HI200 Hampton Wood Cast Insert

8

Clearance diagram for installations

INSTALLATION

Side and Top facing is a maximum of 1.5" thick. 
Floor protection must non-combustible, insulative 
material with an R value of 1.1 or greater.

*

 

If the hearth extension is fl ush with the fl oor (F) 
it must extend 19.5" in front of the body face 
(E).

Note:  Hearth Extension Width (G) is meas-

ured from edge of fuel door to side of 
hearth.

**   A non-combustible mantel may be installed 

at a lower height if the framing is made of 
metal studs covered with a non-combustible 
board.

MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES 

The minimum required clearances to combustible materials when installed into a masonry or factory built fi replace are listed below. 

 

                     Adjacent            Mantle**                 Top                    Side                       Minimum                 Minimum 

      Minimum

                          Side Wall           (to Top)                Facing               Facing                       Hearth                      Hearth 

      Hearth Side

 

                     (to Side)                                        (to Top)            (to Side)                   Extension               Thickness* 

     Extension

 

                          A                        B                           C                       D                                E                              F   

     G

 

     

           15" (381mm)  20" (508mm)  14" (356mm)   7-3/8"(187mm)   16" (406mm) [US]    1-1/2" (38mm)   6" (152mm) [US]

 

 

 

 

                              18" (457mm) [CAN]                            8" (203mm) [CAN] 

A

B

C

D

G

F

E

HOW TO DETERMINE IF ALTERNATE

FLOOR PROTECTION MATERIALS ARE ACCEPTABLE

The specifi ed  fl oor protector should be 3/8" 
(18mm) thick material with a K - factor of 
0.84.

The proposed alternative is 4" (100mm) brick 
with a C-factor of 1.25 over 1/8" (3mm) mineral 
board with a K-factor of 0.29.

Step (a): 

 

Use formula above to convert specifi cation 
to R-value.

 

R = 1/k x T = 1/0.84 x .75 = 0.893.

Step (b): 

 

Calculate R of proposed system.

 

4" brick of C = 1.25, therefore

 

Rbrick = 1/C = 1/1.25 = 0.80

 

1/8" mineral board of k = 0.29, therefore 
Rmin.bd. = 1/0.29 x 0.125 = 0.431

 

Total R = Rmineral board =

 

0.8 + 0.431 = 1.231.

Step (c): 

 

Compare proposed system R of 1.231 to 
specifi ed R of 0.893. Since proposed system 
R is greater than required, the system is 
acceptable.

DEFINITIONS

 

Thermal Conductance:

 

 

=         Btu  

=          W

                    (hr)(ft

2  

)(

o

F)                 (m

2)

)(K)

   

Thermal Conductivity:

 

k  =  (Btu)(inch)    =     W      =     Btu

 

 (hr)(ft

3

)(

o

F)            (m)(K)       (hr)(ft)(

o

F)

 

Thermal Resistance:

 

R   = (ft

2

)(hr)(

o

F)      =      (m

2

)(K)

 

  

    Btu 

         W

 

Floor Protection

Please check to ensure that your fl oor protection and hearth will meet the standards for clear-
ance to combustibles. Your hearth extension must be made from a non-combustible material.

Thermal fl oor protection is not required if the unit is 
raised 3.5" minimum (measured from the bottom of 
the stove). However, standard ember fl oor protection 
is required. It will need to be a non-combustible mate-
rial that covers 16"  (406 mm) in the US and 18" (450 
mm) in Canada to the front of the unit and 8" (200 
mm) to the sides.

If the unit is not raised, thermal fl oor protection required 
is 18" (450 mm) in the US and Canada.

Содержание Wood Insert HI200

Страница 1: ...da V4G 1H4 918 739b HI200 Wood Cast Insert 07 19 11 Owner s Installation Manual Tested by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Ple...

Страница 2: ...MPTON DEALER in your area Keep those HAMPTON FIRES burning SAFETY NOTE If this Insert is not properly installed a house fire may result For your safety follow the installation instructions contact loc...

Страница 3: ...ace 11 Installation Into a Masonry Fireplace 11 Fan Cast Faceplate Installation 12 Brick Flue Baffle Secondary Air Tube Installation 14 Firebrick Assembly 14 Draft Control 14 First Fire 15 Fan Operati...

Страница 4: ...PROTECTION AGENCY CERTIFIED TO COMPLY WITH JULY 1990 PARTICULATE EMISSION STANDARDS JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC 2011 2012 2013 Duplicate Serial MADE IN CANADA 339 DATE OF MANUFAC...

Страница 5: ...nsert use these dimensions to en sure appropriate clearances will be met refer to Masonry and Factory Built Fireplace Clearances section UNIT DIMENSIONS WITH STANDARD FLUE ADAPTOR 6 152mm Diameter STA...

Страница 6: ...9 9 16 4 9 16 15 1 16 6 3 8 14 1 8 25 NOTE BeforeassemblingyourInsert use these dimensions to en sure appropriate clearances will be met refer to Masonry and Factory Built Fireplace Clearances section...

Страница 7: ...lling and using your fireplace insert Install and use only in accordance with manufacturer s installation and operating instructions 2 Check your local building codes Build ing Inspection Department Y...

Страница 8: ...ial with a K factor of 0 84 The proposed alternative is 4 100mm brick with a C factor of 1 25 over 1 8 3mm mineral board with a K factor of 0 29 Step a Use formula above to convert specification to R...

Страница 9: ...daptor using 3 screws 1 in the front and 1 each on the left and right side Flex Liner Diagram 1 Your insert is very heavy and will require two or three people to move it into position 1 Remove the Doo...

Страница 10: ...wn in diagram 4 While sliding the unit into place pull on the rod to ensure that the flue adaptor is properly engaged See diagram 5 Pull Rod 10 Ensure that the unit is still level 11 To complete the i...

Страница 11: ...spection authority Three methods of flue connection are acceptable in most areas these include 1 Positive flue connection where a large blocking plate and a short connector pipe is used 2 Direct flue...

Страница 12: ...unting Bracket Mounting Bracket Gasket Gasket 2 Slide the unit into position leaving partially out to allow for installation of the left and right side surrounds 3 Install the left and right side surr...

Страница 13: ...g temperature or at least 30 minutes after starting fire 8 Surround adjustments can be made up or down loosen 4 bolts shown on face of unit Diagram 7 and adjust Surround can also be adjusted left or r...

Страница 14: ...talltheairtubeintotheholesinthe side channels The notch goes on the right hand side with the air holes facing toward the door Slide the tube into the left hand side asfaraspossibleandthenbringitback i...

Страница 15: ...nced during the heating up process Thesenoiseswillbeminimalwhenyourunit reaches temperature 12 Before opening your door to reload open draftfullyforapproximately10to15seconds until fire has been re es...

Страница 16: ...of by burial in soil or otherwise locally dispersed they should be retained in the closedcontaineruntilallcindershavethoroughly cooled Other waste should not be placed in the ash container SOME SAFETY...

Страница 17: ...ure that the glass gasketing will properly seal your unit 5 Re install the glass retainer Ensure that it rests on the gasket and not the glass 6 Secure glass retainer using the 4 screws Do not wrench...

Страница 18: ...justment as the door gasket material com presses over time Removal of spacers will allow the latch to be moved closer to the door frame causing a tighter seal 1 Remove the Latch Assembly from the unit...

Страница 19: ...ch by undoing the inner 2 bolts Adjust to desired location and retighten the 2 bolts make sure the door catch closes freely and makes a good seal Do a paper test to confirm seal Latch Assembly Latch A...

Страница 20: ...Density Door Gasket Kit 20 210 911 Fan Blower Assembly Metallic Black 210 915 Fan Blower Assembly Timberline Brown 910 157 P Blower Fan Motor 910 684 Power Cord 120 Volts 910 142 Fan Thermodisc 910 14...

Страница 21: ...ast Insert 21 CAST FACEPLATE Part Description 210 921 Metallic Black Faceplate 210 925 Timberline Brown Faceplate 1 Top Surround 2 Left Side Surround 3 Right Side Faceplate Not available as a replacem...

Страница 22: ...t Description 170 960 Complete Brick Set 70 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 76 Brick Partial 1 1 4 x 2 x 9 81 Brick Partial 1 1 4 x 1 1 4 x 9 84 Brick Partial 1 1 4 x 4 1 2 x 8 85 Brick Part...

Страница 23: ...days of installation Reported damage after this time will be subject to rejection Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FP...

Страница 24: ...__________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No ___________________________________...

Отзывы: