§ STP : Stop Bit
§ DLN : Data Length
§ R PT : Response Time
Initial value : 1
Setting range
: 1 ~ 2
Contents
: Set Communication Stop Bit.
If communication option is chosen,
Parameter is displayed
C H
ZO N E
P V
S V
Initial value : 7
Setting range
: 7 ~ 8
Contents
: Set Communication Data Length. .
If communication option is chosen,
Parameter is displayed
C H
ZO N E
P V
S V
Initial value :
0
Setting range
: 0 ~ 10
Contents
: Set Communication Response Time.
If communication option is chosen,
Parameter is displayed. Response
time = Processing time+ RPT * 20ms
C H
ZO N E
P V
S V
§ PRI : Parity
Initial value :
0
Setting range
: 0 ~ 2
Contents
: Set Communication Parity
If communication option is chosen,
Parameter is displayed
C H
ZO N E
P V
S V
2 6
§ Filter
§ ADDR : Address
§ BPS : Bits per Second
Initial value :
OFF
Setting range
: 0 ~ 120 s
Contents
: Set the first time of delayed filter to
re m ove any noise in the measured input
value.
C H
ZO N E
P V
S V
§ C T : Cycle Time
Initial value
: Relay 20 s, SSR & TRIAC : 2 s
Setting range
: 1 ‘~ 100 s
Contents
: Set the cycle of control output.
Set output cycle in case of Relay,
Pulse & Triac output. It is not applied in
case of Current output.
C H
ZO N E
P V
S V
Initial value : 1
Setting range
: 1 ~ 99
Contents
: If communication option is chosen,
Parameter is displayed.
It is appointed address of instrument in
case of RS232/485/422 communication.
Refer to Communication manual in detail.
C H
ZO N E
P V
S V
Initial value :
0
Setting range
: 0. 1
Contents
: Set type of Communication Protocol
0 : pc link sum None
1 : pc link sum Existed
C H
ZO N E
P V
S V