a dash (-).
27
Control Modules
For a single circuit, shows a grid displaying the current status of
all the Control modules.
28
Bypass
For a single circuit, shows a grid displaying all the devices that
are currently bypassed.
29
Test Mode
For a single circuit, shows a grid displaying all the devices that
are currently under test.
30
Analog
Displays the analog values of 10 consecutive addresses for a
single circuit.
50
Tasks
This screen is for factory use only.
51
FIFO
Displays the FIFO memory usage of various system tasks. This
diagnostic screen needs to be consulted if the panel has a
Memory Overflow trouble. The first line shows the total FIFO
space and the largest amount any one task has used. For each
task, the first number is the current usage and the second is the
maximum usage. If a task uses a large amount of FIFO memory,
this means that task is having difficulty in operating.
Command
Description
<Del>
Clear and redisplay screen.
<Tab>
View next available screen. Unused/unavailable
screens are skipped over.
<Backspace>
View previous available screen. Unused/unavailable
screens are skipped over.
Screen
Name
Description
Содержание Network Plus HS-3030
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 65: ...Harrington Signal Inc 2519 4th Avenue Moline IL 61265 HARRINGTON FIRE ALARM SIGNAL INC ...