- 18 -
8. Trouble Inspection, and Remedial Measures
[Caution] When inspecting or carrying out remedial measures in the device, turn off the
power.
8.1 Explanation on LED DISPLAY function ( HN3204 )
[Table8-1]
LED NO.
Name
Explanation on Function
Inspection and Remedial Measures
LD1
DRIVE READY
Normal Status of MOTOR and
DRIVE. Preparation for Operation
Light on when normal
LD2
MOTOR TURN
MOTOR Rotation
Light on when motor rotates
LD3
RSP LOCK
DRIVE stop and hold
Light off when drive operates
LD4
PHASE LOSS
Phase loss of 3 phase power supply
Inspection of power supply
circuit and fuses 1, 2, and 3.
LD5
UNDER VOLT
Reduction of rated voltage by less
than15%.
Verify power supply voltage
LD6
+/- VCC
Abnormality in drive power circuit.
Voltage check +15,-15 [V]
±
13
≤
±
VCC
≤
±
17[V] SCOPE
LD7
HEAT SINK
Overheating of drive
’
s heatsink
Check heatsink cooling fan
LD8
MOTOR TH
MOTOR overheating
Check motor cooling fan and filter
LD9
FIELD LOSS
When rated field current is not
introduced
Check field circuit and fuse 4.
LD10
FIELD O.C
Motor field overcurrent
Check field circuit
LD11
OVER CURRENT Temporary exceeding of DRIVE
rated current by 2.5 times.
Check load status and external
speed setting
LD12
LOAD LIMIT
Exceeding I limit set load current
Check load status and I limit setting
LD13
CUT T.G
Damage to MOTOR
’
s T.G.
Check motor T.G and wiring.
* See Figure [8-1]
☞
When conducting inspection or remedial measure, refer to a person in charge of drive at
Hana Control Engineering.
☞
Home Page :
http://www.hanaeng.co.kr
☞
E-mail :
☞
Address : (Postal Code : 153-775) room1207, 8th, Daeryung-Technotown, 481-11,
Gasan-Dong, Geumcheon-Gu, Seoul, Korea
☞
Telephone Number : 02-2163-6720
☞
Facsimile Number : 02-2163-6725