FireSpy Tracker
Installation Manual
19
290-0159
NOTES
:
1) Use only smoke detectors that are in the compatibility list in the
owner's manual.
2) Leave end-of-line resistors on unused circuits.
3) Combined load of all devices, including indicating appliances, is not to
exceed 4A.
TYPICAL
STYLE Y
(CLASS B)
WIRING
USB
PORT
10K
LINE
NEU/LINE
EARTH
14 AWG MIN.
RJ31X
RJ31X
LINE INPUT
120VAC - 50/60Hz
240VAC - 50/60Hz
TO EXTERNAL
SERIAL MODULES
TYPICAL STYLE Z
(CLASS A)
WIRING
(end-of-line resistor
not needed)
CONTACTS RATED
2A @ 30VDC
1.0 POWER FACTOR
USE ONLY POLARIZED
DEVICES ON NACs
Polarity shown is alarm condition
ALL NACs ARE REGULATED 24 DC
+
-
- +
RS485 RS485
B+
A+
A-
B-
B+
A+
A-
B-
NAC2
NAC3 /
AUX PWR
B+
A+
A-
B-
NC
COM
NO
NC
COM
NO
NC
COM
NO
-
+
+
-
RC
RELAYS
NAC1
RELA
Y1
RELA
Y2
AUX I/O
BA
TT
TROUBLE
TO INTERNAL
SERIAL MODULES
A+
A-
B- B+
SLC
+
+
+
+
10K
USB
SECNDRY
PHONE
PRIMARY
PHONE
PDC
MB
J4
SW1
LEDs
FH1 FUSE: 7.5A MAX
CAUTION: For continued protection against risk of fire,
replace only with same type and rating of fuse.
FH1
24VDC, .02A
10K
Marks non-supervised circuits
Marks non-power-limited circuits
All others are supervised and power limited.
Segregate power-limited wiring from
non-power-limited wiring by at least 1/4 inch.
SUPERVISED AND POWER LIMITED
S
P
S
P
P
P
P
P
P
TO RC
TO ANNUNCIATOR
ON CABINET DOOR
J4 jumpers present
TYPICAL STYLE 4 (CLASS B) WIRING
SLC B-
SLC B+
Example SLC wiring
Example RJ31X wiring
Isolators (optional) separate each zone
TYPICAL STYLE 6 (CLASS A) WIRING
ZONE 1
SLC A-
SLC A+
SLC B-
SLC B+
SLC A-
SLC A+
SLC B-
SLC B+
ZONE 2
Isolators separate each detector
Remove J4 jumpers
Remove J4 jumpers
TYPICAL STYLE 7 (CLASS A) WIRING
TIP
HOUSE RING
TIP
TELCO
RING
GRAY
BROWN
GREEN
RED
Figure 3-1: Wiring on MB
Содержание FireSpy Tracker T1000