HAMWORTHY HEATING LTD
38
FLEET H series
500001216/D
Display
Meaning
Internal operating
phases of the LMU...
00
Standby (no demand for heat)
PH_STANDBY
01
Prevention of startup
PH_STARTVER
02 Fan
runup
PH_THL1_1
PH_THL1_2
03 Prepurging
PH_TV
04 Waiting
time
PH_TBRE
PH_TW1
PH_TW2
05 Preignition
time
PH_TVZ
06
Safety time, constant
PH_TSA1_1
PH_TSA2_1
07 Safety
time,
variable
PH_TSA1_2
PH_TSA2_2
10 Heating
operation
PH_TI
PH_MODULATION
Heating mode
11 DHW
operation
PH_TI
PH_MODULATION
DHW mode
12
Parallel operation of space heating and
DHW heating
PH_TI
PH_MODULATION
Heating and DHW
mode
20
Postpurging with the last control of
operation
PH_THL2_1
PH_TN_1
21
Postpurging with control of prepurging
PH_THL2_2
PH_TN_2
22 Home
run
PH_TNB
PH_TLO
PH_TNN
99
Lockout position (display of the current
error code)
PH_STOER
Note:
-If operating phases are passed very quickly or skipped, the relevant display
code will not appear.
Figure 8.3.12 - Operating phases
Содержание F175H
Страница 2: ......
Страница 30: ...HAMWORTHY HEATING LTD 24 FLEET H series 500001216 D Figure 8 2 1 1 Fascia Label Legend Keypad Display Screen ...
Страница 34: ...HAMWORTHY HEATING LTD 28 FLEET H series 500001216 D Figure 8 2 1 3 Operation and display philosophy ...
Страница 43: ...HAMWORTHY HEATING LTD 37 FLEET H series 500001216 D Figure 8 3 11 Operating phases ...
Страница 73: ...HAMWORTHY HEATING LTD 67 FLEET H series 500001216 D NOTES ...
Страница 76: ...HAMWORTHY HEATING LTD 70 FLEET H series 500001216 D ...
Страница 77: ......