HSI #780-0867 

FireSpy Tracker

 Installation Manual 

 

 

19 

 

290-0159

NOTES

:

1)  Use only smoke detectors that are in the compatibility list in the 

owner's manual.

2) Leave end-of-line resistors on unused circuits.
3)  Combined load of all devices, including indicating appliances, is not to 

exceed 4A.

TYPICAL
STYLE Y

(CLASS B)

WIRING

USB

PORT

10K

LINE

NEU/LINE

EARTH

14 AWG MIN.

RJ31X

RJ31X

LINE INPUT

120VAC - 50/60Hz
240VAC - 50/60Hz

TO EXTERNAL
SERIAL MODULES

TYPICAL STYLE Z 

(CLASS A) 

WIRING

(end-of-line resistor 

not needed)

CONTACTS RATED

2A @ 30VDC

1.0 POWER FACTOR

USE ONLY POLARIZED

DEVICES ON NACs

Polarity shown is alarm condition

ALL NACs ARE REGULATED 24 DC

+

-

- +

RS485 RS485

B+

A+

A-

B-

B+

A+

A-

B-

NAC2

NAC3 /

AUX PWR

B+

A+

A-

B-

NC

COM

NO

NC

COM

NO

NC

COM

NO

-

+

+

-

RC

RELAYS

NAC1

RELA

Y1

RELA

Y2

AUX I/O

BA

TT

TROUBLE

TO INTERNAL

 SERIAL MODULES

A+

A-

B- B+

SLC

+

+

+

+

10K

USB

SECNDRY
PHONE

PRIMARY
PHONE

PDC

MB

J4

SW1

LEDs

FH1 FUSE: 7.5A MAX
CAUTION: For continued protection against risk of fire, 
replace only with same type and rating of fuse.

FH1

24VDC, .02A

10K

Marks non-supervised circuits
Marks non-power-limited circuits

All others are supervised and power limited.
Segregate power-limited wiring from
non-power-limited wiring by at least 1/4 inch.

SUPERVISED AND POWER LIMITED

S

P

S

P

P

P

P

P

P

TO RC

TO ANNUNCIATOR

ON CABINET DOOR

J4 jumpers present

TYPICAL STYLE 4 (CLASS B) WIRING

SLC B-

SLC B+

Example SLC wiring 

Example RJ31X wiring 

Isolators (optional) separate each zone

TYPICAL STYLE 6 (CLASS A) WIRING

ZONE 1

SLC A-

SLC A+

SLC B-

SLC B+

SLC A-

SLC A+

SLC B-

SLC B+

ZONE 2

Isolators separate each detector
Remove J4 jumpers

Remove J4 jumpers

TYPICAL STYLE 7 (CLASS A) WIRING

TIP

HOUSE RING

TIP

TELCO

RING

GRAY

BROWN

GREEN

RED

 

Figure 3-1: Wiring on MB 

 

Содержание FireSpy Tracker T1000

Страница 1: ...Installation Manual FireSpy Tracker T1000 T2000 T8000 T2000E Fire Alarm Systems DOCUMENT REV CN 780 0867 C 1012...

Страница 2: ......

Страница 3: ...ule T8000 CM 10 2 3 8 Relay module T8000 RC 11 2 3 9 Serial relay module T8000 SRM 11 2 3 10 DACT communicator module T UDACT 11 2 3 11 Audio evacuation modules 12 2 3 12 City tie reverse polarity com...

Страница 4: ...B 2 4 Air Products 34 B 3 Conventional two wire smoke detectors for use with T8000 CM 35 B 3 1 Harrington Signal 35 B 3 2 Apollo 35 B 3 3 ESL Sentrol 37 B 3 4 System Sensor 37 B 4 Releasing devices f...

Страница 5: ...ure and properly labeled Fire Alarm Circuit Control A suitable battery set must be used to assure required operation in case of primary power loss The battery set must be replaced after 4 years or ear...

Страница 6: ...tice 1 2 Warranty Harrington Signal products are covered by a limited warranty See Harrington s warranty statement for more details document 780 0762 1 3 Support If you have any questions or concerns...

Страница 7: ...ator or with a PC The Tracker 8000 allows up to eight SLCs for a total of 2032 addressable points The SLCs are provided by the use of modular SLC boards which may be mounted in the main enclosure or r...

Страница 8: ...of the network connection System programming can be done from a PC or laptop through the serial port of the panel s communications adapter NOTE A Tracker network must include at least one T8000 panel...

Страница 9: ...T2000 T8000 SYSTEM MAY BE INDIVIDUALLY CONFIGURED AS NAC AUX POWER OR INPUT A SYSTEM MUST USE AT LEAST ONE INITIATING DEVICE TO NETWORK TO ONE OF PRINTER straight cable MODEM straight cable TO PC 290...

Страница 10: ...put current draw AC supply 1 8A 120VAC 2 15A 240VAC 24VDC power available total system current and max battery load 4A Battery charge voltage max 27 6V Battery charge current max 1 6A Battery capacity...

Страница 11: ...s A End of line resistance NAC mode Class B 10k ohm See Appendix C Wire Selection for suggested wiring distances Table 2 6 NAC specifications input mode MB MBC MBCLC Parameter Rating Input voltage inp...

Страница 12: ...distances 2 3 2 Display board T PDC The display board may mount either inside the enclosure door so its buttons are accessible with the door closed or on the chassis assembly MBC or MBCLC only so it i...

Страница 13: ...appropriately UL864 Listed custom enclosures to provide graphic annunciator capabilities The module may be configured to use either LED or incandescent lamps either type of output is supervised Up to...

Страница 14: ...l fire detection devices that are connected to conventional zone modules T8000 CM Each zone module provides 5 Class A zones or 10 Class B zones for FireSpy conventional devices Zone modules may be mou...

Страница 15: ...s 8 programmable relays It may be mounted in the main enclosure or remotely see Table 2 20 Table 2 17 Relay module T8000 SRM specifications Parameter Rating Input current draw Standby Alarm 30mA 230mA...

Страница 16: ...icates the number of watts available The speaker outputs can be configured as a Class A Style Z or Class B Style Y speaker zone The T2000E enclosure has space to connect up to two zone splitter module...

Страница 17: ...able 2 20 Enclosure dimensions and module mounting provisions T1 CAB T8000 CAB T2000 CAB T2000E CAB T8000 EXP Size inches Overall Backbox W x H x D 15 88 x 25 19 x 4 8 14 5 x 23 5 x 4 W x H x D 15 88...

Страница 18: ...ervice uses Type Service Signaling Required Equipment Local PPU A M SS WF R Non coded march time Proprietary PPU A M SS WF R Multiplex Remote Station PPU A M SS WF R DACT Reverse polarity T UDACT UCT...

Страница 19: ...ns E and F Verify that these values are within the limits of the power supply see table at the bottom 6 Verify that the current draw on each circuit is within the current limit of the circuit The seco...

Страница 20: ...bly MBCLC onto the enclosure studs with the board oriented as shown in Figure 3 8 T2000E Secure with 10 nuts Install optional accessories To install accessory assemblies follow the installation instru...

Страница 21: ...also require specific programming Refer to the programming manual for more instructions 3 4 Check system operation Initial acceptance testing is required before normal operation of the system Inspect...

Страница 22: ...Proper operation of all audible and visual trouble signals including ground fault indication when any conductor is grounded Proper operation of annunciators shall be verified including fault condition...

Страница 23: ...RELAY1 RELAY2 AUX I O BATT TROUBLE TO INTERNAL SERIAL MODULES A A B B SLC 10K USB SECNDRY PHONE PRIMARY PHONE PDC MB J4 SW1 LEDs FH1 FUSE 7 5A MAX CAUTION For continued protection against risk of fir...

Страница 24: ...tion ALL NACs ARE REGULATED 24 DC 24VDC P1 RS485 B A A B B A A B P7 NAC B A A B P8 NAC B A A B NC COM NO NC COM NO NC COM NO P9 NAC P6 J3 J4 J2 P3 P4 P5 NAC SUPV ALARM TROUBLE ALARM 24VDC TO SERIAL MO...

Страница 25: ...E REGULATED 24 DC NOTES 1 Use only smoke detectors that are listed in compatibility listing in owner s manual 2 Leave end of line resistors on unused circuits 3 All terminals are rated for 14 22 AWG w...

Страница 26: ...ray Segregate power limited wiring from non power limited wiring by at least 1 4 inch CAB MB BATTERY BATTERY USB PDC SECNDRY PHONE PRIMARY PHONE B A A B B A A B NAC2 B A A B NAC3 NAC1 RS485 RS485 A A...

Страница 27: ...ALARM TROUBLE ALARM J1 J2 J2 J1 B A A B B A A B P5 NAC B A A B P6 NAC B A A B P7 NAC P4 NAC NC COM NO NC COM NO NC COM NO P3 P4 P5 NC COM NO NC COM NO NC COM NO NC COM NO A A B B A A B B A A B B A A...

Страница 28: ...O NC COM NO NC COM NO RC RC Con10M Con10M J1 J2 J2 J1 NC COM NO NC COM NO NC COM NO NC COM NO RC RC BATTERY 1 BATTERY 1 BATTERY 2 J2 J1 SUPV ALARM TROUBLE ALARM SUPV ALARM TROUBLE ALARM BATTERY BATTER...

Страница 29: ...7 8 B A A B B A A B P5 NAC B A A B P6 NAC B A A B P7 NAC P4 NAC NC COM NO NC COM NO NC COM NO P3 P4 P5 RS485 P1 24VDC RS485 P2 24VDC RS485 TB1 24VDC A A B B A A B B A A B B A A B B RS485 TO LOWER MOD...

Страница 30: ...IAL SUPV ALARM TROUBLE ALARM NEU HOT EARTH TB1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 TB3 8 7 6 5 4 3 2 1 TB2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 1 11 S1 SN2 SN1 1 11 1 11 10K 10K HOT EARTH NEU MBC L...

Страница 31: ...1 1 1 T2 P 1 1 1 T2 P D 1 1 1 1 T8 EXP5 R 1 1 T8 EXP U 1 1 T8 EXP 2U 2 1 A 1 2 Board modules Model Description Reference Document T1 MB Main board set 780 0935 T8000 MBC Main board set 780 0862 T2000...

Страница 32: ...780 0858 T2000E CAB Main cabinet T2000E 780 0858 T8000 EXP Small expansion cabinet 780 0858 T8000 EXPD Small expansion cabinet for UDACT 780 0858 T8000 EXP5 Large expansion cabinet 780 0858 T8000 EXP...

Страница 33: ...Circuits Compatible smoke detectors with alarm verification LCU and MCCLC Class A and B Apollo 55000 550 650 886 Harrington TS8 DP TS8 DH TS8 DM B 2 Addressable SLC devices for use with T8000 LCU T200...

Страница 34: ...I Isolator base B200SR Sounder base Accessories 349 0667 M502M Conventional zone interface module 349 1069 CZ 6 Conventional zone interface module 6 zones 349 0509 M500M M500MB Input module 349 0497 M...

Страница 35: ...monitor unit IS816 ISpy Mini priority switch monitor module TSpy Series Harrington Part No Harrington Signal Model Series Description Detectors TS8 DP TSpy TSpy photo smoke detector TS8 DH TSpy TSpy p...

Страница 36: ...6 mounting base 45681 234 XP95 6 low profile mounting base 45681 242 XP95 4 low power relay mounting base 45681 250 XP95 E Z fit mounting base 45681 321 XP95 Short circuit isolating mounting base 4568...

Страница 37: ...Spy photo smoke detector 31 CS823 C Spy ion smoke detector 28 CS824 C Spy 135F heat detector with flashing LED and reed switch 28 CS825 C Spy 170F heat detector 28 CS826 C Spy 200F intermediate heat d...

Страница 38: ...200F intermediate Standard 55000 225 Series 65A ion detector flashing LED reed switch 55000 226 Series 65A ion detector flashing LED 31 55000 227 Series 65A ion detector standard 55000 325 Series 65A...

Страница 39: ...easing devices for use with a NAC on MB MBC MBCLC Refer to the installation document 780 0930 for proper wiring of releasing devices to the NAC Manufacturer Models Description Electrical rating Asco 8...

Страница 40: ...Contents 1 2 3 A B HSI 780 0867 FireSpy Tracker Installation Manual 36...

Страница 41: ...actance of a speaker or bell can be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite T tapping and starring are not recommended C 2 Wire length calculations...

Страница 42: ...input voltage for the device Eq C 3 Vdrop Idraw x Rpanel Rcable x DF2 Rdevices x DF2 Eq C 4 Rcable 2 x Rwire x 1000 x Ltotal Eq C 5 Lfirst Ltotal Lfirst x DF1 DF2 Ltotal Ltotal Eq C 6 Number of device...

Страница 43: ...ng resistance only These values were obtained using Eq C 1 with a maximum voltage drop of 2 4V Table 3 3 Wire Lengths for powering T8000 devices Module Voltage drop V Load mA Maximum distance to devic...

Страница 44: ...op current calculations were performed by using Eq C 3 with Vdrop 5 and solving for Idraw Table 3 5 Wire Lengths for Local RS485 Units 18 AWG 16 AWG 14 AWG 12 AWG Part number of cable referenced for r...

Страница 45: ...t case ft 15873 24390 40000 62500 Max distance capacitance candidate ft 6818 5172 5556 5000 Max distance wavelength candidate ft 4269 4269 4269 4269 Max distance worst case load distribution ft 4269 4...

Страница 46: ...Contents 1 2 3 A B C HSI 780 0867 FireSpy Tracker Installation Manual 42...

Страница 47: ...monitor module 0 0006 ISpy IS812 55000 806 Priority switch monitor module 0 0006 ISpy IS813 55000 820 Switch monitor in out module 0 000 85 ISpy IS814 55000 825 Sounder control module 0 001 ISpy IS816...

Страница 48: ...eSpy Tracker Installation Manual Harrington Signal Inc 2519 4th Ave P O Box 590 Moline IL 61265 800 577 5758 309 762 0731 FAX 309 762 8215 Because Lives Propertyand Businesses Aren t Fireproof www har...

Отзывы: