28
Code
Valid Values
Default
Present
for ORP
C .53 Wednesday hold mode
enable
“OFF”: Disabled
“On”: Enabled
“OFF”
yes
C .54 Thursday hold mode enable
“OFF”: Disabled
“On”: Enabled
“OFF”
yes
C .55 Friday hold mode enable
“OFF”: Disabled
“On”: Enabled
“OFF”
yes
C .56 Saturday hold mode enable
“OFF”: Disabled
“On”: Enabled
“OFF”
yes
C .57 Sunday hold mode enable
“OFF”: Disabled
“On”: Enabled
“OFF”
yes
C .60 Proportional control mode
period
01:00 - 30:00 minutes
05:00
yes
C .70 Hold mode end delay
00 to 99 seconds
00
yes
RELAYS (“rELA”)
0 .01 Relay 1 mode
(see notes 19, 21)
“OFF”: Disabled
“SEt1”: Control, setpoint 1
“SEt2”: Control, setpoint 2
“SCLE”: Simple cleaning
“HOLd”: Energized in hold mode
“SEt1”
yes
0 .02 Relay 2 mode
(see notes 19, 21)
“OFF”: Disabled
“SEt1”: Control, setpoint 1
“SEt2”: Control, setpoint 2
“SCLE”: Simple cleaning
“HOLd”: Energized in hold mode
“SEt1”
yes
0 .03 Relay 3 mode
(see notes 15, 19)
“OFF”: Disabled
“SCLE”: Simple cleaning
“ACLE”: Advanced cleaning /
“HOLd”: Energized in hold mode
“OFF”
yes
0 .04 Relay 4 mode
(see notes 15, 19)
“OFF”: Disabled
“SCLE”: Simple cleaning
“ACLE”: Advanced cleaning /
“HOLd”: Energized in hold mode
“OFF”
yes
0 .05 Hold digital output
“OFF”: Disabled
“HOLd”: Enabled upon hold
mode
“HOLd”
yes
ANALOG OUTPUT #1 (“Out1”)
0 .10 Analog output 1 mode
(see notes 6, 21)
“rECO”: Recorder
“SEt”: Control, setpoint 1
“rECO”
yes
0 .11 Analog output 1 type
“0-20”: 0-20 mA
“4-20”: 4-20 mA
4-20 (6)
yes