B. Clearances To Combustibles
A
C
D
B
F
E
E
C
D
B
A
Parallel
Installation
Inches
Millimeters
Back Wall To Unit Hopper
Side Wall To Unit
Back Wall To Flue Connector
Side Wall To Flue Connector
2 51
17 432
24 610
34 864
F
E
Corner
Installation
Inches
Millimeters
Walls to Unit Body
Walls to Flue Connector
15 381
24 610
C. Floor Protection Requirements
J
H
G
Floor Protection
Requirements
Inches
Millimeters
Sides
Front- measured from glass
Rear
8 203
12 305
18 457
Floor protection must be of a non-combustible materi-
al. It must be located under the appliance and extend
beyond the appliance according to the measure-
ments below. Floor protection must also extend under
any horizontal sections of chimney connector and 2"
(50.8mm) beyond each side of the connector.
DANGER:
The appliance legs may not be removed
for installation.
Minimum Size floor protection is 49½" Deep By 42¾"