4 . The deviation, Ti and Td can be calculated from the fol-
lowing:
• Deviation = Tx * max . slope (pH or mV)
• Ti = Tx / 0 .4 (minutes)
• Td = Tx * 0 .4 (minutes) .
5 . Set the above parameters and restart the system with the
controller in the loop . If the response has too much over-
shoot or is oscillating, then the system can be fine-tuned
slightly increasing or decreasing the PID parameters one
at a time .
Example:
the chart recording in the figure
aside was obtained continuously
dosing an alkaline solution to a
weak acid solution in a tank . The
initial settings will be:
Max . slope = 3 pH/5 mins =
0 .6 pH/min
Time delay = Tx = approx . 7 mins
Deviation
= Tx * 0 .6 = 4 .2 pH
Ti
= Tx / 0 .4 = 17 .5 mins
Td
= Tx * 0 .4 = 2 .8 mins
ALARM RELAY
The alarm relay functions in the following manner:
During normal operation (no alarm condition) the alarm
relay is energized; during an alarm condition or power
failure the relay will be de-energized . As long as a separate
battery power system is used an alarm will sound .
Example:
High alarm set at 10 pH
Low alarm set at 4 pH