3 5
Alarm will act as a
¡ O R¡–condition against all channels.
(* OR condition : If any channel out of total 8 channels exceed ed alarm setting value,
alarm output happened )
¡ H ysterisis against alarm is set up as ¡ 2 ¡
¡ When setting Wait Alarm, in the below mentioned occasion, waiting movements will
be operated.
In case of starting operation for the first time.
In case of changing set value
Set Value was changed due to the change of zone.
ƒUInitial
Value
&
Setting
Range
in
accordance
with
Alarm
Type
5
-
3.
ALARM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Alarm No
Alarm Ty pe
Initial Value
Setting Range
No Alarm
U p per limit Alarm hysterisis
Lower limit Alarm hysterisis
U p per & Lower limit Alarm hysterisis
Alarm within it range
U p per limit hysterisis hold alarm
Lower limit hysterisis hold alarm
U p per&Lower limit hysterisis hold alarm
Hold alarm within range
Absolute upper limit alarm
Absolute lower limit alarm
Absolute upper limit hold alarm
Absolute lower limit hold alarm
SV upper limit alarm
SV lower limit alarm
LBA/HBA Alarm
FAIL alarm
-
EUS (100 %)
EUS (100 %)
EUS (100 %)
EUS (0 %)
EUS (100 %)
EUS (100 %)
EUS (100 %)
EUS (0 %)
EU (100 %)
EU (0 %)
EU (100 %)
EU (0 %)
EU (100 %)
EU (0 %)
-
-
-
EUS (-100~ 100 %)
EUS (-100~100 %)
EUS (0 ~ 100 %)
EUS (0 ~ 100 %)
EUS (-100 ~ 100 %)
EUS (-100 ~ 100 %)
EUS (0 ~ 100 %)
EUS (0 ~ 100 %)
EU (0 ~ 100 %)
EU (0 ~ 100 %)
EU (0 ~ 100 %)
EU (0 ~ 100 %)
EU (0 ~ 100 %)
EU (0 ~ 100 %)
-
-
¡ If you select in Alarm No. 15 in ALT1, LBA Alarm will operate. If you select in
Alarm No. 15 in ALT2,3, HBA alarm will operate.
¡ HBA alarm could be operated only in case output type is RELAY or SSR output.
¡ You can select within its setting range : -1999 ~ 9999
3 4
§ ‰
˙˙
§ Cancel Auto-Tuning
If the below conditions happened, Auto-Tuning will be cancelled.
ƒU Burn-out or ADC error on account of broken sensor input cable.
ƒU Auto-Tuning parameter was OFF during Auto-Tuning.
ƒU In case of Power Off
ƒU In case of changing into RUN/STOP mode.
After finishing Auto-Tuning, changed parameters are PB,AR,TI,TD and LBA. If AT is
cancelled, controller will be back to the previous PID and LBA value and it starts
control. After Auto-Tuning, If control is not working smoothly, please adjust value of
PID integral number to meet suitable controller¡
fl
s value.
This function is used when you want to set same value up from channel 1 to channel 8
in the designated zone.
1 -> 2 -> 3 -> 4 -> 5 -> 6 -> 7 -> 8-> A
¡ A ¡–will be shown om CH display window,
¡ ----
¡ will be shown on SV window. At
this time, please set set-value up by , , key. If you press ENT key, same
value will be set up from channel 1 to channel 9.
If you press key, parameter which can operate
Auto-Tuning will show up as left picture.
C H
ZO N E
P V
S V
If you press key one time, key turns on and off a light.
In this time, if your press
¡
¡–key it stops turning on and off
a light and then AT ramp will turn on and off a light.
C H
ZO N E
P V
S V
5
-
2.
Batch
Setting