HAMWORTHY HEATING LTD
4
FLEET H series
500001216/D
3.0
SIZE AND SPACE REQUIREMENTS
3.1 The Fleet boiler range has been designed to utilise minimum floor space, therefore it is important that the plant room
has sufficient ceiling height to allow for installation and connection to the flue system allowing for sufficient access at sides
and behind boiler for pipe work connections. See Figure 3.1
Figure 3.1.1 - Dimensions
750 crs
1300 min
clearance
700
450
700
B
A
32
0
C
83
0
74
c
rs
172
65
0
36
3
51
4
71
3
Front view
Plan view
Flue connection - F
Air inlet connection - G
Flow
Air inlet
Electric
Safety Valve
Gas
Condense
Return
274
570
638
650
50
40
0
40
0
Fleet H Series Boiler Model
A
950
65
25
110
275
1145
B
C
D
150
130
100
197
130
100
1100
1446
E
F
G
F/G -
for room sealed applications, kits
are available to adapt the flue and air
ducts to 130 or 150mm Ø .
note;
F175H
Dim.
F200H
F250H
F300H
F350H
140
D
E
Rear view
Side view
Flue removed for clarity
Содержание F175H
Страница 2: ......
Страница 30: ...HAMWORTHY HEATING LTD 24 FLEET H series 500001216 D Figure 8 2 1 1 Fascia Label Legend Keypad Display Screen ...
Страница 34: ...HAMWORTHY HEATING LTD 28 FLEET H series 500001216 D Figure 8 2 1 3 Operation and display philosophy ...
Страница 43: ...HAMWORTHY HEATING LTD 37 FLEET H series 500001216 D Figure 8 3 11 Operating phases ...
Страница 73: ...HAMWORTHY HEATING LTD 67 FLEET H series 500001216 D NOTES ...
Страница 76: ...HAMWORTHY HEATING LTD 70 FLEET H series 500001216 D ...
Страница 77: ......