HAMWORTHY HEATING LTD
49
FLEET W series
500001211/F
APPENDIX A - GAS DATA
F85W
F100W
F125W
F150W
Gas Inlet Connection Pipe Thread Size
R ¾”
R ¾”
R 1”
R 1”
Nominal Inlet Pressure Nat Gas
-mbar
20
Maximum Inlet Pressure Nat Gas
-mbar
25
Gas Pressure Switch Setting Nat Gas
-mbar
Gas Flow Rate (max. per module) Nat Gas -m
3
/h
8.25
9.7
11.7
14.6
Target CO
2
% at High / Low fire Nat Gas ±0.25%
9.0
12.5
GENERAL DATA
BOILER MODEL
F40W
F50W
F60W
F70W
Boiler Input (maximum)
- kW (Gross)
41.0
51.3
61.5
71.8
Boiler Input (maximum)
- kW (Nett)
36.9
46.2
55.4
64.7
Boiler Output kW (maximum) condensing 50/30°C
- kW
40
50
60
70
Boiler Output kW (maximum) non condensing 80/60°C - kW
36.1
45.1
54.1
63.2
Boiler Output (minimum) 80/60°C
- kW
7.2
9.0
10.8
12.6
F85W
F100W
F125W
F150W
Boiler Input (maximum)
- kW (Gross)
87.2
102.6
128.2
153.8
Boiler Input (maximum)
- kW (Nett)
78.5
92.4
115.5
138.6
Boiler Output kW (maximum) condensing 50/30°C
- kW
85
100
125
150
Boiler Output kW (maximum) non condensing 80/60°C - kW
76.7
90.3
112.8
135.4
Boiler Output (minimum) 80/60°C
- kW
15.3
17.9
21.6
26.9
GAS DATA
F40W
F50W
F60W
F70W
Gas Inlet Connection Pipe Thread Size
R ¾”
R ¾”
R ¾”
R ¾”
Nominal Inlet Pressure Nat Gas
-mbar
20
Maximum Inlet Pressure Nat Gas
-mbar
25
Gas Pressure Switch Setting Nat Gas
-mbar
12.5
Gas Flow Rate (max. per module) Nat Gas -m
3
/h
3.9
4.8
5.8
6.8
Target CO
2
% at High / Low fire Nat Gas ±0.25%
9.0
Figure A1– Gas data
Содержание FLEET Series
Страница 2: ......
Страница 37: ...HAMWORTHY HEATING LTD 31 FLEET W series 500001211 F Figure 8 2 1 3 Operation and display philosophy ...
Страница 46: ...HAMWORTHY HEATING LTD 40 FLEET W series 500001211 F Figure 8 3 11 Operating phases ...
Страница 79: ...Please complete the information on the Registration card cut out and return to Hamworthy Heating Ltd ...
Страница 80: ......
Страница 81: ......