C1.3 Materials.
Materials used for the flue system must be mechanically robust, resistant to internal and external corrosion, non-
combustible and durable under the conditions to which they are likely to be subjected. Consideration must be
given to avoid possible freezing of condense water traps and pipe work.
C1.4 Suction
The flue system must be designed acknowledging that there is a positive pressure generated by the boiler combustion
fan. Refer to table Appendix C.
The flue system must be designed to limit the max. suction (cold) to 30Pa negative, measured at the connection to the
boiler. If the suction is greater than 30Pa, refer to HHL technical. This condition must then be checked hot and with all
boilers firing, the max. pressure at the connection to the boiler should be 150Pa positive.
In the event that the flue system when hot does generate a suction, the max. suction is 100Pa.
Any stabiliser fitted must be in or close to the vertical chimney.
C1.5 Disconnection
Provisions should be made for disconnection of the flue pipe for servicing. It is advisable that bends are fitted
with removable covers for inspection and cleaning as appropriate.
WARNING: THE FLUE SYSTEM MUST BE SELF SUPPORTING AND NOT PRESENT
A RISK TO PEOPLE IN OR AROUND THE BUILDING.
C1.6 Flue Discharge
The flue system must ensure safe and efficient operation of the boiler protecting the combustion process from
wind effects and dispersing the products of combustion to the external air. The flue must terminate in a freely
exposed position and be so situated as to prevent the products of combustion entering any opening in a building.
Where the flue diameter is less than 204mm (8”) diameter a terminal must be fitted. Where the flue is of a larger
size, consideration should be given to the fitting of a flue discharge terminal or grille to stop ingress of birds etc.
C1.7 Surface Temperatures
Combustible materials in the vicinity of the boiler and flue shall not
exceed 65°C during boiler operation. The flue shall not be closer
than 50mm to any combustible material, except where it passes
through such material with a non-combustible sleeve when the air
gap may not be less than 25mm.
C1.8 Location
The flue system must not be placed or fitted where there is undue
risk of accidental damage to the flue pipe or undue danger to
persons in the vicinity. Check that the flue and chimney are clear
from any obstruction. Fleet boilers are suitable for installation in a
balanced compartment in accordance with the requirements of BS
6644. Consult Hamworthy Heating Technical Department for help
or assistance if in doubt. For B23 applications the HHL air inlet
filter MUST be used to ensure the correct air inlet requirements.
Table C6.1 - Flue equivalent lengths
C1.9. Condensate Discharge
Due to the high thermal efficiency of the boiler, condensation will occur within the boiler casing during firing from
cold conditions. A drain with an integral trap is fitted to each module suitable for connection to a 40mm o.d.
plastic waste pipe (not Hamworthy Heating Ltd supply), which must be connected to a tundish (not Hamworthy
Heating Ltd supply). Discharge piping from a tundish should be of synthetic material due to the mild acidity of the
condensate (pH3-5), with all discharge piping having a minimum fall of 50mm/m away from the boiler.
Consideration should be given to possible freezing of condense water traps and pipe work. This must be avoided
at all times by routing pipe work within the building, where possible.
In addition to the above, should the plastic flue system supplied discharge into a metallic chimney system, any
condensate formed in the chimney MUST NOT drain back through the plastic components to the boiler. A
separate drain for the chimney system must be provided.
Flue
Flue
Equivalent
lengths
(m)
Load
kW
Ø
mm
Max
L
45°
90°
350
200
75
4
5
400
200
50
4
5
500
200
25
4
5
600
200
10
4
5
500
250
100
5
6.5
700
250
50
5
6.5
900
250
25
5
6.5
1050
300
50
6.0
8.0
900
300
75
6.0
8.0
Содержание F175V
Страница 2: ......
Страница 31: ...HAMWORTHY HEATING LTD 25 FLEET V series 500001217 D Figure 8 2 1 3 Operation and display philosophy...
Страница 40: ...HAMWORTHY HEATING LTD 34 FLEET V series 500001217 D Figure 8 3 11 Operating phases...
Страница 63: ...HAMWORTHY HEATING LTD 57 FLEET V series 500001217 D NOTES...
Страница 66: ...HAMWORTHY HEATING LTD 60 FLEET V series 500001217 D...
Страница 67: ......