D
C
B
HSI #780-0867
FireSpy Tracker
Installation Manual
29
Appendix B. Compatible Devices
B.1
Startup delay for devices with alarm verification
The Tracker system includes an alarm verification feature that will result in a delay of the system alarm
signal from the indicated circuits.
The following statement applies to installations intended to meet UL864 requirements: The total delay
(control unit plus smoke detector) shall not exceed 60 seconds. No other smoke detector shall be
connected to these circuits unless approved by the local authority having jurisdiction.
The following statement applies to installations intended to meet California State Fire Marshal
requirements: For fire alarm verification feature (delay of fire alarm), the maximum retard/reset/restart
period (control unit plus detector) must be adjusted to 30 seconds or less.
For the devices below, the delay start-up time marked on the installation wiring diagram of the smoke
detector or on the installed smoke detector is to be used.
Circuits
Compatible smoke detectors with alarm verification
LCU and MCCLC, Class A and B
Apollo
55000-550, -650, -886
Harrington
TS8-DP, TS8-DH, TS8-DM
B.2
Addressable SLC devices (for use with T8000-LCU, T2000-MBCLC, and
T1-MB)
Each SLC circuit must use devices from a single series of compatible devices. Do not mix and match
unless otherwise noted. For example, do not use System Sensor and Apollo devices on the same circuit.
The following devices below may be used together on the same SLC circuit:
•
Harrington ISpy, TSpy, HSPS
•
Apollo XP95, Discovery
•
Air Products
B.2.1.
System Sensor
Harrington
Part No.
System Sensor Model
Description
Detectors
349-0508
1551
Ion smoke detector
349-0494
2551
Photo smoke detector
349-0495
5551
Heat detector, fixed temperature
349-0646
5551R
Heat detector, rate-of-rise
349-1048
1251B
Ion smoke detector – low profile
349-1046
2251, 2251B
Photo smoke detector – low profile
349-1056
2251BR
Photo smoke detector to be used with DNR/DNRW duct smoke detector
349-1047
2251TB
Photo/thermal multicriteria detector (Acclimate)
349-1071
2251TMB
Photo/thermal multicriteria detector (Acclimate)
349-1049
5251B
Fixed temperature heat detector, 135°
349-1059
5251H
Fixed temperature heat detector, 190°