8 CONTROLS OPERATION
visible on the display via the LMU programme. This
MUST
be carried out with the boiler running at
maximum
firing rate.
The 20°C
Δ
T condition across the boiler must be set as follows;
1
Run boiler at maximum rate.
2
Monitor flow temperature (displayed on main screen of HMI).
3
As boiler flow temperature rises, between 60°C & 80°C , press info button (to enter information mode) then
hold down up/down arrows for 3 seconds (to enter extended information mode) use + button to scroll to b1
which displays boiler return temperature.
4
Within the case, locate the ball valve on the return pipe of the boiler, and then adjust to give 20°C
differential between flow and return temperature. Opening the valve will decrease the differential/closing the
valve will increase the differential.
Press mode button to exit back to main screen and check flow temperature. It may be necessary to repeat the
sequence several times to ensure an accurate 20°C delta T is set.
Note.
E164 error code = flow switch interrupt (too little/no flow through boiler).
E154 error code = Delta T supervision active (too little flow through boiler).
7.8 User Instructions.
When the boiler is fully commissioned, the owner or their representative should be made aware of the lighting-up
and operating instructions. A practical demonstration should be given describing each functional step. This
Installation and Commissioning guide, the servicing instructions manual and the user’s instructions should then be
handed over and be kept in a safe place for future reference.
Figure 8.2 - System configuration of boiler control (LMU) & system peripherals
LMU
QAC34 ..
Roo m Thermostat
/ T ime Switch
RVA47
Bu ilding Automation /
Remote Management
Service Tool
OCI420
AGU2.50 0
AGU2.51xx
LPB
Clip-in
Auxiliary mod ules
0..10 V
4..20 mA
OCI /ACS
E
B
A
RVS controller
Содержание F175V
Страница 2: ......
Страница 31: ...HAMWORTHY HEATING LTD 25 FLEET V series 500001217 D Figure 8 2 1 3 Operation and display philosophy...
Страница 40: ...HAMWORTHY HEATING LTD 34 FLEET V series 500001217 D Figure 8 3 11 Operating phases...
Страница 63: ...HAMWORTHY HEATING LTD 57 FLEET V series 500001217 D NOTES...
Страница 66: ...HAMWORTHY HEATING LTD 60 FLEET V series 500001217 D...
Страница 67: ......