3
Parameter
Operation description
● POWER ON DELAY
● uses 1 set time (set time displayed on SV display)
● when power is applied, output turns OFF, timing starts
● when displayed time reaches set time, output turns ON,
displayed time is held (ONE-SHOT output selectable)
POND
● POWER ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV
display, Ton set time displayed on SV display)
● when power is applied, OFF timing starts
● when displayed time reaches Toff set time, output turns ON,
after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, output turns OFF,
after displayed time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff
set times
PFKF
● POWER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF,
after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON,
after displayed time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff
set times
PFKN
● POWER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when power is applied, output turns ON, timing starts
● when displayed time reaches set time, output turns OFF,
displayed time is held
PINT
● TWIN - ON START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output
turns ON, ON timing starts
● when displayed time reaches Ton set time OUT1 output turns
ON, OUT2 output turns OFF, after displayed time initialization
OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
OFF, holds output and displayed time
TWON
● TWIN - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV
display, Ton set time displayed on SV display)
● when power is applied, OUT1 and OUT2 outputs turn OFF, OFF
timing starts
● when displayed time reaches Toff set time, OUT2 output turns
ON, after displayed time initialization ON timing starts
● when displayed time reaches Ton set time, OUT1 output turns
ON, holds output and displayed time
TWOF
● STAR – DELTA
● uses 2 set times, Ton and Toff (Ton set time displayed on PV
display, Toff set time displayed on SV display)
● when power is applied, OUT1 output turns OFF, OUT2 output
turns ON, ON timing starts
● when displayed time reaches Ton set time, OUT2 output turns
OFF, after displayed time initialization OFF timing starts
● when displayed time reaches Toff set time, OUT1 output turns
ON, holds output and displayed time
● OUT1 operates as 'Δ' output, OUT2 operates as ' ' output.
● Toff set time is 'Δ - ' operation switching time
S - D
Parameter
Operation description
● SIGNAL ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts (START signal holds ON status )
● when displayed time reaches set time output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● When START signal is cancelled, initializes output and displayed time
SOND
● SIGNAL ON FLICKER - OFF START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
set time displayed on SV display)
● when START signal is applied,OFF timing starts (START signal holds ON status)
● when displayed time reaches Toff set time, output turns ON, after displayed
time initialization ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
time initialization OFF timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● when START signal is cancelled, initializes output and displayed time
SFKF
● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
holds ON status )
● when displayed time reaches set time output turns OFF,displayed time is held
● When START signal is cancelled, initializes output and displayed time
SINT
● SIGNAL ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● When START signal is applied, output turns ON, timing starts (START signal
holds ON status )
● when displayed time reaches set time, output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time
SNFN
● SIGNAL ON/OFF DELAY - OFF START
● uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff
set time displayed on SV display)
● when START signal is applied, ON timing starts
● when displayed time reaches Ton set time output turns ON,displayed time is held
● When START signal is cancelled, output holds ON output status,OFF timing starts
● when displayed time reaches Toff set time output turns OFF, displayed
time is held
SNFF
● SIGNAL OFF DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON (START signal holds ON
status )
● when START signal is cancelled, holds output and timing starts
● when displayed time reaches set time output turns OFF, displayed time is held
● when START signal is cancelled, initializes output and displayed time
SOFD
● SIGNAL TRIGGER ON DELAY
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, timing starts
● when displayed time reaches set time output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● when START signal is repeatedly applied, only uses the first START signal
S.OND
● SIGNAL TRIGGER ON FLICKER - ON START
● uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton
set time displayed on SV display)
● when START signal is applied, output turns ON, ON timing starts
● when displayed time reaches Ton set time output turns OFF, after displayed
time initialization OFF timing starts
● when displayed time reaches Toff set time, output turns ON, after displayed
time initialization ON timing starts
● output repeats ON/OFF operations according to Ton and Toff set times
● When START signal is repeatedly applied, only uses the first START signal
S.FKN
● SIGNAL TRIGGER ON INTERVAL
● uses 1 set time (set time displayed on SV display)
● when START signal is applied, output turns ON, timing starts
● when displayed time reaches set time output turns OFF, displayed time is held
● When START signal is repeatedly applied, only uses the first START signal
● after reaching set time, when START signal is applied,
output turns ON, and after time value initialization timing starts
S.INT
● SIGNAL TRIGGER ON DELAY – RESET
● when START signal is applied, timing starts
● when displayed time reaches set time, output turns ON, holds output and
displayed time (ONE-SHOT output selectable)
● when START signal is re-applied during timing, timing starts after displayed
time initialization
S.ODR
Operation overview
LT4
LT4S