- 18 -

 

 

8. Trouble Inspection, and Remedial Measures 

[Caution] When inspecting or carrying out remedial measures in the device, turn off the 

 power.  

8.1 Explanation on LED DISPLAY function ( HN3204 ) 

[Table8-1]

 

LED NO. 

      Name 

Explanation on Function 

Inspection and Remedial Measures 

LD1 

DRIVE READY 

Normal Status of MOTOR and 

DRIVE. Preparation for Operation 

Light on when normal 

LD2 

MOTOR TURN 

MOTOR    Rotation 

Light on when motor rotates 

LD3 

RSP LOCK 

DRIVE stop and hold 

Light off when drive operates 

LD4 

PHASE    LOSS 

Phase loss of 3 phase power supply

Inspection of power supply   

circuit and fuses 1, 2, and 3.   

LD5 

UNDER VOLT 

Reduction of rated voltage by less 

than15%.  

Verify power supply voltage 

LD6 

+/- VCC 

Abnormality in drive power circuit.   

Voltage check +15,-15 [V]   

±

13 

 

±

VCC 

 

±

17[V] SCOPE 

LD7 

HEAT SINK 

Overheating of drive

s heatsink 

Check heatsink cooling fan 

LD8 

MOTOR TH 

MOTOR overheating 

Check motor cooling fan and filter 

LD9 

FIELD LOSS 

When rated field current is not 

introduced 

Check field circuit and fuse 4.   

LD10 

FIELD O.C 

Motor field overcurrent 

Check field circuit 

LD11 

OVER CURRENT  Temporary exceeding of DRIVE 

rated current by 2.5 times. 

Check load status and external 

speed setting   

LD12 

LOAD LIMIT 

Exceeding I limit set load current 

Check load status and I limit setting

LD13 

CUT T.G 

Damage to MOTOR

s T.G.   

Check motor T.G and wiring. 

*  See Figure [8-1] 

  When conducting inspection or remedial measure, refer to a person in charge of drive at 

   Hana Control Engineering. 

  Home Page : 

http://www.hanaeng.co.kr

 

 E-mail : 

[email protected]

 

  Address : (Postal Code : 153-775) room1207, 8th, Daeryung-Technotown, 481-11, 

                                      Gasan-Dong, Geumcheon-Gu, Seoul, Korea   

  Telephone Number : 02-2163-6720 

  Facsimile Number : 02-2163-6725 

Содержание HN 3200 SERIES

Страница 1: ...User s Manual DC MOTOR SPEED CONTROLLER 3 PHASE 2 QUADRANT type HN 3200 SERIES Ver 3 0 HANA CONTROL ENGINEERING CO LTD HANA POWER ELECTRONICS CO LTD...

Страница 2: ...2 Standard Specification of Device 5 3 Installation 6 4 Dimension of Device 7 5 Wiring Diagram of Device 8 6 Explanation of Drive Configuration 10 7 Explanation on the Digital Display Function 17 8 Tr...

Страница 3: ...rque characteristic diagram The unit is made of one body type with the field control builted in 2 Soft start and stop and highly sensitive response characteristics are ensured by adopting soft start a...

Страница 4: ...oltage and phase loss 10 Detection of damage and cut of wire in motor tacho generator T G 6 This device has applied input output terminal that allows compatible configuration with winding control unit...

Страница 5: ...F 30 92 110 ST32S 6 30 160 192 ST32S F 37 113 142 ST32S F 7 37 195 236 ST32M F 45 130 156 ST32S F 8 45 230 276 ST32M F 55 160 195 ST32S F 9 55 285 350 ST32M F 75 221 265 ST32M F 10 75 383 460 ST32M F...

Страница 6: ...xternal input terminal for clearing fault DC 24 V Speed setting voltage and current Voltage of 0 10 V 0 5 V and 0 16 mA 0 20 mA 4 20 mA current Controlling torque Able to control within rated current...

Страница 7: ...4 Dimension of Device Figure 4 1 Dimension can be changed to improve the product 7...

Страница 8: ...t be the same as HN3201 board field voltage selectiontab even though it is used for both AC 220 and 380 V FSL1 AC 220 V FSL2 AC 380 V note 3 Load current and speedometer output are for digital meters...

Страница 9: ...contact terminal for motor and drive NO NC 9 10 11 M TURN Relay contact terminal for motor rotation detection NO NC 20 24V Power supply for control signal for 24 V 21 GND O V GND terminal 22 RESET Ex...

Страница 10: ...2 Confirm whether wiring is done as shown in the wiring diagram Also verify that the conditions of terminal connection and the linkage of connecting parts are good 3 Confirm that the phases of main p...

Страница 11: ...ct protection and cooperation on abnormality of motor tacho generator FIELD LOSS When motor has separately excited field select this shunt and compound motor Select when motor hasnot separately excite...

Страница 12: ...eld loss VR60 N OUT Setting output voltage 0 10 V for speed meter No 35 VR93 LOAD OUT Setting output voltage 0 10 V for load meter No 34 VR90 JOG Setting rotational speed of JOG operation VR91 EX SP S...

Страница 13: ...hall be dependent on the minimum value of constant output operation condition 6 5 2 Setting for Maximum and Minimum Rotational Speed Nmax and Nmin due to Tacho Generator T G feedback Verify that the p...

Страница 14: ...10 V and adjust trimmer Nmax VR1 to set it to the maximum rated speed of the motor When using a digital display meter HN230 embedded in the drive to adjust choose selector switch No 6 SW1 and adjust t...

Страница 15: ...ctor switch No 9 SW1 while ENB terminal TB1 No 24 and RUN terminal TB1 No 23 are open and adjust trimmer I limit VR9 to make the limit of load rated current to be displayed on the display meter I limi...

Страница 16: ...to the middle position Set the values as follows with reference to the rotational speed of motor No 4 of selector switch SW1 of the digital display meter HN23 and the armature voltage of motor No 6 S...

Страница 17: ...e power supply circuit voltage 3 0 10 0 V DRIVE external speed command setting value 4 0 1999 RPM Motor rotational speed T G 5 0 1999 A Motor actual load current 6 0 600 V Motor armature voltage 7 0 9...

Страница 18: ...5 V 13 VCC 17 V SCOPE LD7 HEAT SINK Overheating of drive s heatsink Check heatsink cooling fan LD8 MOTOR TH MOTOR overheating Check motor cooling fan and filter LD9 FIELD LOSS When rated field current...

Отзывы: