HANA CONTROL ENGINEERING HN 3200 SERIES Скачать руководство пользователя страница 15

  current value to be displayed on the display meter. 

When the setting of Imax is completed, turn on selector switch S2-2.   

The rated current of the device must be bigger than the actual motor load current.   

  Imax (VR6) is set to the rated current of device (I dn) at production. 

[Caution] When turning selector switch S2-2 on or off, turn off the device beforehand.   

     

6.5.5 Limit of Load Rate Current (I limit) and Setting Delay Time (I time)   

The trimmer I limit (VR9) for setting limit current of motor is determined in reliance on   

the rated current of the motor.    When trimmer is fully turned in clockwise, it is set to the   

value of 120% of the rated current of the device. 

Trimmer I time (VR8) for setting the delay time for motor limit current can be set within 

the range of 0 ~ 60 seconds.    (When it is fully turned in clockwise, the delay time is set 

  to 60 seconds.) 

When more current than I limit (VR9) setting value flows for more than the time set on   

I time (VR8), the relay (RY3) starts to operate. 

- When readjusting the limit value of load rated current (I limit - VR9), choose selector 

  switch No. 9 (SW1) while ENB terminal (TB1 No. 24) and RUN terminal (TB1 No. 23) 

  are open and adjust trimmer I limit (VR9) to make the limit of load rated current to be 

  displayed on the display meter.     

  I limit is set to the rated current of the device (I dn) and I time is set to 10 seconds.   

 

6.5.6 Setting Acceleration and Deceleration Gradient 

When not choosing acceleration and deceleration gradient, set selector switch S1-2 to 

DR, and When using acceleration and deceleration gradient, set selector switch S1-2 to 

AD to adjust the acceleration and deceleration gradient from 0.6 [SEC] to 60 [SEC].   

(Accel (VR2): Acceleration Gradient,    Decel (VR3): Deceleration Gradient) 

To increase the acceleration and deceleration time, turn each switch clockwise. 

 

6.5.7 Setting Speed Loop Gain (Ngain) 

When the motor rotational speed is unstable, adjust the settings as follows. 

First, set selector switch S1-2 to DR.    Fix the external speed command value to 5 [V] 

  under device operation mode and observe the speed feedback value of test point TP7 

  while turning the command value on and off.     

Set trimmer Ngain (VR5) to a value that enables the motor to reach the preset value at the 

  shortest time without delay.    When the adjustment is completed, restore selector switch 

 S1-2 to  AD position.  

 

 

- 15 -

 

 

Содержание HN 3200 SERIES

Страница 1: ...User s Manual DC MOTOR SPEED CONTROLLER 3 PHASE 2 QUADRANT type HN 3200 SERIES Ver 3 0 HANA CONTROL ENGINEERING CO LTD HANA POWER ELECTRONICS CO LTD...

Страница 2: ...2 Standard Specification of Device 5 3 Installation 6 4 Dimension of Device 7 5 Wiring Diagram of Device 8 6 Explanation of Drive Configuration 10 7 Explanation on the Digital Display Function 17 8 Tr...

Страница 3: ...rque characteristic diagram The unit is made of one body type with the field control builted in 2 Soft start and stop and highly sensitive response characteristics are ensured by adopting soft start a...

Страница 4: ...oltage and phase loss 10 Detection of damage and cut of wire in motor tacho generator T G 6 This device has applied input output terminal that allows compatible configuration with winding control unit...

Страница 5: ...F 30 92 110 ST32S 6 30 160 192 ST32S F 37 113 142 ST32S F 7 37 195 236 ST32M F 45 130 156 ST32S F 8 45 230 276 ST32M F 55 160 195 ST32S F 9 55 285 350 ST32M F 75 221 265 ST32M F 10 75 383 460 ST32M F...

Страница 6: ...xternal input terminal for clearing fault DC 24 V Speed setting voltage and current Voltage of 0 10 V 0 5 V and 0 16 mA 0 20 mA 4 20 mA current Controlling torque Able to control within rated current...

Страница 7: ...4 Dimension of Device Figure 4 1 Dimension can be changed to improve the product 7...

Страница 8: ...t be the same as HN3201 board field voltage selectiontab even though it is used for both AC 220 and 380 V FSL1 AC 220 V FSL2 AC 380 V note 3 Load current and speedometer output are for digital meters...

Страница 9: ...contact terminal for motor and drive NO NC 9 10 11 M TURN Relay contact terminal for motor rotation detection NO NC 20 24V Power supply for control signal for 24 V 21 GND O V GND terminal 22 RESET Ex...

Страница 10: ...2 Confirm whether wiring is done as shown in the wiring diagram Also verify that the conditions of terminal connection and the linkage of connecting parts are good 3 Confirm that the phases of main p...

Страница 11: ...ct protection and cooperation on abnormality of motor tacho generator FIELD LOSS When motor has separately excited field select this shunt and compound motor Select when motor hasnot separately excite...

Страница 12: ...eld loss VR60 N OUT Setting output voltage 0 10 V for speed meter No 35 VR93 LOAD OUT Setting output voltage 0 10 V for load meter No 34 VR90 JOG Setting rotational speed of JOG operation VR91 EX SP S...

Страница 13: ...hall be dependent on the minimum value of constant output operation condition 6 5 2 Setting for Maximum and Minimum Rotational Speed Nmax and Nmin due to Tacho Generator T G feedback Verify that the p...

Страница 14: ...10 V and adjust trimmer Nmax VR1 to set it to the maximum rated speed of the motor When using a digital display meter HN230 embedded in the drive to adjust choose selector switch No 6 SW1 and adjust t...

Страница 15: ...ctor switch No 9 SW1 while ENB terminal TB1 No 24 and RUN terminal TB1 No 23 are open and adjust trimmer I limit VR9 to make the limit of load rated current to be displayed on the display meter I limi...

Страница 16: ...to the middle position Set the values as follows with reference to the rotational speed of motor No 4 of selector switch SW1 of the digital display meter HN23 and the armature voltage of motor No 6 S...

Страница 17: ...e power supply circuit voltage 3 0 10 0 V DRIVE external speed command setting value 4 0 1999 RPM Motor rotational speed T G 5 0 1999 A Motor actual load current 6 0 600 V Motor armature voltage 7 0 9...

Страница 18: ...5 V 13 VCC 17 V SCOPE LD7 HEAT SINK Overheating of drive s heatsink Check heatsink cooling fan LD8 MOTOR TH MOTOR overheating Check motor cooling fan and filter LD9 FIELD LOSS When rated field current...

Отзывы: