HS-3030 Programming Manual
25
The
1
st
and 2
nd
Account Codes
identify the system to the central station when a communication is
sent. The code can be programmed for up to four digits. The first and third telephone number
transmit the first account code. The second telephone number transmits the second account code.
The
1
st
and 2
nd
Format
setting affects the type of communication that the dialer sends to the
central station. There are seven formats available including Contact ID, SIA and a pager format.
The Dialer Settings window has the following push buttons along the right side:
•
Exit:
Close the Dialer Settings window and return to the IDs window.
•
Configuration 1:
Display the Dialer Configuration 1 screen.
•
Configuration 2:
Display the Dialer Configuration 2 screen.
•
Zone Data:
Display the Zone Data screen.
•
Maintenance/Common:
Display the Dialer Maintenance and Common Reporting Codes
screen.
Dialer Configuration 1
The
Dialer Configuration 1
dialog
(see
Figure 16
) contains the First
Communicator Options, Second
Communicator Options and
International Options.
The
Communications
option
determines if the dialer will
communicate to the central station.
When Enabled is selected, the
dialer will communicate all events
as programmed. When Disabled is
selected, the dialer will not
communicate any events.
The
TLM One/Two Check
options
determine whether the dialer will test for telephone line faults on line one and line two respectively.
The
Third Phone #
can be programmed for two different modes of operation. When Alternate
Dialing Enabled is selected, the dialer switches between the first and third numbers after each
dialing attempt, until the maximum number of dialing attempts have been made to each number.
When Third Number Backup is enabled, the dialer will use the third number only if all attempts to
communicate to the first number fail. If all attempts to communicate to the third number also fail, a
failure to communicate trouble will be generated. When Disabled is selected, the third telephone
number is not used.
The
Dialing
option has three different options for pulse or DTMF dialing. If All attempts Pulse is
selected, the dialer will always use pulse (rotary) dialing. If All attempts DTMF Dialing is selected,
the dialer will always use DTMF dialing. If 4 attempts DTMF then Pulse is selected, the dialer will
use DTMF dialing for the first four attempts. If unsuccessful, the dialer will switch to pulse dialing
for the remaining attempts.
The
SIA Rep. Codes
option determines whether the dialer will send automatic reporting codes, or
use the reporting codes that are programmed in the
Zone Data
and
Maintenance/Common
reporting codes sections. See Appendix D for a list of the automatic SIA Reporting Codes.
Note:
1. The accounts. refer to central stations, telephone lines both accounts. Can use both telephone lines.
2. The third telephone number is the backup number for the first telephone number.
Figure 16: Dialer Configuration 1