background image

Tel: +44 (0)1732 861200  

-

  E

-

mail: [email protected]  

-

  Web: www.sontay.com

 

© 2017 Sontay Limited. All rights reserved

 

 

SD

-

D

 

Duct Smoke Detector

 

Issue Number 7.1

 

30/09/2021

 

Four Elms Road 

-

 Edenbridge

 

Kent 

-

 TN8 6AB 

-

 UK

 

1 of 3

 

Features and Benefits

 

Product Codes

 

Specification

 

SD

-

S

   

 

Duct smoke detector

 

 

 

 

 
 
 

Technical Overview

 

 

 

 

The SD

-

D duct smoke detector operates on the obscuration principle, using infrared technology and is designed specifically to cope with the 

difficult measurement conditions in air ducts, such as high velocity and levels of dirt accumulation. The relay output is either auto or manual 
reset relay output on detection of smoke.

 

Supply

   

 

 

24Vac/dc, ±20%

 

Power consumption

 

 

50mA max.

 

Relay outputs (smoke & fault)

 

 

 

 

 

SPST 2A @ 48V

 

Minimum duct size

 

 

100 x 320mm 

 

Maximum duct size

 

 

450 x 450mm*

 

LED indication

   

 

ON in alarm

 

Alarm relay (selectable)

  

Manual or auto reset 

 

Probe:

 

 

Dimensions

 

 

300 x 20mm dia.

 

 

Material

 

 

Plastic

 

Housing:

 

Material

 

 

PC/GF (Halogen free, flame retard

 

ant & UV stabilized)

 

 

Dimensions

 

 

125 x 105 x 85mm

 

 

 

 

Environmental:

 

 

Housing:

 

 

-

30 to +60°C 

 

 

 

 

 

20 to 80% non

-

condensing

 

 

Media:

   

 

10 to 40°C

 

Protection

 

 

 

IP65

 

Country of origin

 

 

Denmark 

 

Conformity

 

 

 

EMC, CE & UKCA Marked

 

 

 

 

 

 

 

* Please see recommendations on page 2.

 

 

• 

Manual or auto reset

 

• 

Fault relay output

 

• 

Self

-

test feature

 

WEEE Directive:

 

 

 

At the end of the products useful life please 

 

dispose as 

 

per the local regulations.

 

 

Do not dispose of with normal household waste.

 

 

Do not burn.

 