COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
24
7.4. HANBELL FLOODED TYPE WITH OIL SEPARATOR & OIL COOLER
To obtain high oil filtering efficiency low pressure drop loss and non-interruption with lubricant supply system, the oil separator is
built outside the compressor. The installation of lubricant circuit is a very important issue during the whole procedures. So,
before starting, please make sure to read all the instructions of this manual carefully and ensure each step is done in
accordance with the specifications.
1.External oil separator
7. Oil level switch
2. Oil cooler
8. Oil temperature sensor
3. Oil filter and cartridge
9. Oil heater
4. Lubricant flow switch
10. Manually adjustable flow valve
5. Oil solenoid valve
11. Compressor
6. Sight glass
In the lubricant circuit, installing the oil solenoid valve in the proper place is very important. As the compressor is shut down,
lubricant will automatically inject into the compressor due to pressure differential. It will easily make the system difficult to
restart because of low oil level or lubricant injection inside the compressor chamber.
Содержание RC2 Series
Страница 8: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 8 Chapter 5 Wiring Procedures Y Delta Part Winding...
Страница 10: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 10 Figure 5 A Motor Wiring...
Страница 16: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 16 Chapter 8 RC2 100 140 Installation Guide...
Страница 17: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 17 Chapter 9 RC2 170 580 Installation Guide...
Страница 18: ...COMPRESSOR INSTALLATION START UP GUIDE REVISION M 18 Chapter 10 RC2 710 930 Installation Guide...