HANKISON HPET Series Скачать руководство пользователя страница 14

14

SYMPTOM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

A)  Water downstream of dryer

1.  Residual free moisture remaining in 

downstream pipelines.

2.  Air bypass system is open.

3.  Inlet and Outlet connections are reversed.

4.  Temperatures surrounding air lines 

downstream of dryer have dropped below 

dryers dew point rating.

5.  Excessive free moisture (bulk liquid) at dryer 

inlet.

6.  Condensate not being automatically drained 

 

Drain mechanism is clogged or inoperative.

 

Drain line is restricted or frozen.

 

Electric drains-timer not set to allow for 

sufficient condensate removal. 

7.  Dryer overloaded resulting in elevated dew 

point.

8.  Refrigeration system not functioning properly 

resulting in elevated dew point.

9.  Separator element not properly installed.

Blow out system with dry air.

Check valve positions.

Check for correct connection.

Insulate or heat trace air lines exposed to low 

ambients or dry air to lower dew point.

Install separator ahead of dryer.

Replace drain mechanism if inoperative.

Open drain line.

Electric drains-reset time so that all liquid is 

discharged.

Check inlet air temperature and pressure, flow 

rate (compressor capacity) and ambient air or 

water temperature.

See D below.

Check element installation.

B)  High pressure drop across 

dryer

1.  Excessive air flow

2.  Freezing of moisture in evaporator because of 

refrigeration system improperly functioning.

3.  Inlet air strainer clogged.

4.  Separator filter element clogged

Check flow rate.

See D below.

Clean inlet air strainer.

Replace filter element.

C)  High Temperature Alarm

1.  Dryer overloaded resulting in high air outlet 

temperature.

2.  Refrigeration system not functioning properly 

resulting in high air outlet temperature.

3.  Unit functioning normally but temperature 

sensor is malfunctioning or not securely 

mounted.

See A7.

See D below.

Contact qualified refrigeration repairman or 

manufacturer’s service department.  Check power 

to unit.

D)  Refrigeration system not 

functioning properly

1.  Power on light off

2.  Compressor on light off

3.  Refrigeration compressor 

cycles on and off 

a.  Power failure

b.  Line disconnect switch open

c.  Blown fuses, open breaker

d.  Faulty wiring, loose terminals

a.  ON/OFF switch is “OFF”

b.  Line disconnect switch open

c.  Blown fuses, open breaker

d.  Faulty wiring, loose terminals

a.  High or low ambient conditions

b.  Air-cooled - Dirty, clogged condenser fins, 

obstructed flow across condenser, faulty fan 

motor or fan control switch.

Check for power to unit

Close disconnect switch

Check for continuity

Have electrician check electrical connections.

Turn switch “ON”

Close disconnect switch

Check for continuity

Have electrician check electrical connections

Check min./max. temperature ranges

Clean condenser and check for free air flow, if 

problem persists contact qualified refrigeration 

repairman or manufacturer’s service department.

TROUBLESHOOTING GUIDE

Содержание HPET Series

Страница 1: ...ION 3 2 0 OPERATION 5 3 0 MAINTENANCE 6 SIZING 7 ENGINEERING DATA 8 P I DIAGRAM 9 WIRING DIAGRAMS 10 12 DIMENSIONS WEIGHTS 13 TROUBLESHOOTING GUIDE 14 PARTS LIST 15 WARRANTY 16 INSTRUCTION MANUAL HPET...

Страница 2: ...plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you in sist tha...

Страница 3: ...110 F 4 to 43 C Water cooled 40 to 130 F 4 to 54 C E The installation of a flexible connection prior to the dryer is recommended to prevent possible damage from vibration NOTE Outdoor installation St...

Страница 4: ...requency listed on the serial number tag B Electrical entry on larger dryers is through a hole in the cabinet It is located on the right side panel when facing the front of the unit Connect power sour...

Страница 5: ...aximum ambient temperature Air cooled models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C Condensate Draining Drain Push to Test On Off Switch Switch Legend Power O...

Страница 6: ...Operating Check Points Check the following on a periodic basis A Green power on light is illuminated B Dew point indicator is in green area C Condensate is discharging from drain Condensate Draining...

Страница 7: ...nnually To facilitate service maintenance kits are available SIZING Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at vari ous operat...

Страница 8: ...oltage 207 253 Input Power Rated Flow watts 5 010 7 710 9 710 14 400 Minimum Circuit Ampacity 25 4 28 0 48 0 63 0 Maximum Overcurrent Protector amps 40 45 75 100 Compressor Rated Load Amps 8 2 9 3 15...

Страница 9: ...ER REHEATER AIR AIR HEAT EXCHANGER PRE COOLER REHEATER EVAPORATOR EVAPORATOR EVAPORATOR HEAT EXCHANGER SET 3 USED ON MODELS 7 5 10 HEAT EXCHANGER SET 2 HEAT EXCHANGER SET 1 HIGH TEMPERATURE SWITCH OPT...

Страница 10: ...30 31 32 33 34 35 36 37 38 39 40 41 42 43 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 3 PHASE 60 Hz TB1 L1 L2 L3 PE DISCONNECT L1 L2 L3 L1 L1 L1 L3 L2 T1 L2 L2 L3 L3 T1 T2 T2 T3...

Страница 11: ...1 LINE NEUTRAL THERMISTER THERMISTER DRAIN NEUTRAL DRAIN LINE COMPRESSOR N 3 CONTROL BOARD 4NO 3NO 5 CONT 1 X X TB2 3 TB2 DRAIN HARNESS BLUE BROWN GRN YELLOW DRAIN HARNESS 3 X TB2 PE PE 2 3 1 TEST ALM...

Страница 12: ...Transformer Pack TB1 L1 L2 L3 PE TB1 CONNECTION 460 3 60 460V 1 2 3 PE H4 H3 H2 H1 G X4 X3 X2 X1 H4 H3 H2 H1 G X4 X3 X2 X1 1 2 3 PE 575V L1 L2 L3 PE TRANSFORMER 1 CUSTOMER CONNECTION 575 3 60 575V VOL...

Страница 13: ...rposes FRONT VIEW RIGHT SIDE VIEW BOTTOM VIEW DETAIL A DETAIL B CONDENSER AIR FLOW A B 3 76 1 25 1 25 ELECTRICAL ENTRY 1 4 18 FPT DRAIN CONNECTION 3 4 14 NPT FEMALE I O WATER CONNECTIONS HPET 4 W C MO...

Страница 14: ...refrigeration system improperly functioning 3 Inlet air strainer clogged 4 Separator filter element clogged Check flow rate See D below Clean inlet air strainer Replace filter element C High Temperatu...

Страница 15: ...pansion Valve 3232550 3232550 3232550 3232532 De Superheating Valve 3232542 3232542 3232542 3232531 Liquid Line Filter Dryer 4006402 4006402 4006402 4006402 Suction Filter 4006414 4006414 Cooling Wate...

Страница 16: ...ARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A...

Отзывы: