HAMWORTHY HEATING LTD
25
FLEET W series
500001211/F
High Fire Target
Nat Gas - 9.0% ±0.25% CO
2
If combustion level is outside of this range use the
Cross Head Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.6.1- Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 7.6.3 - Adjusting gas valve offset
Models - F40W/ F50W/ F60W & F70W
Models - F85W/ F100W/ F125W & F150W
4. If combustion is outside of the ranges defined below the factory sealed valves may be adjusted using
the following procedure .
High Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion level is outside of this range use the
Cross Head Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.6.2 - Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 7.6.4 - Adjusting gas valve offset
Models - F40W/ F50W/ F60W & F70W
Models - F85W/ F100W/ F125W & F150W
Содержание F100W
Страница 2: ......
Страница 37: ...HAMWORTHY HEATING LTD 31 FLEET W series 500001211 F Figure 8 2 1 3 Operation and display philosophy...
Страница 46: ...HAMWORTHY HEATING LTD 40 FLEET W series 500001211 F Figure 8 3 11 Operating phases...
Страница 79: ...Please complete the information on the Registration card cut out and return to Hamworthy Heating Ltd...
Страница 80: ......
Страница 81: ......