COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
19
Please refer to the below tables for recommended minimum space requirements
RC2-100
RC2-140
RC2-180
RC2-170
RC2-200
RC2-230
RC2-260
RC2-300
A.(cm)
5.9” (15)
16.1” (41)
18.1” (46)
18.5” (47)
20.1” (51)
B.Outwards(cm)
11” (28)
C.(cm)
9.8” (25)
10.2 (26)
11.8” (30)
13” (33)
D.(cm)
5.9” (15)
E.Suction filter
(mm)
3.7” (95)
4” (103)
5.6” (143)
F.Oil filter
(mm)
7.8” (200)
RC2-310
RC2-320
RC2-340
RC2-370
RC2-410
RC2-470
RC2-510
RC2-550
A.(cm)
20” (51)
22” (56)
21.3” (54)
23.3” (59)
21.7” (55)
23.3” (59)
B.Outwards(cm)
11” (28)
C.(cm)
13” (33)
11.8” (30)
13.8” (35)
14.6” (37)
D.(cm)
5.9” (15)
E.Suction filter
(mm)
5.6” (143
6” (153)
F.Oil filter
(mm)
7.8” (200)
RC2-580
RC2-610
RC2-620
RC2-710
RC2-790
RC2-830
RC2-930
A.(cm)
21.7” (55)
23.6” (60)
23.6” (60)
25.6” (65)
31.5” (80)
B.Outwards(cm)
11” (28)
13.8” (35)
11” (28)
13.8” (35)
C.(cm)
13.8” (35)
14.6” (37)
17.7” (45)
D.(cm)
5.9” (15)
---
5.9” (15)
---
E.Suction filter
(mm)
6” (153)
8.2” (210)
6” (153)
8.2” (210)
F.Oil filter
(mm)
7.8” (200)
9.1” (232)
7.8” (200)
9.1” (232)
Table 7-A Compressor Recommended Space for Maintenance
1.
Reserve enough space for connection and installation of the electrical terminal box, service/stop valves and sole
-
noid valves on the compressor.
2. Consider the compressors’ future overhaul when determining space requirements. All compressors’ outside parts
and electrical controller lines and terminal connections etc should be spaced for easy dismantle and re-assemble.
Chapter - 11. Maintenance Area Requirement
Содержание RC2 Series
Страница 8: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 8 Chapter 5 Wiring Procedures Y Delta Part Winding...
Страница 10: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 10 Figure 5 A Motor Wiring...
Страница 16: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 16 Chapter 8 RC2 100 140 Installation Guide...
Страница 17: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 17 Chapter 9 RC2 170 580 Installation Guide...
Страница 18: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 18 Chapter 10 RC2 710 930 Installation Guide...