Seven Day Two Channel Electronic Timeswitch

Model 852

Installation and Wiring Instructions

The model 852 timeswitch must be installed by a competent 
electrician and the installation should conform to IEE Wiring 
Regulations.

Installation and Wiring

Slacken the four fi xing screws, one in each corner 
of the unit, and carefully separate the front and rear 
portions. Unplug the ribbon cable from the rear portion. 
CAUTION: Do not allow either half of the unit to hang 
by the ribbon cable as damage could be caused. 

Remove the polystyrene packing piece from the top 
of the transformer. It is marked “REMOVE”.

Select the desired fi xing position and observe the label 
“THIS WAY UP” inside the rear portion. The two halves 
will only assemble correctly one way round. 

4 Four 

fi xing holes are provided for attaching the rear 

portion to the wall or mounting surface.Conduit box 
adaptors as shown below are availabe if required. 

Surface cable entries to the unit can be made from 
above, below or from the lefthand side. Conduit or 
recessed cable entry is through the aperture in the 
rear moulding. 

N

L

1

2

3

4

5

6

Links for 230V 
control 
circuit(s)

230V 50Hz 

Mains Supply

Channel 2

OFF

ON

Channel 1

OFF

ON

MK8-852 (3016  12/01)

N

L

6

PART NO: 8/3223 Double Gang Surface Box Adaptor

CABLE
ENTRY

APERTURE

2 fixings for 

double gang 

surface box

Alternative 4 fixings 

for double gang 

surface box

4 fixings 

for MK8 

timeswitch

PART NO: 8/3222 Square Conduit Box Adaptor

For surface cable entry remove the appropriate 
knockout and ensure one of the cable clamps is 
positioned correctly.

Connections to the unit should be made as shown 
below:

If the control circuits are to operate at 240V then 
terminals L, 1 and 4 must be linked, ensuring that the 
cable is sheathed and of a size to carry the required 
load current. 

If the control circuits are operating at voltages other 
than 230V then terminals 1 and 4 should be connected 
to the required power supply and not to terminal L.

8.    Upon completion of wiring, plug in the ribbon cable 

ensuring the polarised plug is fully inserted into the 
socket. Refi t the front half of the timeswich ensuring 
correct alignment and that no cables are trapped before 
re-tightening the screws. 

CABLE
ENTRY

APERTURE

4 fixings for existing 

square conduit box

4 fixings for 

MK8 timeswitch