HANKISON HPET Series Скачать руководство пользователя страница 4

4

1.2  Mounting 

Mount the dryer on a level solid surface.  Holes are provided in 

the dryer base to permanently mount the dryer to the floor.

1.3  Piping Connections 

A.  Air Inlet - Connect compressed air line from air source 

to air inlet.  (Reference markings on dryer or see callout 

drawing on page 13 for air inlet/outlet connection loca

-

tions.)  

 

NOTE:

  Customer piping needs to be properly supported.  

Use back-up wrench when making piping connections.

  

Refer to Serial Number Tag for maximum 

working pressure.  Do not exceed dryer’s Maximum Working 

Pressure.

NOTE:

  Install dryer in air system at highest pressure possible 

(e.g. before pressure reducing valves).

NOTE:

  Install dryer at coolest compressed air temperature 

possible.  Maximum inlet compressed air temperature: 120°F 

(49°C).  If inlet air exceeds this temperature, precool the air 

with an aftercooler.  
B.  Air Outlet – Connect air outlet to downstream air lines.

 

NOTE:

  Customer piping needs to be properly supported.  

Use back-up wrench when making piping connections.

C.  Bypass piping – If servicing the dryer without interrupting 

the air supply is desired, piping should include inlet and 

outlet valves and an air bypass valve.

D.  Water cooled models – cooling water inlet and outlet

1.  Connect cooling water supply to cooling water inlet.

2.  Connect cooling water return line to cooling water 

outlet connection.

NOTE:

  Strainer and water regulating valve are supplied on 

water cooled models.

1.4  Electrical Connections
IMPORTANT:

  Use copper supply wires only.

A.

 

Dryer is designed to operate on the volt-

age, phase, and frequency listed on the 

serial number tag.

B.  Electrical entry on larger dryers is through 

a hole in the cabinet.  It is located on the right side panel 

when facing the front of the unit.  Connect power source 

to terminal strip in electrical enclosure as shown on the 

wiring diagram included with the dryer.

NOTE:

  Refrigeration condensing unit is designed to run con

-

tinuously and should NOT

 be wired to cycle on/off with the air 

compressor.

1.5  Moisture Separator 

A.  Separator has an external drain which auto

-

matically discharges collected condensate. 

 

NOTE:

 It may be desirable to pipe the con-

densate from the Automatic Drain outlet to a 

suitable drain.

B.  For manual draining, convenient dryer depressurization, 

and drain valve maintenance, a three-way valve assembly 

is installed between the drain port on the moisture separa-

tor and the drain valve.  On all models, the three-way 

valve is mounted to the base pan.  Review the following 

for proper drain function:
•  Automatic Draining - Valve handle should be positioned 

parallel to the valve body (as shown), with the arrow 

on the handle pointing toward the drain valve.  In this 

position, condensate will flow from the bowl to the drain 

valve.

•  Drain Isolation (Shutdown) - Valve handle shall be 

turned perpendicular to the valve body (rotate 90°).  In 

this position, condensate flow is shutoff. 

Solenoid Valve

Automatic Discharge

Line

Manual Discharge Line

3-Way Valve

Drain Inlets

•  Manual Draining - Drain valve handle shall be rotated 

slightly past the drain isolation position to allow 

throttling through the valve for manual discharge and 

depressurization.

NOTE:

  Discharge is at system pressure. Drain line should be 

anchored.

NOTE:

  Condensate may contain oil. Comply with applicable 

laws concerning proper disposal.

Содержание HPET Series

Страница 1: ...ION 3 2 0 OPERATION 5 3 0 MAINTENANCE 6 SIZING 7 ENGINEERING DATA 8 P I DIAGRAM 9 WIRING DIAGRAMS 10 12 DIMENSIONS WEIGHTS 13 TROUBLESHOOTING GUIDE 14 PARTS LIST 15 WARRANTY 16 INSTRUCTION MANUAL HPET...

Страница 2: ...plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you in sist tha...

Страница 3: ...110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C E The installation of a flexible connection prior to the dryer is recommended to prevent possible damage from vibration NOTE Outdoor installation St...

Страница 4: ...requency listed on the serial number tag B Electrical entry on larger dryers is through a hole in the cabinet It is located on the right side panel when facing the front of the unit Connect power sour...

Страница 5: ...aximum ambient temperature Air cooled models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C Condensate Draining Drain Push to Test On Off Switch Switch Legend Power O...

Страница 6: ...Operating Check Points Check the following on a periodic basis A Green power on light is illuminated B Dew point indicator is in green area C Condensate is discharging from drain Condensate Draining...

Страница 7: ...nnually To facilitate service maintenance kits are available SIZING Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at vari ous operat...

Страница 8: ...oltage 207 253 Input Power Rated Flow watts 5 010 7 710 9 710 14 400 Minimum Circuit Ampacity 25 4 28 0 48 0 63 0 Maximum Overcurrent Protector amps 40 45 75 100 Compressor Rated Load Amps 8 2 9 3 15...

Страница 9: ...ER REHEATER AIR AIR HEAT EXCHANGER PRE COOLER REHEATER EVAPORATOR EVAPORATOR EVAPORATOR HEAT EXCHANGER SET 3 USED ON MODELS 7 5 10 HEAT EXCHANGER SET 2 HEAT EXCHANGER SET 1 HIGH TEMPERATURE SWITCH OPT...

Страница 10: ...30 31 32 33 34 35 36 37 38 39 40 41 42 43 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 3 PHASE 60 Hz TB1 L1 L2 L3 PE DISCONNECT L1 L2 L3 L1 L1 L1 L3 L2 T1 L2 L2 L3 L3 T1 T2 T2 T3...

Страница 11: ...1 LINE NEUTRAL THERMISTER THERMISTER DRAIN NEUTRAL DRAIN LINE COMPRESSOR N 3 CONTROL BOARD 4NO 3NO 5 CONT 1 X X TB2 3 TB2 DRAIN HARNESS BLUE BROWN GRN YELLOW DRAIN HARNESS 3 X TB2 PE PE 2 3 1 TEST ALM...

Страница 12: ...Transformer Pack TB1 L1 L2 L3 PE TB1 CONNECTION 460 3 60 460V 1 2 3 PE H4 H3 H2 H1 G X4 X3 X2 X1 H4 H3 H2 H1 G X4 X3 X2 X1 1 2 3 PE 575V L1 L2 L3 PE TRANSFORMER 1 CUSTOMER CONNECTION 575 3 60 575V VOL...

Страница 13: ...rposes FRONT VIEW RIGHT SIDE VIEW BOTTOM VIEW DETAIL A DETAIL B CONDENSER AIR FLOW A B 3 76 1 25 1 25 ELECTRICAL ENTRY 1 4 18 FPT DRAIN CONNECTION 3 4 14 NPT FEMALE I O WATER CONNECTIONS HPET 4 W C MO...

Страница 14: ...refrigeration system improperly functioning 3 Inlet air strainer clogged 4 Separator filter element clogged Check flow rate See D below Clean inlet air strainer Replace filter element C High Temperatu...

Страница 15: ...pansion Valve 3232550 3232550 3232550 3232532 De Superheating Valve 3232542 3232542 3232542 3232531 Liquid Line Filter Dryer 4006402 4006402 4006402 4006402 Suction Filter 4006414 4006414 Cooling Wate...

Страница 16: ...ARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A...

Отзывы: