5

 If water is present downstream of the dryer, 

always verify that any condensate drains installed upstream of 

the dryer are draining properly before attempting to readjust 

the LED setting.

1.  For minimum inlet air pressures that fall between column 

values, the setting for the lower pressure is recommended. 

(i.e. select the 300 psi column values for 324 psi inlet pres

-

sure listed in Table 1.)

2.  Where the dryer is consistently operating at less than max

-

imum capacity, it may be possible to increase the LED set 

point to minimize air loss. Discretionary adjustments to the 

dryer should only be made on a hot, humid day when the 

maximum expected air load is flowing through the dryer. 

Failure to do so may prevent the condensate from draining 

completely when operating under peak load conditions.

Table 1  Timed drain illuminated LED Settings

Inlet Pressure

300

400*

500

600

725

Dryer Model

4

1

1

2

2

2

6

1

1

1

1

2

7.5

1

1

1

1

2

10

1

1

1

1

1

*  Recommended and pre-programmed factory settings for each model dryer. 

Assumes inlet conditions with 120°F ambient and 10°F air-cooled aftercooler 

approach temperature.

Table 2  Timed drain illuminated LED Settings

LED

Illuminated

Minutes

between

Drain Cycles

1

st

1

2

nd

3

3

rd

5

4

th

10

5

th

20

6

th

30

7

th

40

8

th

50

9

th

60

2.0  OPERATION

2.1  Minimum/Maximum Operating Conditions

A.

 

Maximum inlet air pressure:  725 psig (50 barg)

B.  Minimum inlet air pressure:  15 psig (1.0 barg) 
C.  Maximum inlet air temperature:  120°F (49°C)

D.

 

Maximum ambient temperature: 

Air-cooled models:  110°F (43°C) 

Water-cooled models:  130°F (54°C)

E.  Minimum ambient temperature:  40°F (4°C)

Condensate 

Draining

Drain

Push-to-Test

On/Off 

Switch

Switch Legend

Power On 

Light

Compressor 

On Light

Dew Point

Temperature

Indicator

2.2  Start-up

IMPORTANT:

 Energize dryer disconnect switch (provided by 

others, see NEC) 24 hours before refrigeration compressor 

is started! Never use the disconnect switch to shut-down the 

dryer for a extended period of time (except for repair). Failure 

to follow these instructions may result in a non-warrantable 

compressor failure.

NOTE:

 It is recommended that dryer be started 15 minutes 

before compressed air flow begins.

NOTE:

  If there is no power to the control board for a period 

of two weeks or more, it may return to the default mode.

1.   Confirm On/Off Switch is in the “Off” position.
2.  Check for proper electrical voltage.
3.  Energize dryer disconnect switch (see IMPORTANT note 

above)

4.  For water-cooled models: after 24 hours, begin cooling 

water flow.

5.   Toggle ON/OFF switch to the ON position to energize 

dryer. Green power-on light will illuminate.

6.  Slowly pressurize unit air side by opening inlet isolation 

valve. Check for leaks.

7.  After 15 minutes, open outlet isolation valve slowly.

8.  Close air by-pass valve.

2.3  Timer Drain
NOTE: 

 The Timer Drain LED level has been pre-programmed 

at the factory for your specific dryer model. Programming is 

based upon a minimum of 400 psig saturated inlet air pressure 

and maximum energy efficiency. The drain open time is fixed 

at one second and a small amount of air will be exhausted with 

each cycle. Generally, no adjustment to the timer is required.

Содержание HPET Series

Страница 1: ...ION 3 2 0 OPERATION 5 3 0 MAINTENANCE 6 SIZING 7 ENGINEERING DATA 8 P I DIAGRAM 9 WIRING DIAGRAMS 10 12 DIMENSIONS WEIGHTS 13 TROUBLESHOOTING GUIDE 14 PARTS LIST 15 WARRANTY 16 INSTRUCTION MANUAL HPET...

Страница 2: ...plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you in sist tha...

Страница 3: ...110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C E The installation of a flexible connection prior to the dryer is recommended to prevent possible damage from vibration NOTE Outdoor installation St...

Страница 4: ...requency listed on the serial number tag B Electrical entry on larger dryers is through a hole in the cabinet It is located on the right side panel when facing the front of the unit Connect power sour...

Страница 5: ...aximum ambient temperature Air cooled models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C Condensate Draining Drain Push to Test On Off Switch Switch Legend Power O...

Страница 6: ...Operating Check Points Check the following on a periodic basis A Green power on light is illuminated B Dew point indicator is in green area C Condensate is discharging from drain Condensate Draining...

Страница 7: ...nnually To facilitate service maintenance kits are available SIZING Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at vari ous operat...

Страница 8: ...oltage 207 253 Input Power Rated Flow watts 5 010 7 710 9 710 14 400 Minimum Circuit Ampacity 25 4 28 0 48 0 63 0 Maximum Overcurrent Protector amps 40 45 75 100 Compressor Rated Load Amps 8 2 9 3 15...

Страница 9: ...ER REHEATER AIR AIR HEAT EXCHANGER PRE COOLER REHEATER EVAPORATOR EVAPORATOR EVAPORATOR HEAT EXCHANGER SET 3 USED ON MODELS 7 5 10 HEAT EXCHANGER SET 2 HEAT EXCHANGER SET 1 HIGH TEMPERATURE SWITCH OPT...

Страница 10: ...30 31 32 33 34 35 36 37 38 39 40 41 42 43 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 3 PHASE 60 Hz TB1 L1 L2 L3 PE DISCONNECT L1 L2 L3 L1 L1 L1 L3 L2 T1 L2 L2 L3 L3 T1 T2 T2 T3...

Страница 11: ...1 LINE NEUTRAL THERMISTER THERMISTER DRAIN NEUTRAL DRAIN LINE COMPRESSOR N 3 CONTROL BOARD 4NO 3NO 5 CONT 1 X X TB2 3 TB2 DRAIN HARNESS BLUE BROWN GRN YELLOW DRAIN HARNESS 3 X TB2 PE PE 2 3 1 TEST ALM...

Страница 12: ...Transformer Pack TB1 L1 L2 L3 PE TB1 CONNECTION 460 3 60 460V 1 2 3 PE H4 H3 H2 H1 G X4 X3 X2 X1 H4 H3 H2 H1 G X4 X3 X2 X1 1 2 3 PE 575V L1 L2 L3 PE TRANSFORMER 1 CUSTOMER CONNECTION 575 3 60 575V VOL...

Страница 13: ...rposes FRONT VIEW RIGHT SIDE VIEW BOTTOM VIEW DETAIL A DETAIL B CONDENSER AIR FLOW A B 3 76 1 25 1 25 ELECTRICAL ENTRY 1 4 18 FPT DRAIN CONNECTION 3 4 14 NPT FEMALE I O WATER CONNECTIONS HPET 4 W C MO...

Страница 14: ...refrigeration system improperly functioning 3 Inlet air strainer clogged 4 Separator filter element clogged Check flow rate See D below Clean inlet air strainer Replace filter element C High Temperatu...

Страница 15: ...pansion Valve 3232550 3232550 3232550 3232532 De Superheating Valve 3232542 3232542 3232542 3232531 Liquid Line Filter Dryer 4006402 4006402 4006402 4006402 Suction Filter 4006414 4006414 Cooling Wate...

Страница 16: ...ARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A...

Отзывы: