HAMWORTHY HEATING LTD
57
FLEET H series
500001216/D
Figure C5.1 - Cascade
flue system 250mm Ø
Table C5.1 - Cascade Flue equivalent lengths - refer to fig. C5.1
Flue
Header
Flue
Header
Equivalent
lengths
(m)
‐
flue
pipe
Load
kW
Size
mm
Max
L
45°
90°
350
250
100
5
6.5
400
250
100
5
6.5
600
250
75
5
6.5
800
‐
Max
250
50
5
6.5
175
‐
350kW
(130/250mm)
Cascade
flue
kit
Extension
kit
HHL
Part
no
562511095
Options:
130Ø
*
1m
straight
‐
st/steel
532511220
250Ø
*
1m
straight
‐
st/steel
532511213
250Ø
87°
Elbow
‐
st/steel
532511208
250Ø
45°
Elbow
‐
st/steel
532511203
562511097
250/300Ø
Expander
‐
st/steel
532511224
300Ø
*
1m
straight
‐
st/steel
532511216
300Ø
87°
Elbow
‐
st/steel
532511209
300Ø
45°
Elbow
‐
st/steel
532511204
Flue
Header
Flue
Equivalent
lengths
(m)
‐
flue
pipe
Load
kW
Size
mm
Max
L
45°
90°
350
300
100
4
5
400
300
100
4
5
600
300
100
4
5
800
300
90
4
5
1000
300
50
4
5
1200
‐
Max
300
30
4
5
750 crs
15
00 m
in
.
225
300 min.
400 min.
140
Concentric Flue - Cuttable extension pieces
When cutting a concentric flue extension piece,
care must be taken to ensure that the inner section
is always cut 10mm longer than the outer section to
allow sections to be joined correctly.
Do not cut all the way through both sections at the
same length. Cut the outer section first and then
the inner section 10mm longer.
Содержание F175H
Страница 2: ......
Страница 30: ...HAMWORTHY HEATING LTD 24 FLEET H series 500001216 D Figure 8 2 1 1 Fascia Label Legend Keypad Display Screen ...
Страница 34: ...HAMWORTHY HEATING LTD 28 FLEET H series 500001216 D Figure 8 2 1 3 Operation and display philosophy ...
Страница 43: ...HAMWORTHY HEATING LTD 37 FLEET H series 500001216 D Figure 8 3 11 Operating phases ...
Страница 73: ...HAMWORTHY HEATING LTD 67 FLEET H series 500001216 D NOTES ...
Страница 76: ...HAMWORTHY HEATING LTD 70 FLEET H series 500001216 D ...
Страница 77: ......