LT-S-L Technical manual
Figure 5-2 Suction Piping for Parallel System
Detail Drawing 2
4)
Suction filter
This model of compressor has a built-in suction filter, but it is only used as a
final protection. It should not be used as an suction filter that needs to be cleaned
regularly.
So It is necessary to install a suction filter (25μm) which is easy to remove and
clean it regularly.
When the system is first used, it may need to be cleaned up frequently.
If the
pressure drop is bigger than 0.5 bar, the filter element should be replaced or cleaned
until the system is clean.
When the filter is disassembled, if the filter is found to be
damaged, it needs to be replaced in time, and the impurities in the pipeline should be
cleaned up.
Ensure that the filter is oriented correctly during installation and it is
recommended to add a shut-off valve at the inlet and outlet for easy
maintenance.Hanbell
The recommended suction filter design is shown in Figure 5-3
below.
Figure 5-3.suction filter
x x x
Detail Drawing 2