HS-3030 Programming Manual
10
•
Alert/Evac:
A First Stage alarm activates the selected bells in Evacuation mode and all
other bells on the panel in Alert mode. If the
Signal Silence
or
Second Stage Inhibit
Hot
Key is not pressed before the
[No Acknowledge] Second Stage Inhibit
timeout, the system
will progress to Second Stage. Second Stage will activate all bells in Evacuation mode.
•
Staged:
The 1st alarm will activate selected bells in Alert mode. If the
Signal Silence
or
Second Stage Inhibit
Hot Key is not pressed before the
[No Acknowledge] Second Stage
Inhibit
timeout, the selected bells are switched to Evacuation mode and the next bells, i.e.
the ones with the next higher number, are activated in Alert mode. This sequence is
repeated until all bells are in Evacuation mode. When the highest numbered bell circuit
switches to Evacuation mode, all bell and strobe circuits on the panel will be turned on in
Evacuation mode. For example, if the alarm activates Bells 1 and 4, after the
[No
Acknowledge] Second Stage Inhibit
timeout, Bells 1 and 4 are switched to Evacuation
mode and Bells 2 and 5 are set to Alert mode. A 2nd alarm will activate all bells in
Evacuation mode. Bells must be assigned consecutive bells circuits with no Releasers
assigned in between Bells. For example: circuits 1, 2, 3, 4 can be assigned as Bells but
not circuits 1, 2, 4, 5 with circuit 3 a Releaser. Control modules cannot be programmed as
bell or strobe if the Staged Bell system is used.
Subsequent Alarm
controls how Alert, Evac and Alert/Evac type bell systems behave when a new
alarm is received while one is still active.
1st Stage
has the panel repeat the First Stage operation.
2nd Stage
has the panel go immediately to Second Stage operation.
Resound
controls how the panels handle the automatic resounding of silenced bells when a new
alarm is received. There are two modes:
•
Local:
Each panel will resound only its own silenced bells when a new alarm is received.
This would be used when panels in a network are in different buildings, such as a campus.
•
Global:
All panels in a network will resound silenced bells when a new alarm condition is
received on any panel in the network. This is used when the panels are all in the same
building, such as a large plant.
Evac
controls whether the bell system Evacuation Mode sounds Steady (continuously) or uses a
Temporal pattern as specified in ANSI S3.41 and ISO 8201
Audible Emergency Evacuation Signal
.
The pattern used ½s On, ½s Off, ½s On, ½s Off, ½s On, 1½s Off repeated.
Waterflow
controls if bells can be silenced if they are started by a waterflow type input. If Non-
Silenceable is chosen, bell circuits activated by a waterflow input cannot be silenced until the
device has restored.
Language
chooses English (default), French or Hungarian characters to be used in messages.
Alarm List Sequence
controls which end of the Alarm List is shown automatically. If
First
is chosen,
the first (oldest) item in the alarm list will be shown. If
Last
is chosen, the last (newest) item in the
alarm list is shown. Regardless of order, alarms always take precedence in being shown. Another
way to think of it is that
First
shows where the fire started while
Last
shows where the fire has
gotten to.
Disconnects
controls which panels the
Signal Disconnect, Relay Disconnect, Releaser Disconnect
and
Common Disconnect
hot keys affect.
•
Local:
The Disconnect hot keys affect only the panel they are on.
•
Global:
The Disconnect hot keys affect all the panels in the network. This means that if a
Disconnect key is pressed on any panel, all panels in the system will be affected.
The
System Message
is a text entry box for defining a message used to identify the system. The
message is three lines by twenty characters long. It is printed at the top of printouts and shown on
some service terminal screens, but only seen on the LCD in the STATUS/IDENTIFICATION menu.
The
System Banner
is a 20 character message that is used as a banner for the Main Menu of the
LCD. The default banner is “HS-3030 by Harrington Signal”.