LT-S-(L) Technical manual
Keep load state
Figure 3-11. Keep Load State
During this process, all S/V are not energized. The high pressure oil coming
continues to go to the left side of the piston. The left side oil inlet of the piston
SV1(unload) and SV5(100%) are closed to keep the oil amount in the right side of the
piston. The piston will not be able to move and stay at its original position, so that the