motor tacho generator (T.G) 

 

  Speed (VR24) is set to be compatible with tacho generator (T.G) at   

DC30[V]/1000[RPM].      

  When the rotation of the motor is unstable during the setting of the maximum rotational 

  speed, adjust Ngain (VR5) to stabilize the speed and set Nmax (VR1). 

 

[caution] In setting the maximum speed, the drive output voltage (A+, B-) must not 

exceed the armature rated voltage of DC motor. 

 

6.5.3 Setting for the maximum and minimum rotational speed (Nmax and Nmin) due to 

the armature voltage feedback (EM-1), Caliberation of Speed according to Load 

-. This applies when there is no motor tacho generator (T.G).    Set selector switch 

 DIPSW1 to EM-1.  

-. Turn on the motor operation signal RUN terminal ( TB1 No. 23).       

-. Set the value for external speed command to the minimum value (0[V]), and adjust 

trimmer Nmin (VR4) to set to the minimum rotational speed.   

-. Slowly increase the external speed command value to set to the maximum 

value(+10 [V]), and adjust trimmer Nmax (VR1) to set it to the maximum rated 

speed of the motor.   

- When using a digital display meter (HN230) embedded in the drive to adjust, choose 

  selector switch No. 6 (SW1) and adjust trimmer Nmax (VR1) to make the display   

meter value to reach the armature rate voltage value of the motor.     

- Trimmer IxR (VR7) is only used in the armature voltage feedback control (EM-1).     

If the rotational speed of motor changed according to the load, adjust trimmer IxR 

  (VR7) to caliberate the speed change. 

 

6.5.4 Setting the Maximum Operational Current Value (Imax) 

-. The setting for the maximum operational current of drive is determined by the 

  actual load current, and is set by trimmer Imax (VR6). 

(Clockwise: Increase the set current,    Counterclockwise: Decrease the set current) 

-. When readjusting the maximum operational current, turn off selector switch S2-2   

while ENB terminal (TB1 No.24) and RUN terminal (TB1 23) are open, and set the   

external speed setting to +5[V]. 

Choose selector switch No. 8 (SW1) of the digital display meter (HN230) embedded 

  in the drive, and adjust trimmer Imax (VR6) to make the maximum operational 

 

 

- 14 -

 

 

Содержание HN 3200 SERIES

Страница 1: ...User s Manual DC MOTOR SPEED CONTROLLER 3 PHASE 2 QUADRANT type HN 3200 SERIES Ver 3 0 HANA CONTROL ENGINEERING CO LTD HANA POWER ELECTRONICS CO LTD...

Страница 2: ...2 Standard Specification of Device 5 3 Installation 6 4 Dimension of Device 7 5 Wiring Diagram of Device 8 6 Explanation of Drive Configuration 10 7 Explanation on the Digital Display Function 17 8 Tr...

Страница 3: ...rque characteristic diagram The unit is made of one body type with the field control builted in 2 Soft start and stop and highly sensitive response characteristics are ensured by adopting soft start a...

Страница 4: ...oltage and phase loss 10 Detection of damage and cut of wire in motor tacho generator T G 6 This device has applied input output terminal that allows compatible configuration with winding control unit...

Страница 5: ...F 30 92 110 ST32S 6 30 160 192 ST32S F 37 113 142 ST32S F 7 37 195 236 ST32M F 45 130 156 ST32S F 8 45 230 276 ST32M F 55 160 195 ST32S F 9 55 285 350 ST32M F 75 221 265 ST32M F 10 75 383 460 ST32M F...

Страница 6: ...xternal input terminal for clearing fault DC 24 V Speed setting voltage and current Voltage of 0 10 V 0 5 V and 0 16 mA 0 20 mA 4 20 mA current Controlling torque Able to control within rated current...

Страница 7: ...4 Dimension of Device Figure 4 1 Dimension can be changed to improve the product 7...

Страница 8: ...t be the same as HN3201 board field voltage selectiontab even though it is used for both AC 220 and 380 V FSL1 AC 220 V FSL2 AC 380 V note 3 Load current and speedometer output are for digital meters...

Страница 9: ...contact terminal for motor and drive NO NC 9 10 11 M TURN Relay contact terminal for motor rotation detection NO NC 20 24V Power supply for control signal for 24 V 21 GND O V GND terminal 22 RESET Ex...

Страница 10: ...2 Confirm whether wiring is done as shown in the wiring diagram Also verify that the conditions of terminal connection and the linkage of connecting parts are good 3 Confirm that the phases of main p...

Страница 11: ...ct protection and cooperation on abnormality of motor tacho generator FIELD LOSS When motor has separately excited field select this shunt and compound motor Select when motor hasnot separately excite...

Страница 12: ...eld loss VR60 N OUT Setting output voltage 0 10 V for speed meter No 35 VR93 LOAD OUT Setting output voltage 0 10 V for load meter No 34 VR90 JOG Setting rotational speed of JOG operation VR91 EX SP S...

Страница 13: ...hall be dependent on the minimum value of constant output operation condition 6 5 2 Setting for Maximum and Minimum Rotational Speed Nmax and Nmin due to Tacho Generator T G feedback Verify that the p...

Страница 14: ...10 V and adjust trimmer Nmax VR1 to set it to the maximum rated speed of the motor When using a digital display meter HN230 embedded in the drive to adjust choose selector switch No 6 SW1 and adjust t...

Страница 15: ...ctor switch No 9 SW1 while ENB terminal TB1 No 24 and RUN terminal TB1 No 23 are open and adjust trimmer I limit VR9 to make the limit of load rated current to be displayed on the display meter I limi...

Страница 16: ...to the middle position Set the values as follows with reference to the rotational speed of motor No 4 of selector switch SW1 of the digital display meter HN23 and the armature voltage of motor No 6 S...

Страница 17: ...e power supply circuit voltage 3 0 10 0 V DRIVE external speed command setting value 4 0 1999 RPM Motor rotational speed T G 5 0 1999 A Motor actual load current 6 0 600 V Motor armature voltage 7 0 9...

Страница 18: ...5 V 13 VCC 17 V SCOPE LD7 HEAT SINK Overheating of drive s heatsink Check heatsink cooling fan LD8 MOTOR TH MOTOR overheating Check motor cooling fan and filter LD9 FIELD LOSS When rated field current...

Отзывы: