c.  This setting may be field adjusted to increase or 

decrease the outlet dew point at tower switch-

over.

4.  When finished, press   to acknowledge the selec-

tion and move to next screen.

Screen 10: Set Points for High Humidity Alarm

 

(Displayed only when JP8 “on”)

HIGH HUMIDITY
XX%RH
XX MBAR  .XXX PSI
XX MIN  SW  DELAY

1.  Press 

  to  increment  the  setting  to  the  desired 

maximum RH value.

a.  Factory set point is 

75%RH

.  The factory setting 

should not require adjustment.

b.  The allowable range of values are 

20 TO 80%RH

 

in 5% increments. 

  Note:  

Value must be set above Energy Manage-

ment Maximum RH Value Set Point (screen 9).

2.  When finished, press   to acknowledge the selec-

tion and scroll to the pressure set point screen.

3.  Press 

  to  increment  the  setting  to  the  desired 

maximum vapor pressure value.
a.  Factory set point for a -40°F dew point dryer is 

24 MBAR (0.348 PSI)

.

 

Note:

  Factory set point for a -100°F dew point 

dryer is 

5 MBAR (0.073 PSI)

.

b.  The allowable range of values is 

3 to 34 MBAR (0.044 to 0.493 PSI)

 in 1 MBAR incre-

ments. 

  Note:  

Value must be set above Energy Man-

agement Maximum Vapor Pressure Set Point 

(screen 9).

4.  When  finished,  press 

  to  acknowledge  the  se-

lection and scroll to the switchover delay set point 

screen.

a.  Factory set point is 

60 MIN.

.

b.  The allowable range of values are 

30 to 120 MIN

 

in 10 minute increments.

5.  When finished, press   to acknowledge the selec-

tion and move to next screen. Exit Program Mode 

when there are no more active screens to display.

6.5.5  Setup Mode

1.  Press  and  hold 

  for  3  seconds  to  enter  Setup 

Mode.

2.  Setup Mode is comprised of the screens that are 

described below.

3.  There are two ways to exit Setup Mode.

a.  Press   after making the selection in Screen 1.

b.  The controller automatically exits Setup Mode if 

no button is pressed with 60 seconds.

4.  One of two things will happen upon exiting Setup 

Mode.

a.  The  controller  will  switch  to  Display  Mode  if 

ENERGY  MANAGEMNT,  FIXED  CYCLE  or 

DEWPOINT CONTROL is selected.

b.  The controller will switch to Test Mode if TEST 

CYCLE is selected.

Screen 1:  Select the Cycle Type

CYCLE TYPE
ENERGY MANAGEMNT

1.  Press   to scroll through the choices:

a.  ENERGY  MANAGEMNT  (displayed  only  when 

JP2 is in the ON position)

b.  DEWPOINT CONTROL (displayed only when JP3 

is in the ON position)

c.  FIXED CYCLE

d.  MANUAL CYCLE 

2.  When finished, press   to save the selection and 

exit the Setup Mode.

Содержание HBP Series

Страница 1: ...36 Electrical Schematic 460VAC 3 phase 38 Electrical Schematic 575VAC 3 phase 39 Electrical Schematic 380VAC 3 phase 40 Electrical Schematic 415VAC 3 phase 41 Electrical Data Fusing Wire Sizing 42 WAR...

Страница 2: ...R WARNING and CAUTION are used to indicate hazard seriousness levels as follows DANGER Immediate hazard which will result in severe injury or death WARNING Hazard or unsafe practice which could result...

Страница 3: ...ryer in order to protect the desiccant bed from liquid and solid contamination Use an Air Line Filter in systems sup plied by a non lubricated oil free air compressor In systems supplied by a lubricat...

Страница 4: ...lectrical enclosure for a remote alarm The contact ratings are shown on the electrical drawing Compressor Aftercooler Separator Receiver Prefilters Afterfilters Receiver Desiccant Dryer Figure 1 Typic...

Страница 5: ...ty and purpose of the desic cant Layer 1 must be installed rst at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed 4 Utilizing an appro...

Страница 6: ...E MAX F G C D B A MAX H K N MAX P L S GAS INLET M FACE OF CUSTOMER WET GAS INLET CONNECTION FACE OF CUSTOMER DRY GAS OUTLET CONNECTION R SLOT TYP 4 PLACES TOP VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR...

Страница 7: ...NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6...

Страница 8: ...ge mounted on the gauge panel of the dryer indicates purge air pressure 5 4 Energy Management System The optional Energy Management System EMS automatically adjusts dryer operation to compensate for c...

Страница 9: ...DRAIN PORT TOWER INSULATION OPTIONAL CONTROL ENCLOSURE HIGH TENSION ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REPRESS VALVE HEATER TEMP THERMOCOUPLE CENTER END IN PIPE OPPOSITE SIDE H...

Страница 10: ...ER DEPRESS VALVE ASME RELIEF VALVE REPRESS VALVE TOP VIEW FRONT VIEW PURGE HEATER WITH INSULATION PURGE SUCTION FILTER SILENCER PURGE BLOWER AND MOTOR REAR VIEW LEFT TOWER INLET VALVE ASME CODE TAG LE...

Страница 11: ...DEPRESS VALVE DESICCANT DRAIN PORT TOWER INSULATION OPTIONAL HIGH TENSION ENCLOSURE CONTROL ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REPRESS VALVE PURGE BLOWER AND MOTOR PURGE BLOWER...

Страница 12: ...slowly depressurized Air exits through exhaust muf er M2 After the right tower has depressurized the Right Purge Valve V4 is opened and the Blower M and Heater H1 are energized The heated air ows thro...

Страница 13: ...LEFT TOWER SET 45 PSIG M RTD 3 SET 650 F 1TC SET 370 F V5 2PS SET 176 F 4PS SET 5 PSIG REGEN SET 45 PSIG SET AT 100 PSIG RIGHT TOWER V8 V12 V13 SOL E V7 V11 RV1 SET 165 PSIG DEWPOINTER OPTION DPA SOLE...

Страница 14: ...d because the repressurization step will occur before the bed temperature can fall to 150 F Note In Energy Management or Dew Point Control as the drying time extends beyond 4 hours additional cooling...

Страница 15: ...is installed in the OFF position if Switching Failure is disabled 6 JP6 Not Used NOTE Jumpers JP7 and JP8 are used by the factory during nal inspection to download language text and to enable factory...

Страница 16: ...for the Heated Desiccant Dryer Control a Program Mode b Setup Mode c Alarm Service Mode d Display Mode e Test Mode 2 Each Mode is described below 6 5 4 Program Mode 1 Press and hold and for 3 seconds...

Страница 17: ...Point Demand Control Displayed only when JP3 on DPNT CNTL SETPT XX C XXX F 1 Press to increment the setting to the desired value a Standard set point is 30 C 22 F b The allowable range of values is fr...

Страница 18: ...m Vapor Pressure Set Point screen 9 4 When nished press to acknowledge the se lection and scroll to the switchover delay set point screen a Factory set point is 60 MIN b The allowable range of values...

Страница 19: ...ing the drying cycle b Left or Right tower regenerating high pressure i Regenerating tower pressure switch is closed while purge valve is open after an initial time delay c Left or Right tower regener...

Страница 20: ...UNDER RANGE ALARM RIGHT TWR DEW POINT OVER RANGE ALARM LEFT TOWER TEMP UNDER RANGE ALARM LEFT TOWER TEMP OVER RANGE ALARM RIGHT TWR TEMP OVER RANGE ALARM RIGHT TWR TEMP UNDER RANGE ALARM RIGHT TWR DR...

Страница 21: ...rogram Mode b Humidity Sensor i Under range RH 15 ii Over range RH 115 c RTD i Over range Temperature above 448 F 231 C ii Under range Temperature below 20 F 28 C d On alarm condition i Local alarm is...

Страница 22: ...upplied to the controller whether the controller is switched on or off When a service time interval expires see also 14 d below the controller operates as follows a The service LED blinks and the appr...

Страница 23: ...e reminder lters HOURS TO SERVICE FILTERS XXXX Service reminder desiccant HOURS TO SERVICE DESICCANT XXXX Service reminder valves HOURS TO SERVICE VALVES XXXX Outlet Dew Point Displayed only if JP3 is...

Страница 24: ...ying Drying Drying Drying 1PS Closed Closed Closed Closed Closed Closed Closed then Open Open Open Open then Closed 2PS Closed Closed then Open Open Open Open then Closed Closed Closed Closed Closed C...

Страница 25: ...pressurized Exception If switching failure is disabled then pressure condition is ignored Screen 6 Step 6 TEST6 RT DRYING RT XX C XXX F Screen 7 Step 7 TEST7 DEPR LT LT XX C XXX F Note Sequence step...

Страница 26: ...d 600 Inlet switching valves are normally open pneumatically piston actuated Y angle poppet valves Ayellow indicator can be seen through a clear window at the top of the ac tuator housing when the val...

Страница 27: ...ization valve closes 6 9 1 2 On restoration of power 1 If power is lost when the off line tower is in either the HEAT or COOL step the off line tower will be either partially or fully repressurized On...

Страница 28: ...ASCII representation of the energy savings x Reserved for future use always 1 for now ETX end of text character OxO3 CR carriage return LF line feed JUMPERS The programming jumpers are as follows 0 o...

Страница 29: ...Layer 1 must be installed rst at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed e Utilizing an appropriate sized funnel ll each desi...

Страница 30: ...Replacement may be required sooner if pressure drop across cartridge prevents the Dew Point Analyzer from operating properly Warning The Dew Point Analyzer lter housing is a pressure containing device...

Страница 31: ...k Valve leak ing 1 Check compressor supplying dryer 2 Check equipment downstream of dryer 3 Check pressure switch operation using tower pressure gauge for comparison Replace switch if defective 4a Che...

Страница 32: ...3 Regenerating tower Depressurization Valve failed to close 4 Repressurization valve V11 failed to open 5 Repressurization ori ces are blocked 1 Check pressure switch operation using tower pressure ga...

Страница 33: ...ins Repair or replace as necessary Useful life of desiccant has been exceeded Heater Over Temperature Alarm 1 Insuf cient purge gas ow 2 Temperature sensor failure 1 Check for purge blockage temperatu...

Страница 34: ...SOL C 2 1 3 LEFT TOWER SET 45 PSIG M RTD 3 SET 650 F 1TC SET 370 F V5 2PS SET 176 F 4PS SET 5 PSIG 18 REGEN 9 SET 45 PSIG SET AT 100 PSIG RIGHT TOWER 12 11 8 7 V8 26 V12 V13 SOL E V7 V11 SET 165 PSIG...

Страница 35: ...43 ENERGY MANAGEMENT SENSOR RTD4 HS1 DEWPOINTER OPTION 44 DEWPOINT ANALYZER 44A DEWPOINT ANALYZER FILTER INSULATION OPTION 54 CHAMBER INSULATION LEFT CHAMBER DRYING RIGHT CHAMBER REGEN CLOSED NO 3 WA...

Страница 36: ...TD 3 SET 650 F 1TC SET 370 F V5 V6 2PS REGEN SET 176 F 4PS SET 5 PSIG 18 9 RIGHT TOWER SET 45 PSIG SET AT 100 PSIG 12 11 8 7 26 V12 V13 SOL E V11 V7 V8 SET 165 PSIG DEWPOINTER OPTION DPA 15 3 22 14 13...

Страница 37: ...AGEMENT SENSOR RTD4 HS1 DEWPOINTER OPTION 44 DEWPOINT ANALYZER 44A DEWPOINT ANALYZER FILTER INSULATION OPTION 54 CHAMBER INSULATION FAILS IN POSITION LEFT CHAMBER DRYING RIGHT CHAMBER REGEN CLOSED NO...

Страница 38: ...ENERGY MGMT OPTION RTD4 1HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89 32 3...

Страница 39: ...2HC2 2HC3 507 508 509 4 20MA OUT ENERGY MGMT OPTION RTD4 2HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101...

Страница 40: ...ON RTD4 1HTR 102 101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89...

Страница 41: ...101 102 102 102 1CR 102 101 101 101 109 111 101 107 SOLENOID C 21 LEFT CHAMBER DEPRESS LEFT CHAMBER PURGE EXHAUST HEAT ENABLE C NO 101 102 20 21 80 81 70 72 21 10 11 84 85 86 87 88 89 32 33 34 35 50...

Страница 42: ...AWG 4300 HEATER 2 35 KW 2 35 1 2 40 AMPS 2 8 AWG MOTOR 7 5 HP 9 15 AMPS 12 AWG Models 3200 3600 and 4300 use a two stage heater circuit with two contactors six fuses and six wires Electrical Service...

Страница 43: ...43...

Страница 44: ...arranty and any resulting charge or subsequent claim will not be paid THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WRITTEN ORAL OR STATUTORY AND IS EXPRESSED IN LIEU OF THE...

Отзывы: