 Dry Seasoned Wood Only!                                                              3-90-798                                                                 Save These Instructions

Oakleaf Woodburning stove

Hearth & Home Technologies welcomes you to our tradition of excellence! By choosing a Harman appliance, 
you have become part of our commitment to meeting the heating needs of consumers with the most distinctive, 
powerful and responsible home heating products available. 
The Oakleaf has huge features in an elegantly small package. With a heating capacity of 1400 to 1600 ft²,  The 
Oakleaf takes advantage of Harman’s 30+ years of stove design, technology and manufacturing. The Firedome 
secondary combustion system provides for super-clean burning and minimal maintenance. The top-loading feature 
makes for more convenient loading, with enough fuel for an all day burn.

We wish you and your family many years of enjoyment in the warmth and comfort of your hearth appliance.
Thank you for choosing Harman.

Harman

A division of

 

Hearth & Home Technologies, Inc.

352 Mountain House Road

Halifax, PA 17032

www.harmanstoves.com

When This Room Heater Is Not Properly 

Installed, a House fire May Result.  

To Reduce The Risk Of fire, follow 

The Installation Instructions.  Contact 

Local Building Or fire Officials About 

Restrictions And Installation Inspection 

Requirements In your Area.

This Label is located on the rear of the appliance. It contains important safety test information as well as the 

clearances to combustible materials. The label also contains the appliance serial number. For your records, 

copy your serial number and purchase date here.

Serial #: ________________________  

 

Date of Purchase: ________________________

Report #/ Raport # 135-S-26-6.2

Tested to / Testé à: UL1482-10, and ULC S627-00 

Test Date: August 2010
Approved For Use in Mobile/Manufactured Homes- 

USA ONLY

This appliance is also approved for installation into a shop.

“PREVENT HOUSE FIRES”

Install and use only in accordance with manufacturer’s installation and operation instructions 

and local codes. In absence of local codes, installation must meet minimum requirements of 

NFPA 211 in USA. Refer to manufacturer’s instructions and local codes for precautions required 

for passing chimney through a combustible wall or ceiling. 

WARNING FOR MANUFACTURED HOMES:

 (US Only) Do not install appliance in a sleeping 

room. An outside air inlet must be provided. The structural integrity of the manufactured home’s 

floor, walls, and ceiling must be maintained.

Flue connector pipe must be 6” diameter, minimum 24 MSG blue steel. Chimney must be factory   

                built 103HT or masonry construction.

                Contact Local Building or Fire Officials About Restrictions and Installation       

                Inspection In Your Area.

DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY SERVING ANOTHER APPLIANCE.

FOR USE WITH SOLID WOOD FUEL ONLY

 Do not burn coal.

DO NOT Overfire - If Heater or chimney connector glows, you are overfiring.

Optional Blower

 

Harman #1-00-797032:

 Electrical Rating 115 VAC, 60Hz, 1AMP Maximum 

Route power cord away from unit. 

Replace glass only with 5mm ceramic, available from your dealer.

Combustible flooring must be protected with an approved 0.45R hearth board.

Appliance must be installed with the legs attached. Do not obstruct airflow under the appliance.

DANGER: Risk of Fire or Explosion - Do not burn garbage,  gasoline, drain oil or other 

flammable liquids.

WARNING: Risk of Fire 

Do not operate with fuel loading or ash removal doors open. 

Do not store fuel or combustibles within marked clearances.

Inspect and clean chimney and connector regularly- Under certain conditions of use, 

creosote buildup may occur rapidly.

The Bypass Damper must be opened prior to opening any load or ash door.

Do not install a grate or otherwise elevate the fire.

OAKLEAF Woodburning Stove

Poêle Du Bois OAKLEAF

Serial No.

№ de série

008

Rapport no 135-S-26-6.2

Conforme à UL 1482-10 et ULC S627-00

Date d’essai: Aug. 2010

Homologué pour les maisons mobiles et préfabriquées - É.-U. SEULEMENT

Cet appareil est également homologué pour être installé dans un atelier.

«ÉVITEZ LES INCENDIES DE MAISON»

N’installez et n’utilisez cet appareil que selon le mode d’installation et le mode 

d’emploi  du  fabricant  et  les  codes  locaux.  En  l’absence  de  codes  locaux, 

l’installation doit au minimum être conforme aux exigences de la norme NFPA 

211 aux É.-U. Voir dans les recommandations du fabricant et dans les codes 

locaux les précautions quant au passage d’une cheminée à travers un mur ou 

un plafond combustible.

MISE EN GARDE POUR LES MAISONS PRÉFABRIQUÉES : (É.-U. seulement) 

N’installez pas cet appareil dans une chambre à coucher. Une arrivée d’air de 

combustion extérieur doit être prévue. L’intégrité structurelle du plancher, des 

murs et du plafond de la maison préfabriquée doit être maintenue.

Le tuyau de raccord à la cheminée doit être d’un diamètre de 15,25 cm (6 po), 

au  minimum  en  acier  bleu  24  MSG.  La  cheminée  doit  être  en  métal  103HT 

d’usine ou construite en maçonnerie.

NE RELIEZ PAS CE POÊLE À UNE CHEMINÉE QUI SERT POUR UN AUTRE 

APPAREIL.

IL NE FAUT UTILISER QUE DU BOIS EN BUCHES.

  Ne chauffez pas TROP. Si 

l’appareil ou le raccord de cheminée rougit, c’est que le feu est trop puissant.

Éloignez le cordon électrique de l’appareil.

DANGER: 

Risque  de  décharge  électrique.  Débranchez  la  prise  avant  tout 

entretien.  Pour plus de détails, consultez le mode d’emploi.

Ne remplacez le verre que par du verre céramique de 5 mm à obtenir de votre 

détaillant.

L’appareil doit être installé avec ses pieds fixés. N’obstruez pas le passage d’air 

sous l’appareil.

DANGER: 

Risque  d’incendie  ou  d’explosion.  Ne  brûlez  pas  d’ordures, 

d’essence, d’huile de vidange ni aucun autre liquide inflammable.

MISE EN GARDE:

 Risque d’incendie.

N’utilisez pas le poêle lorsque les portes du foyer et du cendrier sont ouvertes.

Gardez le carburant et les matériaux combustibles 

en dehors des dégagements prescrits.

Inspectez et nettoyez fréquemment les conduits et la cheminée.

J

H

G

Floor Protection 

Requirements

Inches Millimeters

Sides / Côtés
Front- from glass/Devant, par rapport au verre
Rear / Arrière

8             203

 8             203

18            457

CLEARANCE TO COMbUSTIbLES /

 

DISTANCES MINIMALES DE SECURITE:

Date of Manufacture / Date de fabrication:

2010  2011  2012  JAN   FEB   MAR   APR   MAY   JUN   JUL   AUG   SEP   OCT   NOV   DEC

Fabriqué par: Harman Home Heating 352 Mountain House Road, Halifax PA 17032 (É.-U.)

P.N. 3-90-797

IGN

CAUTION:

 

HOT  WHILE  IN  OPERATION.  DO  NOT  TOUCH.  KEEP 

CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS. 

SEE  NAMEPLATE  AND  INSTRUCTIONS.  KEEP  FURNISHINGS  AND 

OTHER COMbUSTIbLE MATERIALS A CONSIDERAbLE DISTANCE AWAY 

FROM THIS APPLIANCE.

ATTENTION:

 

CHAUD LORS DU FONCTIONNEMENT. NE TOUCHEZ 

PAS L’APPAREIL.GARDEZ LES ENFANTS ET LES VÊTEMENTS ÉLOIGNÉS. TOUT 

CONTACT PEUT ENTRAÎNER DES BRÛLURES DE LA PEAU.  RÉFÉREZ-VOUS À 

LA PLAQUE SIGNALÉTIQUE ET AU MODE D’EMPLOI. GARDEZ LE MOBILIER ET 

LES AUTRES MATÉRIAUX COMBUSTIBLES BIEN À L’ÉCART DE L’APPAREIL.

A C

D

b

E

F

F

C
D

b

A

Parallel 

Installation

Inches Millimeters

Back Wall / Entre mur arriereet l’appareil
Side Wall To Unit / Entre mur lateral et l’appareil
Back Wall To Flue Pipe / Entre  tuyau et le mur arriere
Side Wall To Flue Pipe / Entre tuyau et le mur lateral

14            330

17.5          444

17            432

26.75         679

F

E

Corner 

Installation

Inches Millimeters

Walls to Unit Body / Entre mur adjacent et l’appareil
Walls to Flue Pipe / Entre tuyau et le mur adjacent

14           330

21.75        552

Floor  protection  must  be  a  minimum  3/8” 

(9.5mm) of 0.84k material, or 0.45R. Must also 

be  placed  under  any  horizontal  sections  of 

flue connector, extending 2” (51mm) beyond 

the measurement of the pipe. Use of bottom 

heat shield required on protected floor.
Pour  protéger  le  plancher,  il  faut  sous  le 

poêle  un  matériau  (9.5mm  /  0.84k),  o  0.45R. 

Qui  doit  aussi  être  placé  sous  les  parties 

horizontales  du  tuyau  de  raccord  à  la 

cheminée et s’étendre à 51 mm (2 po) au-delà 

de la mesure du tuyau.

G

G

H

J

15.5”

5.875”

Made in U.S.A. of US and imported parts. / Fabriqué aux États-Unis-

d’Amérique par des pièces d’origine américaine et pièces importées.

E

REFER TO MANUFACTURER’S INSTRUCTIONS 

FOR CLEARANCES WITH ADDITIONAL VENT 

CONFIGURATIONS.

Содержание OAKLEAF

Страница 1: ...Comply with all minimum clearances to combustibles as specified Failure to comply may cause a house fire Check building codes prior to installation Installation MUST comply with local regional state...

Страница 2: ...U SEULEMENT Cet appareil est galement homologu pour tre install dans un atelier VITEZ LES INCENDIES DE MAISON N installez et n utilisez cet appareil que selon le mode d installation et le mode d empl...

Страница 3: ...Mobile Home US only A Mobile Home Installation 21 Section 7 Appliance Set Up A Outside Air Attachment 22 B Leveling The Appliance 22 C Optional Cooking Grill 22 D Optional Blower Kit 23 E Optional Rea...

Страница 4: ...must be properly grounded to the frame of the mobile home and must never be installed in a room designated for sleep ing The unit must have provisions for an outside air source when installed in a mob...

Страница 5: ...is designed to be as safe as possible it is important that you install a CO detector This is true for oil gas or coal burning products as well CO is not specifically heavier or lighter than air There...

Страница 6: ...is needed to replace what the chimney draws away through the appliance CAUTION Do NOT connect this unit to a chimney flue servicing another appliance Do NOT connect to any forced air distribu tion duc...

Страница 7: ...Follow these instructions for changing the direction First remove the upper rear heat shield by removing 8 tek screws that secure it Reaching upward through the firebox and the open bypass damper loos...

Страница 8: ...le 12 The optional air distribution blower has been installed properly 13 A properly grounded electrical receptacle is available within reach of the blower s power cord if installed WARNING WARNING In...

Страница 9: ...1 1990 Weight 430 lbs Flue Size 6 inch Log Length Recommended 18 Average Emissions 2 2 Grams Per Hr Outside Air size 4 5 inch I D 25 635mm 26 2 665 5mm 27 2 691mm 29 2 742mm 18 9 480mm 25 6 650mm Air...

Страница 10: ...Pipe to Ceiling 16 407 mm F Minimum Vertical 0 0 mm For clearance reduction methods refer to NFPA 211 or Local Codes Pipe clearance may be reduced using double wall or insulated connector pipe provid...

Страница 11: ...Side Wall 17 432 mm B Unit to Back Wall 13 330 mm C Vent Pipe to Side Wall 26 5 673 mm Corner Installation D Shield Corner to Wall 14 356 mm E NFPA 211 specifies clearance of 18 457 mm Although vent c...

Страница 12: ...lue the better the protection Example 1 inch of Durock 0 52R In all installations the area under and around the stove must be protected from falling ash and live coals The area under a horizontal run...

Страница 13: ...or roof space closet or other concealed space or through a floor or ceiling Whenever possible avoid passing the connector through a combustible C Wall Pass thrus Depending on your local building codes...

Страница 14: ...neys extend 3 ft 0 9 m above the highest point at which they exit from the roof Then the chimney must extend 2 ft 0 6 m above the highest point within a 10 ft 3 m radius Thus the 3 foot 2 foot 10 foot...

Страница 15: ...ferred method a breech pipe is a piece of steel pipe used the same way In Canada a breech pipe has ridges or protrusions to lock it firmly into the refractory cement In either case the chimney connect...

Страница 16: ...g Installation with Factory Built Chimney Chimney Cap Factory Built Metal Chimney Sealed Storm Collar Finishing Collar Chimney Connector Cathedral Ceiling Installation with Factory Built Chimney Roof...

Страница 17: ...per Joint of Chimney Connector Mantel and Trim Pro tection Floor Protection in Accordance with Solid Fuel Appliance Listing Airtight insulated Clean out Chimney Breach Fireplace Conversion with Non Co...

Страница 18: ...Seal with Non Combustible Material Floor Protection in Accordance with Solid Fuel Appliance Listing Airtight insulated Clean Out Damper Plate is Removed or Fastened in Open Posi tion Listed Fireplace...

Страница 19: ...ning system Follow liner manufacturer s instructions on insulation and support Floor Protection in Accordance with Solid Fuel Appliance Listing Damper Plate Removed or Fas tened in Open Position Floor...

Страница 20: ...rior Chimney or 2 Clearance for Interior Chimney and 2 Clear ance for NFPA 211 Type Approved Thimbles Floor Protection in Accordance with Solid Fuel Appliance Listing Check with your local building co...

Страница 21: ...vent manufacturer s instructions when installing in a mobile home 7 Installation shall be in accordance with the Manu factured Home and Safety Standard HUD CFR 3280 Part 24 8 The appliance must never...

Страница 22: ...ke flex pipe into the stub on the rear of the Oakleaf and secure it with aluminum tape This air intake will supply outside air for the secondary combustion within the FireDome 7 Secure the trim ring i...

Страница 23: ...rom the top vent shield and install the rear vent shield in it s place Height adjustment for blower use is done the same as with the top vent shield in place See D Optional Blower Installation above f...

Страница 24: ...d interfere with door operation safe loading and ash removal B General Operating Information 1 Draft Before you install and operate your Oakleaf wood stove please read the entire contents of this manu...

Страница 25: ...is where the volatile gases contained in the wood are released and burned This represents most of the wood s heating capacity The final stage is the charcoal stage where the charcoal burns the remaini...

Страница 26: ...imum air flow Ignite the paper and close the loading door s Allow this start up fire to burn for a few minutes keeping the bypass damper open Add about five more pieces of wood in the 2 to 3 inch 50 8...

Страница 27: ...imary air control lever too far to the right 3 Inadvertently leaving the damper open or 4 Not keeping up with routine maintenance such as checking door gaskets for wear Overfiring results in excessive...

Страница 28: ...ling During future burns be careful not to overload the stove with fuel so you will not be tempted to constantly operate at a low air control setting Other causes of poor ventilation or draft are icin...

Страница 29: ...or yard waste 2 Door Glass Frequency As needed Weekly By User Whenever the view of the fire is obstructed or weekly clean the glass using a soft cloth dampened with stan dard household glass cleaner...

Страница 30: ...s very important to clean all ashes at the end of the heating season When cleaning the chimney connector above the ap pliance keep the bypass damper in the open position This will keep any loosened ma...

Страница 31: ...Dry Seasoned Wood Only Oakleaf Woodburning Stove 10Reference Materials Variable Speed Switch Power Cord Blower Thermostat Rocker Grounded to housing Switch Black Wire White Wire 2 1 Oakleaf Optional B...

Страница 32: ...ollowing page Cast Iron Wood stove 1 90 797000 1 Black 1 90 797000 2 Charcoal 1 90 797000 3 Goldenfire Beginning Manufacturing date sept 2010 Ending Manufacturing date Active 1 2 7 6 8 23 22 3 4 5 28...

Страница 33: ...Round PSA 15 FT 1 00 2312 y 9 Brick Clip Set 1 00 249153 y 10 Damper Assembly 1 10 797103A y Damper Adjustment Kit 1 00 249142 y Damper Handle 3 50 00500S y Damper Plate 4 00 797113 y Damper Rod 1 10...

Страница 34: ...Nut FHN 5 16 18 Z 5 Pkg of 100 3 30 8005 100 y 21 Center Brick 3 40 797020 y Gasket 1 4 Round PSA 15 FT 1 00 2312 y 22 Brick 12 X 6 X 1 1 4 3 40 86125 y Brick Clip 1 Set 1 00 249172 y 23 Seal Plate 1...

Страница 35: ...after July 1 1990 0 8 5 Grams Per Hour SMOke 50 60 70 80 90 100 Wood heaters with higher efficiencies cost less to operate effIcIency Heat OutPut 9 600 to 24 700 btu use this to choose the right size...

Страница 36: ...truction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlie...

Страница 37: ...t of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enamel...

Страница 38: ...38 Dry Seasoned Wood Only 3 90 798 Save These Instructions Oakleaf Woodburning Stove Service Maintenance Log Date Of Service Performed By Description Of Service...

Страница 39: ......

Страница 40: ...Proudly Printed On 100 Recycled Paper...

Отзывы: