background image

23

maintenance - Cleaning

Combustion intake assembly latch

2. Remove the combustion intake assembly. See 

Fig. 35. The combustion intake assembly is held into 

place with two swing latches. See Fig. 37. Swing 

each latch until it hangs down away from the retainer 

stud. Now the assembly can be taken out by tilting 

the right side outward first through the lower door 

opening.

3. The  units  interior  is  now  ready  to  clean.  Use 

the scraper provided to clean the heat exchanger 

surfaces. A wire brush or short bristled brush is an 

excellent  cleaning  tool.  Clean  the  fan  blade  and 

combustion blower fan housing. NOTE: Be careful 

not  to  bend  the  fan  blade  while  cleaning. A  bent 

blade will throw the fan blade out of balance. See 

Fig. 38.

4.  With  the  blower  housing  open,  there  is  easy 

access to the flue pipe exiting the rear of the unit. 

See Fig. 38. Vacuum the flue pipe as far into the 

pipe as possible. NOTE: Be careful while cleaning 

the flue pipe not to bend the exhaust probe. The 

ESP is approximately 8" into the tube and is visible 

when looking into the exhaust.

 

Fig. 37

Fig. 38

ESP location

Содержание Accentra

Страница 1: ...SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authority such as municipal...

Страница 2: ...curred If creosote has accumulated it should be removed to reduce the risk of a chimney fire Guidance on minimizing creosote formation and the need for periodic creosote removal The chimney should be...

Страница 3: ...t once a year To remove the feeder cover Remove the 5 16 wing nut Lift the cover off of the tab at the top and the threaded stud Inspect and clean the inner chamber if necessary See above picture Rein...

Страница 4: ...to clean the heat exchanger surfaces A wire brush or short bristled brush is an excellent cleaning tool Clean the fan blade and combustion blower fan housing NOTE Be careful not to bend the fan blade...

Страница 5: ...lps knock scale off of the igniter element Figure 41 The igniter is made to be removable for service by insulated male female wire connectors These connections between the hot leads the wires inside t...

Страница 6: ...ic circuit that continuously monitors the ESP and Room Sensor for faults If a fault should occur the control sends a status alert and at the same time the unit goes down to minimum feed minimum burn a...

Страница 7: ...code 1 No pellets in hopper 2 Draft setting is too low 3 Something is restricting fuel flow 4 Hopper lid not closed properly 5 Power failure or blown fuse SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fu...

Отзывы: